Chapter 9 Roof Assemblies

Section R901 General

R901.1 Scope.

The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies.

Section R902 Fire Classification

R902.1 Roof assemblies.

Roof decks shall be covered with materials as set forth in Section R904 or with roof coverings as set forth in Section R905. Class A, B or C roof assemblies shall be installed in jurisdictions designated by law as requiring their use or where the edge of the roof deck is less than 3 feet (914 mm) from a lot line. Where Class A, B or C roof assemblies are required, they shall be tested in accordance with ASTM E108 or UL 790. Where required, the roof assembly shall be listed and identified as to class by an approved testing agency.

Exceptions:

  1. 1.

    Class A roof assemblies include those with coverings of brick, masonry and exposed concrete roof deck.

  2. 2.

    Class A roof assemblies include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile, or slate installed on noncombustible roof decks.

  3. 3.

    Class A roof assemblies include minimum 16 ounces per square foot (4.882 kg/m2) copper sheets installed over combustible roof decks.

  4. 4.

    Class A roof assemblies include slate installed over underlayment over combustible roof decks.

R902.2 Fire-retardant-treated shingles and shakes.

Fire-retardant-treated wood shakes and shingles shall be treated by impregnation with chemicals by the full-cell vacuum-pressure process, in accordance with AWPA C1. Each bundle shall be marked to identify the manufactured unit and the manufacturer, and shall be labeled to identify the classification of the material in accordance with the testing required in Section R902.1, the treating company and an approved agency.

R902.3 Building-integrated photovoltaic (BIPV) systems.

Building-integrated photovoltaic (BIPV) systems installed as the roof covering shall be tested, listed and labeled for fire classification in accordance with UL 7103. Class A, B or C BIPV products shall be installed where the edge of the roof is less than 3 feet (914 mm) from a lot line.

R902.4 Rooftop-mounted photovoltaic panel systems.

Rooftop-mounted photovoltaic panel systems installed on or above the roof covering shall be tested, listed and identified with a fire classification in accordance with UL 2703. Class A, B or C photovoltaic panel systems and modules shall be installed in jurisdictions designated by law as requiring their use or where the edge of the roof is less than 3 feet (914 mm) from a lot line.

Section R903 Weather Protection

R903.1 General.

Roof decks shall be covered with approved roof coverings secured to the building or structure in accordance with the provisions of this chapter. Roof assemblies shall be designed and installed in accordance with this code and the approved manufacturer’s instructions such that the roof assembly shall serve to protect the building or structure.

R903.2 Flashing.

Flashings shall be installed in a manner that prevents moisture from entering the wall and roof through joints in copings, through moisture permeable materials and at intersections with parapet walls and other penetrations through the roof plane.

R903.2.1 Locations.

Flashings shall be installed at wall and roof intersections, wherever there is a change in roof slope or direction and around roof openings. A flashing shall be installed to divert the water away from where the eave of a sloped roof intersects a vertical sidewall. Where flashing is of metal, the metal shall be corrosion resistant with a thickness of not less than 0.019 inch (0.5 mm) (No. 26 galvanized sheet).

R903.2.2 Crickets and saddles.

A cricket or saddle shall be installed on the ridge side of any chimney or penetration more than 30 inches (762 mm) wide as measured perpendicular to the slope. Cricket or saddle coverings shall be sheet metal or of the same material as the roof covering.

Exception: Unit skylights installed in accordance with Section R324.6 and flashed in accordance with the manufacturer’s instructions shall be permitted to be installed without a cricket or saddle.

R903.3 Coping.

Parapet walls shall be properly coped with noncombustible, weatherproof materials of a width not less than the thickness of the parapet wall.

R903.4 Roof drainage.

Unless roofs are sloped to drain over roof edges, roof drains shall be installed at each low point of the roof.

R903.4.1 Secondary (emergency overflow) drains or scuppers.

Where roof drains are required, secondary emergency overflow roof drains or scuppers shall be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason. Overflow drains having the same size as the roof drains shall be installed with the inlet flow line located 2 inches (51 mm) above the low point of the roof, or overflow scuppers having three times the size of the roof drains and having a minimum opening height of 4 inches (102 mm) shall be installed in the adjacent parapet walls with the inlet flow located 2 inches (51 mm) above the low point of the roof served. The installation and sizing of overflow drains, leaders and conductors shall comply with Sections 1106 and 1108 of the International Plumbing Code, as applicable.

Overflow drains shall discharge to an approved location and shall not be connected to roof drain lines.

Section R904 Materials

R904.1 Scope.

The requirements set forth in this section shall apply to the application of roof covering materials specified herein. Roof assemblies shall be applied in accordance with this chapter and the manufacturer’s installation instructions. Installation of roof assemblies shall comply with the applicable provisions of Section R905.

R904.2 Compatibility of materials.

Roof assemblies shall be of materials that are compatible with each other and with the building or structure to which the materials are applied.

R904.3 Material specifications and physical characteristics.

Roof covering materials shall conform to the applicable standards listed in this chapter.

R904.4 Product identification.

Roof covering materials shall be delivered in packages bearing the manufacturer’s identifying marks and approved testing agency labels required. Bulk shipments of materials shall be accompanied by the same information issued in the form of a certificate or on a bill of lading by the manufacturer.

Section R905 Requirements for Roof Coverings

R905.1 Roof covering application.

Roof coverings shall be applied in accordance with the applicable provisions of this section and the manufacturer’s installation instructions. Unless otherwise specified in this section, roof coverings shall be installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

R905.1.1 Underlayment.

Underlayment in accordance with this section is required for asphalt shingles, clay and concrete tile, metal roof shingles, mineral-surfaced roll roofing, slate and slate-type shingles, wood shingles, wood shakes, metal roof panels and building-integrated photovoltaic (BIPV) roof coverings shall conform to the applicable standards listed in this chapter. Underlayment materials required to comply with ASTM D226; D1970; D2626; D4869; D6380, Class M; D6757; or D8257 shall bear a label indicating compliance to the standard designation and, if applicable, type classification indicated in Table R905.1.1(1). Underlayment shall be applied in accordance with Table R905.1.1(2). Underlayment shall be fastened in accordance with Table R905.1.1(3).

Exception: Structural metal panels that do not require a substrate or underlayment.

TABLE R905.1.1(1) UNDERLAYMENT TYPES

ROOF COVERING

SECTION

AREAS WHERE WIND DESIGN IS NOT REQUIRED IN ACCORDANCE WITH FIGURE R301.2.1.1

AREAS WHERE WIND DESIGN IS REQUIRED IN ACCORDANCE WITH FIGURE R301.2.1.1

Asphalt shingles

R905.2

ASTM D226 Type I or II
ASTM D1970
ASTM D4869 Type I, II, III or IV
ASTM D6757
ASTM D8257

ASTM D226 Type II
ASTM D1970
ASTM D4869 Type III or IV
ASTM D8257

Clay and concrete tile

R905.3

ASTM D226 Type II
ASTM D1970
ASTM D2626
ASTM D6380 Class M
ASTM D8257

ASTM D226 Type II
ASTM D1970
ASTM D8257

Metal roof shingles

R905.4

ASTM D226 Type I or II
ASTM D1970
ASTM D4869 Type I, II, III or IV
ASTM D8257

ASTM D226 Type II
ASTM D1970
ASTM D4869 Type III or IV
ASTM D8257

Mineral-surfaced roll roofing

R905.5

ASTM D226 Type I or II
ASTM D1970
ASTM D4869 Type I, II, III or IV
ASTM D8257

ASTM D226 Type II
ASTM D1970
ASTM D4869 Type III or IV
ASTM D8257

Slate and slate-type shingles

R905.6

ASTM D226 Type I
ASTM D1970
ASTM D4869 Type I, II, III or IV
ASTM D8257

ASTM D226 Type II
ASTM D1970
ASTM D4869 Type III or IV
ASTM D8257

Wood shingles

R905.7

ASTM D226 Type I or II
ASTM D4869 Type I, II, III or IV

ASTM D226 Type II
ASTM D4869 Type III or IV

Wood shakes on solid sheathing

R905.8

ASTM D226 Type I or II
ASTM D4869 Type I, II, III or IV

ASTM D226 Type II
ASTM D4869 Type III or IV

Metal panels on solid sheathing

R905.10

ASTM D226 Type I or II
ASTM D4869 Type I, II III or IV

ASTM D226 Type II
ASTM D1970
ASTM D4869 Type III or IV
ASTM D8257

BIPV roof coverings

R905.15

ASTM D226 Type I or II
ASTM D1970

ASTM D4869 Type I, II, III or IV
ASTM D6757
ASTM D8257

ASTM D226 Type II
ASTM D1970

ASTM D4869 Type III or IV
ASTM D8257

For SI: 1 mile per hour = 0.447 m/s.

TABLE R905.1.1(2) UNDERLAYMENT APPLICATION

ROOF COVERING

SECTION

AREAS WHERE WIND DESIGN IS NOT REQUIRED IN ACCORDANCE WITH FIGURE R301.2.1.1

AREAS WHERE WIND DESIGN IS REQUIRED IN ACCORDANCE WITH FIGURE R301.2.1.1

Asphalt shingles

R905.2

Underlayment shall be one of the following:

  1. 1.

    For roof slopes from 2 units vertical in 12 units horizontal (2:12), up to 4 units vertical in 12 units horizontal (4:12), underlayment shall be two layers applied in the following manner: apply a strip of underlayment that is half the width of a full sheet parallel to and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply fullwidth sheets of underlayment, overlapping successive sheets half the width of a full sheet plus 2 inches. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

  2. 2.

    For roof slopes of 4 units vertical in 12 units horizontal (4:12) or greater, underlayment shall be one layer applied in the following manner: underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 2 inches. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

  3. 3.

    A single layer of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the underlayment and roof covering manufacturer’s installation instructions for the deck material, roof ventilation configuration and climate exposure of the roof covering.

Underlayment shall be one of the following:

  1. 1.

    Two layers of mechanically fastened underlayment applied in the following manner: Apply a strip of underlayment that is half the width of a full sheet parallel to and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply full-width sheets of underlayment, overlapping successive sheets half the width of a full sheet plus 2 inches. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

  2. 2.

    A minimum 4-inch-wide strip of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the manufacturer’s installation instructions for the deck material, shall be applied over all joints in the roof decking. An approved underlayment complying with Table R905.1.1(1) for the applicable roof covering shall be applied over the entire roof over the 4-inch- wide membrane strips.

  3. 3.

    A single layer of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the underlayment and roof covering manufacturer’s installation instructions for the deck material, roof ventilation configuration and climate exposure of the roof covering.

Clay and concrete tile

R905.3

Underlayment shall be one of the following:

  1. 1.

    For roof slopes from 2 1/2 units vertical in 12 units horizontal (2 1/2:12), up to 4 units vertical in 12 units horizontal (4:12), underlayment shall be two layers applied in the following manner: apply a strip of underlayment that is half the width of a full sheet parallel to and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply fullwidth sheets of underlayment, overlapping successive sheets half the width of a full sheet plus 2 inches. End laps shall be 4 inches and shall be offset by 6 feet.

  2. 2.

    For roof slopes of 4 units vertical in 12 units horizontal (4:12) or greater, underlayment shall be one layer applied in the following manner: underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 2 inches. End laps shall be 4 inches and shall be offset by 6 feet.

  3. 3.

    A single layer of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the underlayment and roof covering manufacturer’s installation instructions for the deck material, roof ventilation configuration and climate exposure of the roof covering.

Underlayment shall be one of the following:

  1. 1.

    Two layers of mechanically fastened underlayment applied in the following manner: Apply a strip of underlayment felt that is half the width of a full sheet parallel to and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply full width sheets of underlayment, overlapping successive sheets half the width of a full sheet plus 2 inches. Distortionsin the underlayment shall not interferewith the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

  2. 2.

    A minimum 4-inch-wide strip of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the manufacturer’s installation instructions for the deck material, shall be applied over all joints in the roof decking. An approved underlayment complying with Table R905.1.1(1) for the applicable roof covering shall be applied over the entire roof over the 4-inch-wide membrane strips.

  3. 3.

    A single layer of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the underlayment and roof covering manufacturer’s installation instructions for the deck material, roof ventilation configuration and climate exposure of the roof covering.

Metal roof shingles

R905.4

Apply in accordance with the manufacturer’s installation instructions.

Underlayment shall be one of the following:

  1. 1.

    Two layers of mechanically fastened underlayment applied in the following manner: Apply a strip of underlayment that is half the width of a full sheet parallel to and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply full width sheets of underlayment, overlapping successive sheets half the width of a full sheet plus 2 inches. End laps shall be 4 inches and shall be offset by 6 feet.

  2. 2.

    A minimum 4-inch-wide strip of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the manufacturer’s installation instructions for the deck material, shall be applied over all joints in the roof decking. An approved underlayment complying with Table R905.1.1(1) for the applicable roof covering shall be applied over the entire roof over the 4-inch-wide membrane strips.

  3. 3.

    A single layer of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the underlayment and roof covering manufacturer’s installation instructions for the deck material, roof ventilation configuration and climate exposure of the roof covering.

Mineral-surfaced roll roofing

R905.5

Slate and slate-type shingles

R905.6

Wood shingles

R905.7

Wood shakes

R905.8

Metal panels

R905.10

BIPV roof coverings

R905.15

Underlayment shall be one of the following:

  1. 1.

    For roof slopes from 2 units vertical in 12 units horizontal (2:12), up to 4 units vertical in 12 units horizontal (4:12), underlayment shall be two layers applied in the following manner: apply a strip of underlayment that is half the width of a full sheet parallel to and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply full width sheets of underlayment, overlapping successive sheets half the width of a full sheet plus 2 inches. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

  2. 2.

    For roof slopes of 4 units vertical in 12 units horizontal (4:12) or greater, underlayment shall be one layer applied in the following manner: underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 2 inches. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

  3. 3.

    A single layer of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the underlayment and roof covering manufacturer’s installation instructions for the deck material, roof ventilation configuration and climate exposure of the roof covering.

Underlayment shall be one of the following:

  1. 1.

    Two layers of mechanically fastened underlayment applied in the following manner: Apply a strip of underlayment that is half the width of a full sheet parallel to and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply full width sheets of underlayment, overlapping successive sheets half the width of a full sheet plus 2 inches. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

  2. 2.

    A minimum 4-inch-wide strip of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the manufacturer’s installation instructions for the deck material, shall be applied over all joints in the roof decking. An approved underlayment complying with Table R905.1.1(1) for the applicable roof covering shall be applied over the entire roof over the 4-inch-wide membrane strips.

  3. 3.

    A single layer of self-adhering polymer modified bitumen underlayment complying with ASTM D1970, installed in accordance with the underlayment and roof covering manufacturer’s installation instructions for the deck material, roof ventilation configuration and climate exposure of the roof covering.

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.

TABLE R905.1.1(3) UNDERLAYMENT ATTACHMENT

ROOF COVERING

SECTION

AREAS WHERE WIND DESIGN IS NOT REQUIRED IN ACCORDANCE WITH FIGURE R301.2.1.1

AREAS WHERE WIND DESIGN IS REQUIRED IN ACCORDANCE WITH FIGURE R301.2.1.1

Asphalt shingles

R905.2

Fastened sufficiently to hold in place

Mechanically fastened underlayment shall be fastened with corrosion-resistant fasteners in a grid pattern of 12 inches between side laps with a 6-inch spacing at side and end laps. Underlayment shall be attached using annular ring or deformed shank nails with 1-inch-diameter metal or plastic caps. Metal caps shall have a thickness of not less than 32-gage sheet metal. Powerdriven metal caps shall have a minimum thickness of 0.010 inch. Minimum thickness of the outside edge of plastic caps shall be 0.035 inch. The cap nail shank shall be not less than 0.083 inch. The cap nail shank shall have a length sufficient to penetrate through the roof sheathing or not less than 3/4 inch into the roof sheathing.

Self-adhering polymer modified bitumen underlayment shall be installed in accordance with the underlayment and roof covering manufacturers’ installation instructions for the deck material, roof ventilation configuration, and climate exposure of the roof covering.

Clay and concrete tile

R905.3

BIPV roof covering

R905.15

Metal roof shingles

R905.4

Manufacturer’s installation instructions.

Mechanically fastened underlayment shall be fastened with corrosion-resistant fasteners in a grid pattern of 12 inches between side laps with a 6-inch spacing at side and end laps. Underlayment shall be attached using annular ring or deformed shank nails with 1-inch-diameter metal or plastic caps. Metal caps shall have a thickness of not less than 32-gage sheet metal. Powerdriven metal caps shall have a minimum thickness of 0.010 inch. Minimum thickness of the outside edge of plastic caps shall be 0.035 inch. The cap nail shank shall be not less than 0.083 inch. The cap nail shank shall have a length sufficient to penetrate through the roof sheathing or not less than 3/4 inch into the roof sheathing.

Self-adhering polymer modified bitumen underlayment shall be installed in accordance with the underlayment and roof covering manufacturers’ installation instructions for the deck material, roof ventilation configuration and climate exposure of the roof covering.

Exception: Self-adhering polymer modified bitumen underlayment shall not be installed under wood shakes or wood shingles.

Mineral-surfaced roll roofing

R905.5

Slate and slate-type shingles

R905.6

Wood shingles

R905.7

Wood shakes

R905.8

Metal panels

R905.10

For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.

R905.1.2 Ice barriers.

In areas where there has been a history of ice forming along the eaves causing a backup of water as designated in Table R301.2, an ice barrier shall be installed for asphalt shingles, metal roof shingles, mineral-surfaced roll roofing, slate and slate-type shingles, wood shingles and wood shakes. The ice barrier shall consist of not fewer than two layers of underlayment cemented together, or a self-adhering polymer-modified bitumen sheet shall be used in place of normal underlayment and extend from the lowest edges of all roof surfaces to a point not less than 24 inches (610 mm) inside the exterior wall line of the building.

On roofs with slope equal to or greater than 8 units vertical in 12 units horizontal (67 percent slope), the ice barrier shall be applied not less than 36 inches (914 mm) measured along the roof slope from the eave edge of the building.

Exception: Detached accessory structures not containing conditioned floor area.

R905.2 Asphalt shingles.

The installation of asphalt shingles shall comply with the provisions of this section.

R905.2.1 Sheathing requirements.

Asphalt shingles shall be fastened to wood structural panels or solid lumber sheathing.

R905.2.2 Slope.

Asphalt shingles shall be used only on roof slopes of 2 units vertical in 12 units horizontal (17 percent slope) or greater. For roof slopes from 2 units vertical in 12 units horizontal (17 percent slope) up to 4 units vertical in 12 units horizontal (33 percent slope), double underlayment application is required in accordance with Section R905.1.1.

R905.2.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.2.4 Asphalt shingles.

Asphalt shingles shall comply with ASTM D3462.

R905.2.4.1 Wind resistance of asphalt shingles.

Asphalt shingles shall be tested in accordance with ASTM D7158. Asphalt shingles shall meet the classification requirements of Table R905.2.4.1 for the appropriate ultimate design wind speed. Asphalt shingle packaging shall bear a label to indicate compliance with ASTM D7158 and the required classification in Table R905.2.4.1.

Exception: Asphalt shingles not included in the scope of ASTM D7158 shall be tested and labeled in accordance with ASTM D3161. Asphalt shingle packaging shall bear a label to indicate compliance with ASTM D3161 and the required classification in Table R905.2.4.1.

TABLE R905.2.4.1 CLASSIFICATION OF ASPHALT ROOF SHINGLES

MAXIMUM ULTIMATE DESIGN WIND SPEED, Vult FROM Figure R301.2(2) (mph)

MAXIMUM BASIC WIND SPEED, V ASD FROM TABLE R301.2.1.3 (mph)

ASTM D7158 a SHINGLE CLASSIFICATION

ASTM D3161 SHINGLE CLASSIFICATION

110

85

D, G or H

A, D or F

116

90

D, G or H

A, D or F

129

100

G or H

A, D or F

142

110

G or H

F

155

120

G or H

F

168

130

H

F

181

140

H

F

194

150

H

F

For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.

  1. a.

    The standard calculations contained in ASTM D7158 assume Exposure Category B or C and a building height of 60 feet or less. Additional calculations are required for conditions outside of these assumptions.

R905.2.5 Fasteners.

Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum 3/8-inch-diameter (9.5 mm) head, complying with ASTM F1667, of a length to penetrate through the roofing materials and not less than 3/4 inch (19.1 mm) into the roof sheathing. Where the roof sheathing is less than 3/4 inch (19.1 mm) thick, the fasteners shall penetrate through the sheathing.

R905.2.6 Attachment.

Asphalt shingles shall have the minimum number of fasteners required by the manufacturer’s approved installation instructions, but not less than four fasteners per strip shingle or two fasteners per individual shingle. Where the roof slope exceeds 21 units vertical in 12 units horizontal (21:12, 175 percent slope), shingles shall be installed in accordance with the manufacturer’s approved installation instructions.

R905.2.7 Ice barrier.

Where required, ice barriers shall comply with Section R905.1.2.

R905.2.8 Flashing.

Flashing for asphalt shingles shall comply with this section and the asphalt shingle manufacturer’s approved installation instructions.

R905.2.8.1 Base and cap flashing.

Base and cap flashing shall be installed in accordance with manufacturer’s instructions. Base flashing shall be of either corrosion-resistant metal of minimum nominal 0.019-inch (0.5 mm) thickness or mineral-surfaced roll roofing weighing not less than 77 pounds per 100 square feet (4 kg/m2). Cap flashing shall be corrosion-resistant metal of minimum nominal 0.019-inch (0.5 mm) thickness.

R905.2.8.2 Valleys.

Valley linings shall be installed in accordance with the manufacturer’s instructions before applying shingles. Valley linings of the following types shall be permitted:

  1. 1.

    For open valleys (valley lining exposed) lined with metal, the valley lining shall be not less than 24 inches (610 mm) wide and of any of the corrosion-resistant metals in Table R905.2.8.2.

  2. 2.

    For open valleys, valley lining of two plies of mineral-surfaced roll roofing, complying with ASTM D3909 or ASTM D6380 Class M, shall be permitted. The bottom layer shall be 18 inches (457 mm) and the top layer not less than 36 inches (914 mm) wide.

  3. 3.

    For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D6380 and not less than 36 inches wide (914 mm) or valley lining as described in Item 1 or 2 shall be permitted. Self-adhering polymer-modified bitumen underlayment complying with ASTM D1970 and not less than 36 inches (914 mm) wide shall be permitted in lieu of the lining material.

TABLE R905.2.8.2 VALLEY LINING MATERIAL

MATERIAL

MINIMUM THICKNESS (inches)

GAGE

WEIGHT (pounds)

Aluminum

0.024

Cold-rolled copper

0.0216 nominal

ASTM B370, 16 oz. per square foot

Galvanized steel

0.0179

26 (zinc-coated G90)

High-yield copper

0.0162 nominal

ASTM B370, 12 oz. per square foot

Lead

2 1/2

Lead-coated copper

0.0216 nominal

ASTM B101, 16 oz. per square foot

Lead-coated high-yield copper

0.0162 nominal

ASTM B101, 12 oz. per square foot

Painted terne

20

Stainless steel

28

Zinc alloy

0.027

For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg, 1 square foot = 0.93 m2.

R905.2.8.3 Sidewall flashing.

Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches (102 mm) in width and shall direct water away from the vertical sidewall onto the roof or into the gutter. Where siding is provided on the vertical sidewall, the vertical leg of the flashing shall be continuous under the siding. Where anchored masonry veneer is provided on the vertical sidewall, the base flashing shall be provided in accordance with this section and counterflashing shall be provided in accordance with Section R703.8.2.2. Where exterior plaster or adhered masonry veneer is provided on the vertical sidewall, the base flashing shall be provided in accordance with this section and Section R703.7.3.

R905.2.8.4 Other flashing.

Flashing against a vertical front wall, as well as soil stack, vent pipe and chimney flashing, shall be applied in accordance with the asphalt shingle manufacturer’s instructions.

R905.2.8.5 Drip edge.

A drip edge shall be provided at eaves and rake edges of shingle roofs. Adjacent segments of drip edge shall be overlapped not less than 2 inches (51 mm). Drip edges shall extend not less than 1/4 inch (6.4 mm) below the roof sheathing and extend up back onto the roof deck not less than 2 inches (51 mm). Drip edges shall be mechanically fastened to the roof deck at not more than 12 inches (305 mm) o.c. with fasteners as specified in Section R905.2.5. Underlayment shall be installed over the drip edge along eaves and under the drip edge along rake edges.

R905.3 Clay and concrete tile.

The installation of clay and concrete tile shall comply with the provisions of this section.

R905.3.1 Sheathing requirements.

Concrete and clay tile shall be installed over wood structural panels or solid lumber sheathing.

Exception: Spaced lumber sheathing in accordance with Section R803.1 shall be permitted in Seismic Design Categories A, B and C.

R905.3.2 Slope.

Clay and concrete roof tile shall be installed on roof slopes of 2 1/2 units vertical in 12 units horizontal (25 percent slope) or greater. For roof slopes from 2 1/2 units vertical in 12 units horizontal (25 percent slope) to 4 units vertical in 12 units horizontal (33 percent slope), double underlayment application is required in accordance with Section R905.3.3.

R905.3.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.3.4 Clay tile.

Clay roof tile shall comply with ASTM C1167.

R905.3.5 Concrete tile.

Concrete roof tile shall comply with ASTM C1492.

R905.3.6 Wind resistance of concrete and clay tile.

In regions where wind design is required in accordance with Figure R301.2.1.1, wind loads on concrete and clay tile shall be determined in accordance with Section 1504.3 of the International Building Code. In regions where wind design is not required in accordance with Figure R301.2.1.1, concrete and clay tiles shall be attached in accordance with Sections R905.3.8 and R905.3.9.

R905.3.7 Fasteners.

Nails shall be corrosion resistant and not less than 11-gage [0.120 inch (3 mm)], 5/16-inch (11 mm) head, and of sufficient length to penetrate the roof deck not less than 3/4 inch (19 mm) or through the thickness of the roof deck, whichever is less. Attaching wire for clay or concrete tile shall not be smaller than 0.083 inch (2 mm). Perimeter fastening areas include three tile courses but not less than 36 inches (914 mm) from either side of hips or ridges and edges of eaves and gable rakes.

R905.3.8 Application.

Tile shall be applied in accordance with this chapter and the manufacturer’s installation instructions, based on the following:

  1. 1.

    Climatic conditions.

  2. 2.

    Roof slope.

  3. 3.

    Underlayment system.

  4. 4.

    Type of tile being installed.

Clay and concrete roof tiles shall be fastened in accordance with this section and the manufacturer’s installation instructions. Perimeter tiles shall be fastened with not less than one fastener per tile. Tiles with installed weight less than 9 pounds per square foot (0.4 kg/m2) require not less than one fastener per tile regardless of roof slope. Clay and concrete roof tile attachment shall be in accordance with the manufacturer’s installation instructions where applied in areas where the ultimate design wind speed exceeds 130 miles per hour (58 m/s) and on buildings where the roof is located more than 40 feet (12 192 mm) above grade. In areas subject to snow, not less than two fasteners per tile are required. In other areas, clay and concrete roof tiles shall be attached in accordance with Table R905.3.8.

TABLE R905.3.8 CLAY AND CONCRETE TILE ATTACHMENT

SHEATHING

ROOF SLOPE

NUMBER OF FASTENERS

Solid without battens

All

One per tile

Spaced or solid with battens

Slope < 5:12

Fasteners not required

Spaced sheathing without battens

5:12 ≤ slope < 12:12

One per tile/every other row

12:12 ≤ slope < 24:12

One per tile

R905.3.9 Flashing.

At the juncture of roof vertical surfaces, flashing and counterflashing shall be provided in accordance with this chapter and the manufacturer’s installation instructions and, where of metal, shall be not less than 0.019 inch (0.5 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend not less than 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25 mm) in height at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of 3 units vertical in 12 units horizontal (25 percent slope) and greater, valley flashing shall have a 36-inch-wide (914 mm) underlayment of one layer of Type I underlayment running the full length of the valley, in addition to other required underlayment. In areas where the average daily temperature in January is 25°F (-4°C) or less, metal valley flashing underlayment shall be solid-cemented to the roofing underlayment for slopes less than 7 units vertical in 12 units horizontal (58 percent slope) or be of self-adhering polymer-modified bitumen sheet.

R905.4 Metal roof shingles.

The installation of metal roof shingles shall comply with the provisions of this section.

R905.4.1 Sheathing requirements.

Metal roof shingles shall be fastened to wood structural panels, solid lumber sheathing or closely fitted lumber sheathing, except where the roof covering is specifically designed to be applied to spaced lumber sheathing.

R905.4.2 Slope.

Metal roof shingles shall not be installed on roof slopes below 3 units vertical in 12 units horizontal (25 percent slope).

R905.4.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.4.3.1 Ice barrier.

Where required, ice barriers shall comply with Section R905.1.2.

R905.4.4 Material standards.

Metal roof shingle roof coverings shall comply with Table R905.10.3(1). The materials used for metal roof shingle roof coverings shall be naturally corrosion resistant or be made corrosion resistant in accordance with the standards and minimum thicknesses listed in Table R905.10.3(2).

R905.4.4.1 Wind resistance of metal roof shingles.

Metal roof shingles fastened to wood structural panels, solid lumber sheathing or closely fitted lumber sheathing shall be tested in accordance with ASTM D3161, FM 4474, UL 580 or UL 1897. Metal roof shingles tested in accordance with ASTM D3161 shall meet the classification requirements of Table R905.4.4.1 for the appropriate maximum basic wind speed and the metal shingle packaging shall bear a label to indicate compliance with ASTM D3161 and the required classification in Table R905.2.4.1.

TABLE R905.4.4.1 CLASSIFICATION OF STEEP SLOPE METAL ROOF SHINGLES TESTED IN ACCORDANCE WITH ASTM D3161

MAXIMUM ULTIMATE DESIGN WIND SPEED, V ult, FROM FIGURE R301.2(2) (mph)

MAXIMUM BASIC WIND SPEED, V ASD, FROM TABLE R301.2.1.3 (mph)

ASTM D3161 SHINGLE CLASSIFICATION

110

85

A, D or F

116

90

A, D or F

129

100

A, D or F

142

110

F

155

120

F

168

130

F

181

140

F

194

150

F

For SI: 1 mile per hour = 1.609 kph.

R905.4.5 Application.

Metal roof shingles shall be secured to the roof in accordance with this chapter and the approved manufacturer’s installation instructions.

R905.4.6 Flashing.

Roof valley flashing shall be of corrosion-resistant metal of the same material as the roof covering or shall comply with the standards in Table R905.10.3(1). The valley flashing shall extend not less than 8 inches (203 mm) from the centerline each way and shall have a splash diverter rib not less than 3/4 inch (19 mm) in height at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). The metal valley flashing shall have a 36-inch-wide (914 mm) underlayment directly under it consisting of one layer of underlayment running the full length of the valley, in addition to underlayment required for metal roof shingles. In areas where the average daily temperature in January is 25°F (-4°C) or less, the metal valley flashing underlayment shall be solid-cemented to the roofing underlayment for roof slopes under 7 units vertical in 12 units horizontal (58 percent slope) or self-adhering polymer-modified bitumen sheet.

R905.5 Mineral-surfaced roll roofing.

The installation of mineral-surfaced roll roofing shall comply with this section.

R905.5.1 Sheathing requirements.

Mineral-surfaced roll roofing shall be fastened to wood structural panels or solid lumber sheathing.

R905.5.2 Slope.

Mineral-surfaced roll roofing shall not be applied on roof slopes below 1 unit vertical in 12 units horizontal (8 percent slope).

R905.5.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.5.3.1 Ice barrier.

Where required, ice barriers shall comply with Section R905.1.2.

R905.5.4 Material standards.

Mineral-surfaced roll roofing shall conform to ASTM D3909 or ASTM D6380, Class M.

R905.5.5 Application.

Mineral-surfaced roll roofing shall be installed in accordance with this chapter and the manufacturer’s instructions.

R905.5.6 Wind resistance of mineral-surfaced roll roofing.

Mineral-surfaced roll roofing shall be installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

R905.6 Slate shingles.

The installation of slate shingles shall comply with the provisions of this section.

R905.6.1 Sheathing requirements.

Slate shingles shall be fastened to wood structural panels or solid lumber sheathing.

R905.6.2 Slope.

Slate shingles shall be used only on slopes of 4 units vertical in 12 units horizontal (33 percent slope) or greater.

R905.6.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.6.3.1 Ice barrier.

Where required, ice barriers shall comply with Section R905.1.2.

R905.6.4 Material standards.

Slate shingles shall comply with ASTM C406.

R905.6.5 Wind resistance of slate shingles.

Slate shingles shall be tested in accordance with ASTM D3161. Slate shingle packaging shall bear a label indicating compliance with ASTM D3161 and the required classification in Table R905.6.5.

TABLE R905.6.5 CLASSIFICATION OF SLATE SHINGLES TESTED IN ACCORDANCE WITH ASTM D3161

MAXIMUM ULTIMATE DESIGN WIND SPEED, V ult, FROM FIGURE R301.2(2) (mph)

MAXIMUM BASIC WIND SPEED, Vasd, FROM TABLE R301.2.1.3 (mph)

ASTM D3161 CLASSIFICATION

110

85

A, D or F

116

90

A, D or F

129

100

A, D or F

142

110

F

155

120

F

168

130

F

181

140

F

194

150

F

For SI: 1 mph = 0.447 m/s

R905.6.6 Application.

Minimum headlap for slate shingles shall be in accordance with Table R905.6.6. Slate shingles shall be secured to the roof with two fasteners per slate. Slate shingles shall be installed in accordance with this chapter and the manufacturer’s instructions.

TABLE R905.6.6 SLATE SHINGLE HEADLAP

SLOPE

HEADLAP (inches)

4:12 ≤ slope < 8:12

4

8:12 ≤ slope < 20:12

3

Slope ≥ 20:12

2

For SI: 1 inch = 25.4 mm.

R905.6.7 Flashing.

Flashing and counterflashing shall be made with sheet metal. Valley flashing shall be not less than 15 inches (381 mm) wide. Valley and flashing metal shall be a minimum uncoated thickness of 0.0179-inch (0.5 mm) zinc-coated G90. Chimneys, stucco or brick walls shall have not less than two plies of felt for a cap flashing consisting of a 4-inch-wide (102 mm) strip of felt set in plastic cement and extending 1 inch (25 mm) above the first felt and a top coating of plastic cement. The felt shall extend 2 inches (51 mm) over the base flashing.

R905.7 Wood shingles.

The installation of wood shingles shall comply with the provisions of this section.

R905.7.1 Sheathing requirements.

Wood shingles shall be fastened to wood structural panels, solid lumber sheathing or spaced lumber sheathing. Where spaced lumber sheathing is used, sheathing boards shall be not less than 1-inch by 4-inch (25 mm by 102 mm) nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. Where 1-inch by 4-inch (25 mm by 102 mm) spaced sheathing is installed at 10 inches (254 mm) or greater, additional 1-inch by 4-inch (25 mm by 102 mm) boards shall be installed between the sheathing boards. Where wood shingles are installed over spaced sheathing and the underside of the shingles are exposed to the attic space, the attic shall be ventilated in accordance with Sections R806.1, R806.2, R806.3 and R806.4. The shingles shall not be backed with materials that will occupy the required air gap space and prevent the free movement of air on the interior side of the spaced sheathing.

R905.7.1.1 Solid sheathing required.

In areas where the average daily temperature in January is 25°F (-4°C) or less, wood structural panels or solid lumber sheathing is required on that portion of the roof deck requiring the application of an ice barrier.

R905.7.2 Slope.

Wood shingles shall be installed on slopes of 3 units vertical in 12 units horizontal (25 percent slope) or greater.

R905.7.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.7.3.1 Ice barrier.

Where required, ice barriers shall comply with Section R905.1.2.

R905.7.4 Material standards.

Wood shingles shall be of naturally durable wood and comply with the requirements of Table R905.7.4.

TABLE R905.7.4 WOOD SHINGLE MATERIAL REQUIREMENTS

MATERIAL

MINIMUM GRADES

APPLICABLE GRADING RULES

Wood shingles of naturally durable wood

1, 2 or 3

CSSB

R905.7.5 Wind resistance of wood shingles.

In regions where wind design is required in accordance with Figure R301.2.1.1, wood shingles shall be installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2). In regions where wind design is not required in accordance with Figure R301.2.1.1, wood shingles are permitted to be attached in accordance with Section R905.7.6.

R905.7.6 Application.

Wood shingles shall be installed in accordance with this chapter and the manufacturer’s instructions. Wood shingles shall be laid with a side lap not less than 1 1/2 inches (38 mm) between joints in courses, and two joints shall not be in direct alignment in any three adjacent courses. Spacing between shingles shall be not less than 1/4 inch to 3/8 inch (6.4 mm to 9.5 mm). Weather exposure for wood shingles shall not exceed those set in Table R905.7.6(1). Fasteners for untreated (naturally durable) wood shingles shall be box nails in accordance with Table R905.7.6(2). Nails shall be stainless steel Type 304 or 316 or hotdipped galvanized with a coating weight of ASTM A153 Class D or ASTM A641 Class 3S (1.0 oz/ft2). Alternatively, two 16-gage stainless steel Type 304 or 316 staples with crown widths 7/16 inch (11.1 mm) minimum, 3/4 inch (19.1 mm) maximum, shall be used. Fasteners installed within 15 miles (24 km) of saltwater coastal areas shall be stainless steel Type 316. Fasteners for fire-retardanttreated shingles in accordance with Section R902 or pressure-impregnated-preservative-treated shingles of naturally durable wood in accordance with AWPA U1 shall be stainless steel Type 316. Fasteners shall have a minimum penetration into the sheathing of 3/4 inch (19.1 mm). For sheathing less than 3/4 inch in (19.1 mm) thickness, each fastener shall penetrate through the sheathing. Wood shingles shall be attached to the roof with two fasteners per shingle, positioned in accordance with the manufacturer’s installation instructions. Fastener packaging shall bear a label indicating the appropriate grade material or coating weight.

TABLE R905.7.6(1) WOOD SHINGLE WEATHER EXPOSURE AND ROOF SLOPE

ROOFING MATERIAL

LENGTH (inches)

GRADE

EXPOSURE (inches)

3:12 pitch to < 4:12

4:12 pitch or steeper

Shingles of naturally durable wood

16

No. 1

3 3/4

5

No. 2

3 1/2

4

No. 3

3

3 1/2

18

No. 1

4 1/4

5 1/4

No. 2

4

4 1/2

No. 3

3 1/2

4

24

No. 1

5 3/4

7 1/2

No. 2

5 1/2

6 1/2

No. 3

5

5 1/2

For SI: 1 inch = 25.4 mm.

TABLE R905.7.6(2) NAIL REQUIREMENTS FOR WOOD SHAKES AND WOOD SHINGLES

PRODUCT TYPE

NAIL TYPE, MINIMUM LENGTH AND SHANK DIAMETER (inches)

Shakes

 18″ straight-split

5d box 1 3/4″ × 0.080

 18″ and 24″ handsplit and resawn

6d box 2″ × 0.099

 24″ taper-split

5d box 1 3/4″ × 0.080

 18″ and 24″ tapersawn

6d box 2″ × 0.099

Shingles

 16″ and 18″

3d box 1 1/4″ × 0.076

 24″

4d box 1 1/2″ × 0.076

For SI: 1 inch = 25.4 mm.

R905.7.7 Valley flashing.

Roof flashing shall be not less than No. 26 gage [0.019 inches (0.5 mm)] corrosion-resistant sheet metal and shall extend 10 inches (254 mm) from the centerline each way for roofs having slopes less than 12 units vertical in 12 units horizontal (100 percent slope), and 7 inches (178 mm) from the centerline each way for slopes of 12 units vertical in 12 units horizontal (100 percent slope) and greater. Sections of flashing shall have an end lap of not less than 4 inches (102 mm).

R905.7.8 Label required.

Each bundle of shingles shall be identified by a label of an approved grading or inspection bureau or agency.

R905.8 Wood shakes.

The installation of wood shakes shall comply with the provisions of this section.

R905.8.1 Sheathing requirements.

Wood shakes shall be fastened to wood structural panels, solid lumber sheathing or spaced lumber sheathing. Where spaced lumber sheathing is used, sheathing boards shall be not less than 1-inch by 4-inch (25 mm by 102 mm) nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. Where 1-inch by 4-inch (25 mm by 102 mm) spaced lumber sheathing is installed at 10 inches (254 mm) on center, additional 1-inch by 4-inch (25 mm by 102 mm) boards shall be installed between the sheathing boards. Where wood shakes are installed over spaced sheathing and the underside of the shakes are exposed to the attic space, the attic shall be ventilated in accordance with Sections R806.1, R806.2, R806.3 and R806.4. The shakes shall not be backed with materials that will occupy the required air gap space and prevent the free movement of air on the interior side of the spaced sheathing.

R905.8.1.1 Solid sheathing required.

In areas where the average daily temperature in January is 25°F (-4°C) or less, wood structural panels or solid lumber sheathing is required on that portion of the roof deck requiring an ice barrier.

R905.8.2 Slope.

Wood shakes shall only be used on slopes of 3 units vertical in 12 units horizontal (25 percent slope) or greater.

R905.8.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.8.3.1 Ice barrier.

Where required, ice barriers shall comply with Section R905.1.2.

R905.8.4 Interlayment.

Interlayment shall comply with ASTM D226, Type I.

R905.8.5 Material standards.

Wood shakes shall comply with the requirements of Table R905.8.5.

TABLE R905.8.5 WOOD SHAKE MATERIAL REQUIREMENTS

MATERIAL

MINIMUM GRADES

APPLICABLE GRADING RULES

Wood shakes of naturally durable wood

1

Cedar Shake and Shingle Bureau

Tapersawn shakes of naturally durable wood

1 or 2

Cedar Shake and Shingle Bureau

Preservative-treated shakes and shingles of naturally durable wood

1

Cedar Shake and Shingle Bureau

Fire-retardant-treated shakes and shingles of naturally durable wood

1

Cedar Shake and Shingle Bureau

Preservative-treated tapersawn shakes of Southern pine treated in accordance with AWPA Standard U1 (Commodity Specification A, Special Requirement 4.6)

1 or 2

Forest Products Laboratory of the Texas Forest Services

R905.8.6 Wind resistance of wood shakes.

In regions where wind design is required in accordance with Figure R301.2.1.1, Wood shakes shall be installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2). In regions where wind design is not required in accordance with Figure R301.2.1.1, wood shakes are permitted to be attached in accordance with Section R905.8.8.

R905.8.7 Application.

Wood shakes shall be installed in accordance with this chapter and the manufacturer’s installation instructions. Wood shakes shall be laid with a side lap not less than 1 1/2 inches (38 mm) between joints in adjacent courses. Spacing between shakes in the same course shall be 3/8 inch to 5/8 inch (9.5 mm to 15.9 mm) including tapersawn shakes. Weather exposures for wood shakes shall not exceed those set in Table R905.8.7. Fasteners for untreated (naturally durable) wood shakes shall be box nails in accordance with Table R905.7.6(2). Nails shall be stainless steel Type 304, or Type 316 or hot-dipped with a coating weight of ASTM A153 Class D or ASTM A641 Class 3S (1.0 oz/ft2). Alternatively, two 16-gage Type 304 or Type 316 stainless steel staples, with crown widths 7/16 inch (11.1 mm) minimum, 3/4 inch (19.1 mm) maximum, shall be used. Fasteners installed within 15 miles (24 km) of saltwater coastal areas shall be stainless steel Type 316. Wood shakes shall be attached to the roof with two fasteners per shake positioned in accordance with the manufacturer’s installation instructions. Fasteners for fire-retardanttreated (as defined in Section R902) shakes or pressure-impregnated-preservative-treated shakes of naturally durable wood in accordance with AWPA U1 shall be stainless steel Type 316. Fasteners shall have a minimum penetration into the sheathing of 3/4 inch (19.1 mm). Where the sheathing is less than 3/4 inch (19.1 mm) thick, each fastener shall penetrate through the sheathing. Fastener packaging shall bear a label indicating the appropriate grade material or coating weight.

TABLE R905.8.7 WOOD SHAKE WEATHER EXPOSURE AND ROOF SLOPE

ROOFING MATERIAL

LENGTH (inches)

GRADE

EXPOSURE (inches)

4:12 pitch or steeper

Shakes of naturally durable wood

18

No. 1

7 1/2

24

No. 1

10a

Preservative-treated tapersawn shakes of Southern Yellow Pine

18

No. 1

7 1/2

24

No. 1

10

18

No. 2

5 1/2

24

No. 2

7 1/2

Taper-sawn shakes of naturally durable wood

18

No. 1

7 1/2

24

No. 1

10

18

No. 2

5 1/2

24

No. 2

7 1/2

For SI: 1 inch = 25.4 mm.

  1. a.

    For 24-inch by 3/8-inch handsplit shakes, the maximum exposure is 7 1/2 inches.

R905.8.8 Shake placement.

The starter course at the eaves shall be doubled and the bottom layer shall be either 15-inch (381 mm), 18-inch (457 mm) or 24-inch (610 mm) wood shakes or wood shingles. Fifteen-inch (381 mm) or 18-inch (457 mm) wood shakes shall be permitted to be used for the final course at the ridge. Shakes shall be interlaid with 18-inch-wide (457 mm) strips of not less than No. 30 felt shingled between each course in such a manner that felt is not exposed to the weather by positioning the lower edge of each felt strip above the butt end of the shake it covers a distance equal to twice the weather exposure.

R905.8.9 Valley flashing.

Roof valley flashing shall be not less than No. 26 gage [0.019 inch (0.5 mm)] corrosion-resistant sheet metal and shall extend not less than 11 inches (279 mm) from the centerline each way. Sections of flashing shall have an end lap of not less than 4 inches (102 mm).

R905.8.10 Label required.

Each bundle of shakes shall be identified by a label of an approved grading or inspection bureau or agency.

R905.9 Built-up roofs.

The installation of built-up roofs shall comply with the provisions of this section and the manufacturer’s approved installation instructions.

R905.9.1 Slope.

Built-up roofs shall have a design slope of not less than 1/4 unit vertical in 12 units horizontal (2 percent slope) for drainage, except for coal-tar built-up roofs, which shall have a design slope of a minimum 1/8 unit vertical in 12 units horizontal (1 percent slope).

R905.9.2 Material standards.

Built-up roof covering materials shall comply with the standards in Table R905.9.2 or UL 55A.

TABLE R905.9.2 BUILT-UP ROOFING MATERIAL STANDARDS

MATERIAL STANDARD

STANDARD

Acrylic coatings used in roofing

ASTM D6083

Aggregate surfacing

ASTM D1863

Asphalt adhesive used in roofing

ASTM D3747

Asphalt cements used in roofing

ASTM D2822; D3019; D4586

Asphalt-coated glass fiber base sheet

ASTM D4601

Asphalt coatings used in roofing

ASTM D1227; D2823; D2824; D4479

Asphalt glass felt

ASTM D2178

Asphalt primer used in roofing

ASTM D41

Asphalt-saturated and asphalt-coated organic felt base sheet

ASTM D2626

Asphalt-saturated organic felt (perforated)

ASTM D2626

Asphalt used in roofing

ASTM D312

Coal-tar cements used in roofing

ASTM D4022; D5643

Coal-tar primer used in roofing, dampproofing and waterproofing

ASTM D43

Coal-tar saturated organic felt

ASTM D227

Coal-tar used in roofing

ASTM D450, Type I or II

Glass mat, coal tar

ASTM D4990

Glass mat, venting type

ASTM D4897

Mineral-surfaced inorganic cap sheet

ASTM D3909

Thermoplastic fabrics used in roofing

ASTM D5665; D5726

R905.9.3 Application.

Built-up roofs shall be installed in accordance with this chapter and the manufacturer’s instructions.

R905.9.4 Wind resistance of built-up roofs.

Built-up roof coverings shall be tested in accordance with FM 4474, UL 580 or UL 1897 and installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

R905.10 Metal roof panels.

The installation of metal roof panels shall comply with the provisions of this section.

R905.10.1 Sheathing requirements.

Metal roof panel roof coverings shall be fastened to wood structural panels, solid lumber sheathing or spaced lumber sheathing, except where the roof covering is specifically designed to be applied to spaced supports.

R905.10.2 Slope.

Minimum slopes for metal roof panels shall comply with the following:

  1. 1.

    The minimum slope for lapped, nonsoldered-seam metal roofs without applied lap sealant shall be 3 units vertical in 12 units horizontal (25 percent slope).

  2. 2.

    The minimum slope for lapped, nonsoldered-seam metal roofs with applied lap sealant shall be 1/2 unit vertical in 12 units horizontal (4 percent slope). Lap sealants shall be applied in accordance with the approved manufacturer’s installation instructions.

  3. 3.

    The minimum slope for standing-seam roof systems shall be 1/4 unit vertical in 12 units horizontal (2 percent slope).

R905.10.3 Material standards.

Metal-sheet roof covering systems that incorporate supporting structural members shall be designed in accordance with the International Building Code. Metal-sheet roof coverings installed over structural decking shall comply with Table R905.10.3(1). The materials used for metal-sheet roof coverings shall be naturally corrosion resistant or provided with corrosion resistance in accordance with the standards and minimum thicknesses shown in Table R905.10.3(2).

TABLE R905.10.3(1) METAL ROOF COVERING STANDARDS

ROOF COVERING TYPE

STANDARD APPLICATION RATE/THICKNESS

Aluminum

ASTM B209, 0.024 minimum thickness for roll-formed panels and 0.019-inch minimum thickness for press-formed shingles.

Cold-rolled copper

ASTM B370 minimum 16 oz/sq ft and 12 oz/sq ft high-yield copper for metal-sheet roof-covering systems; 12 oz/sq ft for preformed metal shingle systems.

Galvanized steel

ASTM A653 G90 Zinc coated

Hard lead

2 lb/sq ft

Lead-coated copper

ASTM B101

Soft lead

3 lb/sq ft

Stainless steel

ASTM A240, 300 Series alloys

Steel

ASTM A924

Terne (tin) and terne-coated stainless

Terne coating of 40 lb per double base box, field painted where applicable in accordance with manufacturer’s installation instructions.

Zinc

0.027-inch minimum thickness: 99.995% electrolytic high-grade zinc with alloy additives of copper (0.08–0.20%), titanium (0.07%–0.12%) and aluminum (0.015%).

For SI: 1 ounce per square foot = 0.305 kg/m2, 1 pound per square foot = 4.214 kg/m2, 1 inch = 25.4 mm, 1 pound = 0.454 kg.

TABLE R905.10.3(2) MINIMUM CORROSION RESISTANCE

MATERIAL

STANDARD

55% aluminum-zinc-alloy-coated steel

ASTM A792 AZ 50

5% aluminum alloy-coated steel

ASTM A875 GF60

Aluminum-coated steel

ASTM A463 T2 65

Galvanized steel

ASTM A653 G-90

Prepainted steel

ASTM A755 a

  1. a.

    Paint systems in accordance with ASTM A755 shall be applied over steel products with corrosion-resistant coatings complying with ASTM A792, ASTM A875, ASTM A463 or ASTM A653.

R905.10.4 Attachment.

Metal roof panels shall be secured to the supports in accordance with this chapter and the manufacturer’s installation instructions. In the absence of manufacturer’s installation instructions, the following fasteners shall be used:

  1. 1.

    Galvanized fasteners shall be used for steel roofs.

  2. 2.

    Copper, brass, bronze, copper alloy and 300-series stainless steel fasteners shall be used for copper roofs.

  3. 3.

    Stainless steel fasteners are acceptable for metal roofs.

R905.10.5 Wind resistance of metal roof panels.

Metal roof panels shall be installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2). Metal roof panels applied to a solid or closely fitted deck shall be tested for wind resistance in accordance with FM 4474, UL 580, or UL 1897. Structural standing seam metal panel roof systems shall be tested for wind resistance in accordance with ASTM E1592 or FM 4474. Structural through-fastened metal panel roof systems shall be tested for wind resistance in accordance with ASTM E1592, FM 4474 or UL 580.

Exceptions:

  1. 1.

    Metal roofs constructed of cold-formed steel shall be permitted to be designed and tested in accordance with the applicable referenced structural design standard in Section 2208.1 of the International Building Code.

  2. 2.

    Metal roofs constructed of aluminum shall be permitted to be designed and tested in accordance with the applicable referenced structural design standard in Section 2002.1 of the International Building Code.

R905.10.6 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.11 Modified bitumen roofing.

The installation of modified bitumen roofing shall comply with the provisions of this section and the manufacturer’s approved installation instructions.

R905.11.1 Slope.

Modified bitumen roofing shall have a design slope of not less than one-fourth unit vertical in 12 units horizontal (2 percent slope) for drainage.

R905.11.2 Material standards.

Modified bitumen roofing shall comply with the standards in Table R905.11.2.

TABLE R905.11.2 MODIFIED BITUMEN ROOFING MATERIAL STANDARDS

MATERIAL

STANDARD

Acrylic coating

ASTM D6083

Asphalt adhesive

ASTM D3747

Asphalt cement

ASTM D3019

Asphalt coating

ASTM D1227; D2824

Asphalt primer

ASTM D41

Modified bitumen roof membrane

ASTM D6162; D6163; D6164;D6222; D6223;D6298

R905.11.2.1 Base sheet.

A base sheet that complies with the requirements of Section 1507.11.2 of the International Building Code, ASTM D1970 or ASTM D4601 shall be permitted to be used with a modified bitumen cap sheet.

R905.11.3 Application.

Modified bitumen roofs shall be installed in accordance with this chapter and the manufacturer’s instructions.

R905.11.4 Wind resistance of modified bitumen roofing.

Modified bitumen roofing shall be tested in accordance with FM 4474, UL 580 or UL 1897 and installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

R905.12 Single-ply roofing.

The installation of single-ply membrane roof coverings shall comply with the provisions of this section.

TABLE R905.12 SINGLE-PLY ROOFING MATERIAL STANDARDS

MATERIAL

STANDARD

Chlorosulfanated polyethylene (CSPE) or polyisobutylene (PIB)

ASTM D5019

Ethylene propylene diene monomer (EPDM)

ASTM D4637

Ketone Ethylene Ester (KEE)

ASTM D6754

Polyvinyl chloride (PVC) or (PVC/KEE)

ASTM D4434

Thermosplastic polyolefin (TPO)

ASTM D6878

R905.12.1 Slope.

Single-ply membrane roof coverings shall have a design slope of not less than 1/4 unit vertical in 12 units horizontal (2 percent slope) for drainage.

R905.12.2 Material standards.

Single-ply membrane roof coverings shall comply with the material standards in Table R905.12.

R905.12.3 Application.

Single-ply membrane roof coverings shall be installed in accordance with this chapter and the manufacturer’s installation instructions.

R905.12.4 Wind resistance of single-ply roofing.

Single-ply roofing shall be tested in accordance with FM 4474, UL 580 or UL 1897 and installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

R905.13 Sprayed polyurethane foam roofing.

The installation of sprayed polyurethane foam roofing shall comply with the provisions of this section.

R905.13.1 Slope.

Sprayed polyurethane foam roofs shall have a design slope of not less than 1/4 unit vertical in 12 units horizontal (2 percent slope) for drainage.

R905.13.2 Material standards.

Spray-applied polyurethane foam insulation shall comply with ASTM C1029, Type III or IV or ASTM D7425.

R905.13.3 Application.

Foamed-in-place roof insulation shall be installed in accordance with this chapter and the manufacturer’s instructions. A liquid-applied protective coating that complies with Table R905.13.3 shall be applied not less than 2 hours nor more than 72 hours following the application of the foam.

TABLE R905.13.3 PROTECTIVE COATING MATERIAL STANDARDS

MATERIAL

STANDARD

Acrylic coating

ASTM D6083

Moisture-cured polyurethane coating

ASTM D6947

Silicone coating

ASTM D6694

R905.13.4 Wind resistance of sprayed polyurethane foam roofing.

Sprayed polyurethane foam roofing shall be tested in accordance with FM 4474, UL 580 or UL 1897 and installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

R905.13.5 Foam plastics.

Foam plastic materials and installation shall comply with Section R303.

R905.14 Liquid-applied roofing.

The installation of liquid-applied roofing shall comply with the provisions of this section.

R905.14.1 Slope.

Liquid-applied roofing shall have a design slope of not less than 1/4 unit vertical in 12 units horizontal (2 percent slope).

R905.14.2 Material standards.

Liquid-applied roofing shall comply with ASTM C836, C957, D1227, D3468, D6083, D6694 or D6947.

R905.14.3 Application.

Liquid-applied roofing shall be installed in accordance with this chapter and the manufacturer’s installation instructions.

R905.14.4 Wind resistance of liquid-applied roofing.

Liquid-applied roofing shall be tested in accordance with FM 4474, UL 580 or UL 1897 and installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

R905.15 BIPV shingles.

The installation of BIPV shingles shall comply with the provisions of this section, Section R329 and NFPA 70.

R905.15.1 Sheathing requirements.

BIPV shingles shall be fastened to wood structural panels, solid lumber sheathing or closely fitted lumber sheathing, except where the roof covering is specifically designed to be applied over spaced lumber sheathing.

R905.15.2 Slope.

BIPV shingles shall be used only on roof slopes of 2 units vertical in 12 units horizontal (2:12) or greater.

R905.15.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.15.3.1 Ice barrier.

Where required, ice barriers shall comply with Section R905.1.2.

R905.15.4 Material standards.

BIPV shingles shall be listed and labeled in accordance with UL 7103 .

R905.15.5 Attachment.

BIPV shingles shall be attached in accordance with the manufacturer’s installation instructions.

R905.15.6 Wind resistance.

BIPV shingles shall comply with the classification requirements of Table R905.15.6 for the appropriate maximum basic wind speed.

TABLE R905.15.6 CLASSIFICATION OF BIPV SHINGLES

MAXIMUM ULTIMATE DESIGN WIND SPEED, V ult, FROM FIGURE R301.2(2) (mph)

MAXIMUM BASIC WIND SPEED, V ASD, FROM TABLE R301.2.1.3 (mph)

UL 7103 SHINGLE CLASSIFICATION

110

85

A, D or F

116

90

A, D or F

129

100

A, D or F

142

110

F

155

120

F

168

130

F

181

140

F

194

150

F

For SI: 1 mile per hour = 1.609 kph.

R905.16 Building-integrated photovoltaic (BIPV) roof panels applied directly to the roof deck.

The installation of BIPV roof panels shall comply with the provisions of this section, Section R329 and NFPA 70.

R905.16.1 Sheathing requirements.

BIPV roof panels shall be fastened to wood structural panels, solid lumber sheathing or closely-fitted lumber sheathing, except where the roof covering is specifically designed to be applied over spaced lumber sheathing.

R905.16.2 Slope.

BIPV roof panels shall be used only on roof slopes of 2 units vertical in 12 units horizontal (17 percent slope) or greater.

R905.16.3 Underlayment.

Underlayment shall comply with Section R905.1.1.

R905.16.3.1 Ice barrier.

Where required, an ice barrier shall comply with Section R905.1.2.

R905.16.4 Ice barrier.

In areas where there has been a history of ice forming along the eaves causing a backup of water, as designated in Table R301.2, an ice barrier that consists of not less than two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal underlayment and extend from the lowest edges of all roof surfaces to a point not less than 24 inches (610 mm) inside the exterior wall line of the building.

Exception: Detached accessory structures that do not contain conditioned floor area.

R905.16.5 Material standards.

BIPV roof panels shall be listed and labeled in accordance with UL 7103.

R905.16.6 Attachment.

BIPV roof panels shall be attached in accordance with the manufacturer’s installation instructions.

R905.16.7 Wind resistance of BIPV roof panels.

BIPV roof panels shall be tested in accordance with UL 7103 and installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

Section R906 Roof Insulation

R906.1 General.

Where above-deck thermal insulation is installed, such insulation shall be covered with an approved roof covering and shall comply with NFPA 276 or UL 1256.

R906.2 Material standards.

Above-deck thermal insulation board shall comply with the standards in Table R906.2 .

TABLE R906.2 MATERIAL STANDARDS FOR ROOF INSULATION

MATERIAL

STANDARD

Cellular glass board

ASTM C552 or ASTM C1902

Composite boards

ASTM C1289, Type III, IV, V or VI

Expanded polystyrene

ASTM C578

Extruded polystyrene board

ASTM C578

Fiber-reinforced gypsum board

ASTM C1278

Glass-faced gypsum board

ASTM C1177

Mineral wool board

ASTM C726

Perlite board

ASTM C728

Polyisocyanurate board

ASTM C1289, Type I or II

Wood fiberboard

ASTM C208

Section R907 Rooftop-Mounted Photovoltaic Panel Systems

R907.1 Rooftop-mounted photovoltaic panel systems.

Rooftop-mounted photovoltaic panel systems shall be designed and installed in accordance with Section R329 and NFPA 70.

Section R908 Reroofing

R908.1 General.

Materials and methods of application used for recovering or replacing an existing roof covering shall comply with the requirements of this chapter.

Exceptions:

  1. 1.

    Reroofing shall not be required to meet the minimum design slope requirement of one-quarter unit vertical in 12 units horizontal (2 percent slope) in Section R905 for roofs that provide positive roof drainage.

  2. 2.

    For roofs that provide positive drainage, recovering or replacing an existing roof covering shall not require the secondary (emergency overflow) drains or scuppers of Section R903.4.1 to be added to an existing roof.

R908.2 Structural and construction loads.

The structural roof components shall be capable of supporting the roof covering system and the material and equipment loads that will be encountered during installation of the roof covering system.

R908.3 Roof replacement.

Roof replacement shall include the removal of existing layers of roof coverings down to the roof deck.

Exceptions:

  1. 1.

    Where the existing roof assembly includes an ice barrier membrane that is adhered to the roof deck and the existing sheathing is not water soaked or deteriorated to the point that it is not adequate as a base for additional roofing, the existing ice barrier membrane shall be permitted to remain in place and covered with an additional layer of ice barrier membrane in accordance with Section R905 where permitted by the roof covering manufacturer and new ice barrier underlayment manufacturer.

  2. 2.

    Where the existing roof includes a self-adhered underlayment and the existing sheathing is not water soaked or deteriorated to the point that it is not adequate as a base for additional roofing, the existing self-adhered underlayment shall be permitted to remain in place and covered with an underlayment complying with Table R905.1.1(1), Table R905.1.1(2) and Table R905.1.1(3).

  3. 3.

    Where the existing roof includes one layer of self-adhered underlayment and the existing layer cannot be removed without damaging the roof deck, a second layer of self-adhered underlayment is permitted to be installed over the existing self-adhered underlayment provided that the following conditions are met:

    1. 3.1.

      It is permitted by the roof covering manufacturer and new self-adhered underlayment manufacturer.

    2. 3.2.

      The existing sheathing is not water soaked or deteriorated to the point that it is not adequate as a base for additional roofing.

    3. 3.3.

      The second layer of self-adhered underlayment is installed such that buildup of material at walls, valleys, roof edges, end laps, and side laps does not exceed two layers.

R908.4 Roof recover.

The installation of a new roof covering over an existing roof covering shall be permitted where any of the following conditions occur:

  1. 1.

    Where the new roof covering is installed in accordance with the roof covering manufacturer’s approved instructions.

  2. 2.

    Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building’s structural system and do not rely on existing roofs and roof coverings for support, shall not require the removal of existing roof coverings.

  3. 3.

    Metal panel, metal shingle and concrete and clay tile roof coverings shall be permitted to be installed over existing wood shake roofs where applied in accordance with Section R908.4.1.

  4. 4.

    The application of a new protective roof coating over an existing protective roof coating, metal roof panel, metal roof shingle, mineral surfaced roll roofing, built-up roof, modified bitumen roofing, thermoset and thermoplastic single-ply roofing and spray polyurethane foam roofing system shall be permitted without tear-off of existing roof coverings.

Exceptions: A roof recover shall not be permitted where any of the following conditions occur:

  1. 1.

    Where the existing roof or roof covering is water soaked or has deteriorated to the point that the existing roof or roof covering is not adequate as a base for the additional roofing.

  2. 2.

    Where the existing roof covering is slate, clay, cement or asbestos-cement title.

  3. 3.

    Where the existing roof has two or more applications of any type of roof covering.

R908.4.1 Roof recovering over wood shingles or shakes.

Where the application of a new roof covering over wood shingle or shake roofs creates a combustible concealed space, the entire existing surface shall be covered with gypsum board, mineral fiber, glass fiber or other approved materials securely fastened in place.

R908.5 Reinstallation of materials.

Existing slate, clay or cement tile shall be permitted for reinstallation, except that damaged, cracked or broken slate or tile shall not be reinstalled. Any existing flashings, edgings, outlets, vents or similar devices that are a part of the assembly shall be replaced where rusted, damaged or deteriorated. Aggregate surfacing materials shall not be reinstalled.

R908.6 Flashings.

Flashings shall be reconstructed in accordance with approved manufacturer’s installation instructions. Metal flashing to which bituminous materials are to be adhered shall be primed prior to installation.

Section R909 Roof Coatings

R909.1 General.

The installation of a roof coating on a roof covering shall comply with the requirements of Section R902, Section R904 and this section. Roof coatings shall be installed in accordance with the manufacturer’s installation instructions.

R909.2 Material standards.

Roof coating materials shall comply with one of the standards in Table R909.2.

TABLE R909.2 ROOF COATING MATERIAL STANDARDS

COATING MATERIAL

STANDARD

Acrylic coating

ASTM D6083

Asphaltic emulsion coating

ASTM D1227

Asphalt coating

ASTM D2823

Asphalt roof coating

ASTM D4479

Aluminum-pigmented asphalt coating

ASTM D2824

Silicone coating

ASTM D6694

Moisture-cured polyurethane coating

ASTM D6947