Appendix BI Light Straw-Clay Construction

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.

Section BI101 General

BI101.1 Scope.

This appendix shall govern the use of light straw-clay as a nonbearing building material and wall infil system in Seismic Design Categories A and B. Use of light straw-clay in Seismic Design Categories C, D0, D1 and D2 shall require an approved engineered design by a registered design professional in accordance with Section R301.1.3.

BI101.2 Flood hazard areas.

In flood hazard areas established in Table R301.2, buildings using light straw-clay infil shall meet the requirements of Section R306.

Section BI102 Definitions

BI102.1 General.

The following words and terms shall, for the purposes of this appendix, have the meanings shown herein. Refer to Chapter 2 for general definitions.

CLAY.

Inorganic soil with particle sizes of less than 0.00008 inch (0.002 mm) having the characteristics of high to very high dry strength and medium to high plasticity.

CLAY SLIP.

A suspension of clay or clay subsoil particles in water.

CLAY SUBSOIL.

Subsoil sourced directly from the earth or refined, containing clay and not more than trace amounts organic matter.

INFILL.

Light straw-clay that is placed between the structural and nonstructural members of a building.

LIGHT STRAW-CLAY.

A mixture of straw and clay slip compacted and dried to form insulation and plaster substrate between or around structural and nonstructural members in a wall.

NONBEARING.

Not bearing the weight of the building other than the weight of the light straw-clay itself and its finish.

STRAW.

The dry stems of cereal grains after the seed heads have been removed.

VOID.

Any space in a light straw-clay wall wider than 1/4 inch (6 mm), greater than 2 inches (51 mm) in horizontal length and greater than 2 inches (51 mm) in depth.

Section BI103 Nonbearing Light Straw-Clay Construction

BI103.1 General.

Light straw-clay shall be limited to infil between or around structural and nonstructural wall framing members.

BI103.2 Structure.

The structure of buildings using light straw-clay shall be in accordance with this code or shall be in accordance with an approved design by a registered design professional.

BI103.2.1 Number of stories.

Use of light straw-clay infil shall be limited to buildings that are not more than one story above grade plane.

Exception: Buildings using light straw-clay infil that are greater than one story above grade plane shall be in accordance with an approved design by a registered design professional.

BI103.2.2 Bracing.

Bracing for buildings with light straw-clay infil shall be in accordance with Section R602.10. Walls with light straw-clay infil shall use Method LIB and shall not be sheathed with solid sheathing. Walls without light straw-clay infil shall comply with any bracing method prescribed by this code.

BI103.2.3 Requirements and properties of light straw-clay mixtures.

The requirements and properties of light straw-clay mixtures shall be in accordance with Table BI103.2.3.

TABLE BI103.2.3 REQUIREMENTS AND PROPERTIES OF LIGHT STRAW-CLAY MIXTURESa

DENSITY (pcf)

STRAW (pcf)

SUBSOIL (pcf)

WATER (gal/cf)b

MIN. % CLAY IN SUBSOIL

MINIMUM CLAY:SILT RATIO

SUBSOIL TESTING METHODc, d

MAX. WALL THICKNESS, INCHES

R-VALUE (hr/F°/cf/BTU/inch)

10

6.7

3.3

1.55

70

3.5:1

A

15

1.80

12

6.7

5.3

1.63

46

1.7:1

A

15

1.72

13

6.7

6.3

1.67

40

1.33:1

A

15

1.69

15

6.7

8.3

1.74

35

0.95:1

A

15

1.63

20

6.7

13.3

1.93

30

0.60:1

A

12

1.48

30

6.7

23.3

2.31

NA

NA

B

12

1.22

40

6.7

33.3

2.70

NA

NA

B

12

1.01

50

6.7

43.3

3.08

NA

NA

B

12

0.84

©Douglas Piltingsrud and StrawClay.org. Used by permission.

  1. a.

    Interpolation permitted. Extrapolation not permitted.

  2. b.

    Water mixed with subsoil equals clay slip.

  3. c.

    Subsoil Testing Methods:

    1. 1.

      Lab test for percent of clay, silt and sand via hydrometer method.

    2. 2.

      The Figure 2 Ribbon Test and the Figure 3 Ball Test in the appendix of ASTM E2392/E2392M.

  4. d.

    Trace amounts of organic materials are acceptable.

BI103.2.4 Stabilization of light straw-clay.

Light straw-clay shall be stabilized as follows, or shall be in accordance with an approved design by a registered design professional:

  1. 1.

    Vertical stabilization shall be of structural or nonstructural wood framing in accordance with Figure BI103.2.4(1), BI103.2.4(2) or BI103.2.4(3). Framing members that are both load-bearing and stabilization members shall meet the requirements of Section R602 and this section. Nonstructural stabilization members shall be not more than 32 inches (813 mm) on center.

  2. 2.

    Horizontal stabilization shall be installed at not more than 24 inches (610 mm) on center and in accordance with Figure BI103.2.4(1), BI103.2.4(2) or BI103.2.4(3). Horizontal stabilization shall be of any of the following with the stated minimum dimensions: 3/4-inch (19.1 mm) bamboo, 1/2-inch (12.7 mm) fiberglass rod, 1-inch (25 mm) wood dowel or nominal 1-inch by 2-inch (25 mm by 51 mm) wood.

FIGURE BI103.2.4(1) LIGHT STRAW-CLAY WALL WITH LARSEN TRUSSES
GARC2024V1.0_Pt10_AppxBI_SecBI103.2.4_FigBI103.2.4_1.svg

For SI: 1 inch = 25.4 mm.

FIGURE BI103.2.4(2) LIGHT STRAW-CLAY WALL, SINGLE STUD WIDTH
GARC2024V1.0_Pt10_AppxBI_SecBI103.2.4_FigBI103.2.4_2.svg
FIGURE BI103.2.4(3) LIGHT STRAW-CLAY WALL WITH BLIND STUDS
GARC2024V1.0_Pt10_AppxBI_SecBI103.2.4_FigBI103.2.4_3.svg

BI103.3 Materials.

The materials used in light straw-clay construction shall be in accordance with Sections BI103.3.1 through BI103.3.3.

BI103.3.1 Straw requirements.

Straw shall be stems of wheat, rye, oats, rice or barley, and shall be free of visible decay, insects and green plant material.

BI103.3.2 Clay subsoil requirements.

Suitability of clay subsoil shall be determined in accordance with Table BI103.2.3.

BI103.3.3 Light straw-clay mixture.

A light straw-clay mixture shall consist of loose straw mixed and coated with clay slip such that there is not more than 5 percent uncoated straw, and shall be in accordance with Table BI103.2.3.

BI103.4 Wall construction.

Light straw-clay wall construction shall be in accordance with the requirements of Sections BI103.4.1 through BI103.4.7.

BI103.4.1 Light straw-clay maximum thickness.

The maximum thickness of light straw-clay shall be in accordance with Table BI103.2.3.

BI103.4.2 Distance above grade.

Light straw-clay and its exterior finish shall be not less than 8 inches (203 mm) above exterior finished grade.

BI103.4.3 Moisture barrier.

An approved moisture barrier shall separate the bottom of light straw-clay walls from any masonry or concrete foundation or slab that directly supports the walls. Penetrations and joints in the barrier shall be sealed with an approved sealant.

BI103.4.4 Contact with wood members.

Light straw-clay shall be permitted to be in contact with untreated wood members.

BI103.4.5 Contact with nonwood structural members.

Nonwood structural members in contact with light straw-clay shall be resistant to corrosion or shall be coated to prevent corrosion with an approved coating.

BI103.4.6 Installation.

Light straw-clay shall be installed in accordance with the following:

  1. 1.

    Formwork shall be sufficiently strong to resist bowing where the light straw-clay is compacted into the forms.

  2. 2.

    Light straw-clay shall be uniformly placed into forms and evenly tamped to achieve stable walls free of voids. Light straw-clay shall be placed in lifts of not more than 6 inches (152 mm) and shall be thoroughly tamped before additional material is added.

  3. 3.

    Temporary formwork shall be removed from walls within 24 hours after tamping, and walls shall remain exposed until moisture content is in accordance with Section BI103.5.1. Visible voids shall be filled with light straw-clay or other insulative material prior to plastering.

BI103.4.7 Openings in walls.

Openings in walls shall be in accordance with the following:

  1. 1.

    Rough framing for doors and windows shall be fastened to structural members in accordance with this code. Windows and doors shall be flashed in accordance with this code.

  2. 2.

    An approved moisture barrier shall be installed at windowsills in light straw-clay walls prior to installation of windows.

BI103.5 Wall finishes.

The interior and exterior surfaces of light straw-clay walls shall be protected with a finish in accordance with Sections BI103.5.1 through BI103.5.5.

BI103.5.1 Dimensional stability of light straw-clay prior to application of plaster finish.

Light straw-clay infil having a density of 30 pounds per cubic foot (480.6 kg/m3) or greater shall be dry to a moisture content of not more than 20 percent at a depth of 4 inches (102 mm), as measured from each side of the wall. Light straw-clay infil having a density of less than 30 pounds per cubic foot (480.6 kg/m3) shall be sufficiently dry such that the overall shrinkage of the light straw-clay is dimensionally stable.

BI103.5.2 Plaster finish.

Exterior plaster shall be clay plasters or lime plasters. Interior plasters shall be clay plasters, lime plasters or gypsum plasters. Plasters shall be permitted to be applied directly to the surface of the light straw-clay walls without reinforcement, except that the juncture of dissimilar substrates shall be in accordance with Section BI103.5.4. Plasters shall have a thickness of not less than 1/2 inch (12.7 mm) and not more than 1 inch (25 mm) and shall be installed in not less than two coats. Rain-exposed clay plasters shall be finished with a lime-based or silicate-mineral coating.

BI103.5.3 Separation of wood and plaster.

Where wood framing occurs in light straw-clay walls, such wood surfaces shall be separated from exterior plaster with No.15 asphalt felt, Grade D paper or other approved material except where the wood is preservative treated or naturally durable.

Exception: Exterior clay plasters shall not be required to be separated from wood.

BI103.5.4 Bridging across dissimilar substrates.

Bridging shall be installed across dissimilar substrates prior to the application of plaster. Acceptable bridging materials include expanded metal lath, woven wire mesh, welded wire mesh, fiberglass mesh, reed matting or burlap. Bridging shall extend not less than 4 inches (102 mm), on both sides of the juncture.

BI103.5.5 Exterior cladding.

Exterior cladding shall be spaced not less than 1/2 inch (12.7 mm) from the light straw-clay such that a ventilation space is created to allow for moisture diffusion. Furring strips that create this ventilation space shall be securely fastened to the stabilization members or framing. The cladding shall be fastened to the wood furring strips in accordance with the manufacturer’s instructions. Insect screening shall be provided at the top and bottom of the ventilation space.

Section BI104 Thermal Performance

BI104.1 Thermal characteristics.

Walls with light straw-clay infil of densities greater than or equal to 20 pounds per cubic foot (480.6 kg/m3) shall be classified as mass walls in accordance with Section N1102.2.6 (R402.2.6) and shall meet the R-value requirements for mass walls in Table N1102.1.3. Walls with light straw-clay infil of densities less than 20 pounds per cubic foot (480.6 kg/m3) shall meet the R-value requirements for wood frame walls in Table N1102.1.3.

BI104.2 Thermal resistance.

Light straw-clay shall be deemed to have a thermal resistance as specified in Table BI103.2.3.

Section BI105 Referenced Standards

BI105.1 General.

See Table BI105.1 for standards that are referenced in various section of this appendix. Standards are listed by the standard identification with the effective date, the standard title, and the section or sections of this appendix that reference this standard.

TABLE BI105.1 REFERENCED STANDARDS

STANDARD ACRONYM

STANDARD NAME

SECTIONS HEREIN REFERENCED

ASTM E2392/E2392M—10(2016)

Standard Guide for Design of Earthen Wall Building Systems

Table BI103.2.3

Source and transcript record

Record Georgia · 2024 IRC · Appendix BI Light Straw-Clay Construction

Effective January 1, 2026 · source captured Aug 30, 2026

Transcript SHA-256 5aa05f0f9a7634726f555d0d00deefae78fbc933ac8e7dbce639189cbe6c3a78 · text SHA-256 d9e819b4edbabffa78527ebac103a492c00e1fdc72b55f266d0411aff1395b84

Adoption authority · Official amendments · ICC chapter source