Chapter 34 General Requirements

This Electrical Part (Chapters 34 through 43) is produced and copyrighted by the National Fire Protection Association (NFPA) and is based on the 2023 National Electrical Code®(NEC®) (NFPA 70®—2023), copyright 2022, National Fire Protection Association, all rights reserved. Use of the Electrical Part is pursuant to license with the NFPA.
The title National Electrical Code®, the acronym NEC®and the document number NFPA 70®are registered trademarks of the National Fire Protection Association, Quincy, MA. The section numbers appearing in parentheses or brackets after IRC text are the section numbers of the corresponding text in the National Electrical Code (NFPA 70).
IMPORTANT NOTICE AND DISCLAIMER CONCERNING THE NEC AND THIS ELECTRICAL PART.
This Electrical Part is a compilation of provisions extracted from the 2023 edition of the NEC. The NEC, like all NFPA codes and standards, is developed through a consensus standards development process approved by the American National Standards Institute. This process brings together volunteers representing varied viewpoints and interests to achieve consensus on fire and other safety issues. While the NFPA administers the process and establishes rules to promote fairness in the development of consensus, it does not independently test, evaluate or verify the accuracy of any information or the soundness of any judgments contained in its codes and standards.
The NFPA disclaims liability for any personal injury, property or other damages of any nature whatsoever, whether special, indirect, consequential or compensatory, directly or indirectly resulting from the publication, use of, or reliance on the NEC or this Electrical Part. The NFPA also makes no guaranty or warranty as to the accuracy or completeness of any information published in these documents.
In issuing and making the NEC and this Electrical Part available, the NFPA is not undertaking to render professional or other services for or on behalf of any person or entity. Nor is the NFPA undertaking to perform any duty owed by any person or entity to someone else. Anyone using these documents should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent professional in determining the exercise of reasonable care in any given circumstances.
The NFPA has no power, nor does it undertake, to police or enforce compliance with the contents of the NEC and this Electrical Part. Nor does the NFPA list, certify, test, or inspect products, designs, or installations for compliance with these documents. Any certification or other statement of compliance with the requirements of these documents shall not be attributable to the NFPA and is solely the responsibility of the certifier or maker of the statement.
For additional notices and disclaimers concerning NFPA codes and standards see http://www.nfpa.org/disclaimers.

Section E3401 General

E3401.1 Applicability.

The provisions of Chapters 34 through 43 shall establish the general scope of the electrical system and equipment requirements of this code. Chapters 34 through 43 cover those wiring methods and materials most commonly encountered in the construction of one- and two-family dwellings and structures regulated by this code. Other wiring methods, materials and subject matter covered in NFPA 70 are also allowed by this code.

E3401.2 Scope.

Chapters 34 through 43 shall cover the installation of electrical systems, equipment and components indoors and outdoors that are within the scope of this code, including services, power distribution systems, fixtures, appliances, devices and appurtenances. Services within the scope of this code shall be limited to 120/240-volt, 0- to 400-ampere, single-phase systems. These chapters specifically cover the equipment, fixtures, appliances, wiring methods and materials that are most commonly used in the construction or alteration of one- and two-family dwellings and accessory structures regulated by this code. The omission from these chapters of any material or method of construction provided for in the referenced standard NFPA 70 shall not be construed as prohibiting the use of such material or method of construction. Electrical systems, equipment or components not specifically covered in these chapters shall comply with the applicable provisions of NFPA 70.

E3401.3 Not covered.

Chapters 34 through 43 do not cover the following:

  1. 1.

    Installations, including associated lighting, under the exclusive control of communications utilities and electric utilities.

  2. 2.

    Services over 400 amperes.

E3401.4 Additions and alterations.

Any addition or alteration to an existing electrical system shall be made in conformity to the provisions of Chapters 34 through 43. Where additions subject portions of existing systems to loads exceeding those permitted herein, such portions shall be made to comply with Chapters 34 through 43.

Section E3402 Building Structure Protection

E3402.1 Drilling and notching.

Wood-framed structural members shall not be drilled, notched or altered in any manner except as provided for in this code.

E3402.2 Penetrations of fire-resistance-rated assemblies.

Electrical installations in hollow spaces, vertical shafts and ventilation or air-handling ducts shall be made so that the possible spread of fire or products of combustion will not be substantially increased. Electrical penetrations into or through fire-resistance-rated walls, partitions, floors or ceilings shall be protected by approved methods to maintain the fire-resistance rating of the element penetrated. Penetrations of fire-resistance-rated walls shall be limited as specified in Section R302.4. (300.21)

E3402.3 Penetrations of firestops and draftstops.

Penetrations through fire blocking and draftstopping shall be protected in an approved manner to maintain the integrity of the element penetrated.

Section E3403 Inspection and Approval

E3403.1 Approval.

Electrical materials, components and equipment shall be approved. (110.2)

E3403.2 Inspection required.

New electrical work and parts of existing systems affected by new work or alterations shall be inspected by the building official to ensure compliance with the requirements of Chapters 34 through 43.

E3403.3 Listing and labeling.

Electrical materials, components, devices, fixtures and equipment shall be listed or identified for the application, shall bear the label of an approved agency and shall be installed, and used, or both, in accordance with any instructions included in the listing, labeling or identification. [110.3(B)]

Section E3404 General Equipment Requirements

E3404.1 Voltages.

Throughout Chapters 34 through 43, the voltage considered shall be that at which the circuit operates. The voltage rating of electrical equipment shall be not less than the nominal voltage of the circuit to which it is connected. (110.4)

E3404.2 Interrupting rating.

Equipment intended to interrupt current at fault levels shall have a minimum interrupting rating of 10,000 amperes at the nominal circuit voltage. Equipment intended to interrupt current at levels other than fault levels shall have an interrupting rating at nominal circuit voltage of not less than the current that must be interrupted. (110.9)

E3404.3 Circuit characteristics.

The overcurrent protective devices, total impedance, equipment short-circuit current ratings and other characteristics of the circuit to be protected shall be so selected and coordinated as to permit the circuit protective devices that are used to clear a fault to do so without extensive damage to the electrical equipment of the circuit. This fault shall be assumed to be either between two or more of the circuit conductors or between any circuit conductor and the equipment grounding conductors permitted in Section E3908.9. Listed equipment applied in accordance with its listing shall be considered to meet the requirements of this section. (110.10)

E3404.4 Enclosure types.

Enclosures, other than surrounding fences or walls, of enclosed panelboards, meter sockets, enclosed switches, transfer switches, circuit breakers, pullout switches and motor controllers, rated not over 600 volts nominal and intended for such locations, shall be marked with an enclosure-type number as shown in Table E3404.4.

Table E3404.4 shall be used for selecting these enclosures for use in specific locations other than hazardous (classified) locations. The enclosures are not intended to protect against conditions such as condensation, icing, corrosion, or contamination that might occur within the enclosure or enter through the raceway or unsealed openings. (110.28)

TABLE E3404.4 (Table 110.28) ENCLOSURE SELECTION

PROVIDES A DEGREE OF PROTECTION AGAINST THE FOLLOWING ENVIRONMENTAL CONDITIONS

FOR OUTDOOR USE

Enclosure type number

3

3R

3S

3X

3RX

3SX

4

4X

6

6P

Incidental contact with the enclosed equipment

X

X

X

X

X

X

X

X

X

X

Rain, snow and sleet

X

X

X

X

X

X

X

X

X

X

Sleeta

X

X

Windblown dust

X

X

X

X

X

X

X

X

Hosedown

X

X

X

X

Corrosive agents

X

X

X

X

X

Temporary submersion

X

X

Prolonged submersion

X

PROVIDES A DEGREE OF PROTECTION AGAINST THE FOLLOWING ENVIRONMENTAL CONDITIONS

FOR INDOOR USE

Enclosure type number

1

2

4

4X

5

6

6P

12

12K

13

Incidental contact with the enclosed equipment

X

X

X

X

X

X

X

X

X

X

Falling dirt

X

X

X

X

X

X

X

X

X

X

Falling liquids and light splashing

X

X

X

X

X

X

X

X

X

Circulating dust, lint, fibers and flyings

X

X

X

X

X

X

X

Settling airborne dust, lint, fibers and flyings

X

X

X

X

X

X

X

X

Hosedown and splashing water

X

X

X

X

Oil and coolant seepage

X

X

X

Oil or coolant spraying and splashing

X

Corrosive agents

X

X

Temporary submersion

X

X

Prolonged submersion

X

  1. a.

    The mechanism shall be operable when ice covered.

Note 1: The term “raintight” is typically used in conjunction with Enclosure Types 3, 3S, 3SX, 3X, 4, 4X, 6 and 6P. The term “rainproof” is typically used in conjunction with Enclosure Types 3R and 3RX. The term “watertight” is typically used in conjunction with Enclosure Types 4, 4X, 6 and 6P. The term “driptight” is typically used in conjunction with Enclosure Types 2, 5, 12, 12K and 13. The term “dusttight” is typically used in conjunction with Enclosure Types 3, 3S, 3SX, 3X, 5, 12, 12K and 13.

Note 2: Ingress protection (IP) ratings are found in ANSI/NEMA 60529, Degrees of Protection Provided by Enclosures.

Note 3: Some Type 4X enclosures may be marked “indoor only.”

E3404.5 Protection of equipment.

Equipment not identified for outdoor use and equipment identified only for indoor use, such as “dry locations,” “indoor use only” “damp locations,” or enclosure Type 1, 2, 5, 12, 12K and 13, shall be protected against damage from the weather during construction. (110.11)

E3404.6 Unused openings.

Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, and those permitted as part of the design for listed equipment, shall be closed to afford protection substantially equivalent to the wall of the equipment. Where metallic plugs or plates are used with nonmetallic enclosures they shall be recessed at least 1/4 inch (6.4 mm) from the outer surface of the enclosure. [110.12(A)]

E3404.7 Integrity of electrical equipment.

Internal parts of electrical equipment, including busbars, wiring terminals, insulators and other surfaces, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners or abrasives, and corrosive residues. There shall not be any damaged parts that might adversely affect safe operation or mechanical strength of the equipment such as parts that are broken; bent; cut; deteriorated by corrosion, chemical action, or overheating. Foreign debris shall be removed from equipment. [110.12(B)]

E3404.8 Mounting.

Electrical equipment shall be firmly secured to the surface on which it is mounted. Wooden plugs driven into masonry, concrete, plaster, or similar materials shall not be used. [110.13(A)]

E3404.9 Energized parts guarded against accidental contact.

Approved enclosures shall guard energized parts that are operating at 50 volts or more against accidental contact. [110.27(A)]

E3404.10 Prevent physical damage.

In locations where electrical equipment is likely to be exposed to physical damage, enclosures or guards shall be so arranged and of such strength as to prevent such damage. [110.27(B)]

E3404.11 Equipment identification.

  1. 1.

    The manufacturer’s name, trademark or other descriptive marking by which the organization responsible for the product can be identified shall be applied or affixed onto all electric equipment. Other markings shall be provided that indicate voltage, current, wattage or other ratings as specified elsewhere in Chapters 34 through 43. The marking shall have the durability to withstand the environment involved. [110.21(A)(1)]

  2. 2.

    Reconditioned equipment shall be marked with the following:

    1. 2.1.

      Name, trademark, or other descriptive marking of the organization that performed the reconditioning.

    2. 2.2.

      The date of the reconditioning.

    3. 2.3.

      The term reconditioned or other approved wording or symbol indicating that the equipment has been reconditioned.

The original listing mark shall be removed or made permanently illegible. The equipment nameplate shall not be required to be removed or made permanently illegible, only the part of the nameplate that includes the listing mark. Approval of the reconditioned equipment shall not be based solely on the equipment’s original listing. [110.21(A)(2)]

E3404.12 Field-applied hazard markings.

Where caution, warning, or danger hazard markings such as signs or labels are required by this code, the markings shall meet the following requirements:

  1. 1.

    The marking shall be of sufficient durability to withstand the environment involved and warn of the hazard using effective words, colors, symbols or any combination thereof.

  2. 2.

    The marking shall be permanently affixed to the equipment or wiring method.

  3. 3.

    Markings shall not be handwritten except for portions of markings that are variable, or that could be subject to changes. Markings shall be legible. [110.21(B)].

E3404.13 Identification of disconnecting means.

Each disconnecting means shall be legibly marked to indicate its purpose, except where located and arranged so that the purpose is evident. The marking shall have the durability to withstand the environment involved. [110.22(A)]

E3404.14 Reconditioned equipment.

Reconditioned equipment shall be permitted except where prohibited elsewhere in this code. Equipment that is restored to operating condition shall be reconditioned with identified replacement parts, verified under applicable standards, that are either provided by the original equipment manufacturer or that are designed by an engineer experienced in the design of replacement parts for the type of equipment being reconditioned. [110.20]

E3404.14.1 Equipment required to be listed.

Equipment that is reconditioned and required by this code to be listed shall be listed or field labeled as reconditioned using available instructions from the original equipment manufacturer. [110.20(A)]

E3404.14.2 Equipment not required to be listed.

Equipment that is reconditioned and not required by this code to be listed shall comply with one of the following:

  1. 1.

    Be listed or field labeled as reconditioned.

  2. 2.

    Have the reconditioning performed in accordance with the original equipment manufacturer instructions. [110.20(B)]

E3404.14.3 Approved equipment.

If the options specified in Section E3404.14.1 or E3404.14.2 are not available, the authority having jurisdiction shall be permitted to approve reconditioned equipment, and the reconditioner shall provide the authority having jurisdiction with documentation of the changes to the product. [110.20(C)]

Section E3405 Equipment Location and Clearances

E3405.1 Working space and clearances.

Working space and access to egress from working space shall be provided and maintained around all electrical equipment to permit ready and safe operation and maintenance of such equipment in accordance with this section and Figure E3405.1Open equipment doors shall not impede access to and egress from the working space. Access or egress is impeded if one or more simultaneously opened equipment doors restrict working space access to be less than 24 inches (610 mm) wide and 6.5 feet (2.0 m) high. (110.26)

FIGURE E3405.1a, b, c, d, e WORKING SPACE AND CLEARANCES
GARC2024V1.0_Pt10_Ch34_SecE3405.1_FigE3405.1.svg

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

  1. a.

    Equipment, piping and ducts foreign to the electrical installation shall not be placed in the shaded areas extending from the floor to a height of 6 feet above the panelboard enclosure or to the structural ceiling, whichever is lower.

  2. b.

    The working space shall be clear and unobstructed from the floor to a height of 6.5 feet or the height of the equipment, whichever is greater.

  3. c.

    The working space shall not be designated for storage.

  4. d.

    Panelboards, service equipment and similar enclosures shall not be located in bathrooms, toilet rooms, clothes closets or over the steps of a stairway.

  5. e.

    Such work spaces shall be provided with artificial lighting where located indoors and shall not be controlled by automatic means only.

E3405.2 Working clearances for energized equipment and panelboards.

Except as otherwise specified in Chapters 34 through 43, the dimension of the working space in the direction of access to panelboards and live parts of other equipment likely to require examination, adjustment, servicing or maintenance while energized shall be not less than 36 inches (914 mm) in depth. Distances shall be measured from the energized parts where such parts are exposed or from the enclosure front or opening where such parts are enclosed. In addition to the 36-inch dimension (914 mm), the work space shall not be less than 30 inches (762 mm) wide in front of the electrical equipment and not less than the width of such equipment. The work space shall be clear and shall extend from the floor or platform to a height of 6.5 feet (1981 mm) or the height of the equipment, whichever is greater. In all cases, the work space shall allow at least a 90-degree (1.57 rad) opening of equipment doors or hinged panels. Equipment or support structures, such as concrete pads, associated with the electrical installation located above or below the electrical equipment shall be permitted to extend not more than 6 inches (152 mm) beyond the front of the electrical equipment.

Where such equipment is required by installation instruction or function to be located in a space with limited access, all of the following shall apply:

  1. 1.

    Where the equipment is installed above a lay-in ceiling, there shall be an opening not smaller than 22 inches by 22 inches (559 mm by 559 mm), or in a crawl space, there shall be an accessible opening not smaller than 22 inches by 30 inches (559 mm by 762 mm).

  2. 2.

    The width of the working space shall be the width of the equipment enclosure or not less than 30 inches (762 mm), whichever is greater.

  3. 3.

    Enclosure doors and hinged panels shall be capable of opening not less than 90 degrees.

  4. 4.

    The space in front of the enclosure shall comply with the depth requirements of Table 110.26(A)(1) of NFPA 70. The maximum height of the working space shall be the height necessary to install the equipment in the limited space. A horizontal ceiling structural member or access panel shall be permitted in this space. [110.26(A) (1), (2), (3), (4)]

Exceptions:

  1. 1.

    In existing dwelling units, service equipment and panelboards that are not rated in excess of 200 amperes shall be permitted in spaces where the height of the working space is less than 6.5 feet (1981 mm). [110.26(A)(3) Exception No. 1]

  2. 2.

    Meters that are installed in meter sockets shall be permitted to extend beyond the other equipment. Meter sockets shall not be exempt from the requirements of this section. [110.26(A)(3) Exception No. 2]

E3405.3 Indoor dedicated panelboard space.

The indoor space equal to the width and depth of the panelboard and extending from the floor to a height of 6 feet (1829 mm) above the panelboard, or to the structural ceiling, whichever is lower, shall be dedicated to the electrical installation. Piping, ducts, leak protection apparatus and other equipment foreign to the electrical installation shall not be installed in such dedicated space. The area above the dedicated space shall be permitted to contain foreign systems, provided that protection is installed to avoid damage to the electrical equipment from condensation, leaks and breaks in such foreign systems (see Figure E3405.1). [110.26(E)(1)]

Exception: Suspended ceilings with removable panels shall be permitted within the 6-foot (1829 mm) dedicated space. [110.26(E)(1)]

E3405.4 Outdoor dedicated panelboard space.

The outdoor space equal to the width and depth of the panelboard, and extending from grade to a height of 6 feet (1829 mm) above the panelboard, shall be dedicated to the electrical installation. Piping and other equipment foreign to the electrical installation shall not be located in this zone. [110.26(E)(2)]

E3405.5 Location of working spaces and equipment.

Required working space shall not be designated for storage. Panelboards and overcurrent protection devices shall not be located in clothes closets, in bathrooms, or over the steps of a stairway. [110.26(B), 240.24(D), (E), (F)]

E3405.6 Access and entrance to working space.

Access shall be provided to the required working space. [110.26(C)(1)]

E3405.7 Illumination.

Artificial illumination shall be provided for all working spaces for service equipment and enclosed panelboards installed indoors and all illumination shall not be controlled by automatic means only. Additional lighting outlets shall not be required where the workspace is illuminated by an adjacent light source or as permitted by Exception 1 of Section E3903.2 for switched receptacles. [110.26(D)]

E3405.8 In sight from (within sight from, within sight of).

Where this code specifies that one piece of equipment shall be “in sight from,” “within sight from,” or “within sight of” another piece of equipment, the specified equipment shall be visible and not more than 50 feet (15 m) distant from the other. [110.29]

Section E3406 Electrical Conductors and Connections

E3406.1 General.

This section provides general requirements for conductors, connections and splices. These requirements do not apply to conductors that form an integral part of equipment, such as motors, appliances and similar equipment, or to conductors specifically provided for elsewhere in Chapters 34 through 43. (310.1)

E3406.2 Conductor material.

Conductors used to conduct current shall be of copper-clad aluminum or copper-aluminum except as otherwise provided in Chapters 34 through 43. If the conductor material is not specified, the material and the sizes given in these chapters shall apply to copper conductors. If other materials are used, the conductor sizes shall be changed accordingly. (110.5)

E3406.3 Minimum size of conductors.

The minimum size of conductors for feeders and branch circuits shall be 14 AWG copper and 12 AWG aluminum or copper-clad aluminum. The minimum size of service conductors shall be as specified in Chapter 36. The minimum size of Class 2 remote control, signaling and power-limited circuits conductors shall be as specified in Chapter 43. [310.3(A)]

E3406.4 Stranded conductors.

Where installed in raceways, conductors 8 AWG and larger shall be stranded. A solid 8 AWG conductor shall be permitted to be installed in a raceway only to meet the requirements of Sections E3610.2 and E4204. [310.3(C)]

E3406.5 Individual conductor insulation.

Except where otherwise permitted in Sections E3605.1 and E3908.10, and E4303, current-carrying conductors shall be insulated. Insulated conductors shall have insulation types identified as RHH, RHW, RHW-2, THHN, THHW, THW, THW-2, THWN, THWN-2, TW, UF, USE, USE-2, XHHW, XHHW-2, XHWN, XHWN-2, XHHN, XHWN or XHWN-2. Insulation types shall be identified for the application. [310.10(B), (C), 310.4]

E3406.6 Conductors in parallel.

Circuit conductors that are connected in parallel shall be limited to sizes 1/0 AWG and larger. Conductors in parallel shall: be of the same length; consist of the same conductor material; be the same circular mil area and have the same insulation type. Conductors in parallel shall be terminated in the same manner. Where run in separate raceways or cables, the raceway or cables shall have the same physical characteristics. Where conductors are in separate raceways or cables, the same number of conductors shall be used in each raceway or cable. [310.10(G)]

E3406.7 Conductors of the same circuit.

All conductors of the same circuit and, where used, the grounded conductor and all equipment grounding conductors and bonding conductors shall be contained within the same raceway, cable or cord. [300.3(B)]

E3406.8 Aluminum and copper connections.

Terminals and splicing connectors shall be identified for the material of the conductors joined. Conductors of dissimilar metals shall not be joined in a terminal or splicing connector where physical contact occurs between dissimilar conductors except where the device is listed for the purpose and conditions of application. Materials such as inhibitors and compounds shall be suitable for the application and shall be of a type that will not adversely affect the conductors, installation or equipment. (110.14)

E3406.9 Fine stranded conductors.

Connectors and terminals for conductors that are more finely stranded than Class B and Class C stranding, as shown in Table E3406.9, shall be identified for the specific conductor class or classes. (110.14)

TABLE E3406.9 (Chapter 9, Table 10) CONDUCTOR STRANDINGc

CONDUCTOR SIZE

NUMBER OF STRANDS

Copper

Aluminum

AWG or kcmil

mm2

Class B

Class C

Class B

24-30

0.20-0.05

Note a

22

0.32

7

20

0.52

10

18

0.82

16

16

1.3

26

14-2

2.1-33.6

7

19

7b

1-4/0

42.4-107

19

37

19

250-500

127-253

37

61

37

600-1000

304-508

61

91

61

1250-1500

635-759

91

127

91

1750-2000

886-1016

127

271

127

  1. a.

    Number of strands varies.

  2. b.

    Aluminum 14 AWG (2.1 mm2) is not available.

  3. c.

    With the permission of UL Standards & Engagement, this material is reproduced from UL Standard 486A-486B, Wire Connectors, which is copyrighted by UL Standards & Engagement, Northbrook, Illinois. While use of this material has been authorized, UL shall not be responsible for the manner in which the information is presented, nor for any interpretations thereof.

E3406.10 Terminals.

Connection of conductors to terminal parts shall be made without damaging the conductors and shall be made by means of pressure connectors, including set-screw type, by means of splices to flexible leads, or for conductor sizes of 10 AWG and smaller, by means of wire binding screws or studs and nuts having upturned lugs or the equivalent. Terminals for more than one conductor and terminals for connecting aluminum conductors shall be identified for the application. [110.14(A)]

E3406.11 Splices.

Conductors shall be spliced or joined with splicing devices listed for the purpose. Splices and joints and the free ends of conductors shall be covered with an insulation equivalent to that of the conductors or with an insulating device listed for the purpose. Wire connectors or splicing means installed on conductors for direct burial shall be listed for such use. [110.14(B)]

E3406.11.1 Continuity.

Conductors in raceways shall be continuous between outlets, boxes, and devices and shall be without splices or taps in the raceway.

Exception: Splices shall be permitted within surface-mounted raceways that have a removable cover. [300.13(A)]

E3406.11.2 Device connections.

The continuity of a grounded conductor in multiwire branch circuits shall not be dependent on connection to devices such as receptacles and lampholders. The arrangement of equipment grounding connections shall be such that the disconnection or the removal of a receptacle, luminaire or other device fed from the box does not interfere with or interrupt the grounding continuity. [300.13(B), 250.148(C)]

E3406.11.3 Length of conductor for splice or termination.

Where conductors are to be spliced, terminated or connected to fixtures or devices, a minimum length of 6 inches (152 mm) of free conductor shall be provided at each outlet, junction or switch point. The 6 inches (152 mm) free conductor shall be permitted to be spliced or unspliced. The required length shall be measured from the point in the box where the conductor emerges from its raceway or cable sheath. Where the opening to an outlet, junction or switch point is less than 8 inches (200 mm) in any dimension, each conductor shall be long enough to extend at least 3 inches (75 mm) outside of such opening. (300.14)

E3406.12 Installation.

Tightening torque values for terminal connections shall be as indicated on equipment or in installation instructions provided by the manufacturer. An approved means shall be used to achieve the indicated torque value. [110.14 (D)]

E3406.13 Grounded conductor continuity.

The continuity of a grounded conductor shall not depend on connection to a metallic enclosure, raceway or cable armor. [200.2(B)]

E3406.14 Connection of grounding and bonding equipment.

The connection of equipment grounding conductors, grounding electrode conductors and bonding jumpers shall be in accordance with Sections E3406.14.1 and E3406.14.2.

E3406.14.1 Permitted methods.

Equipment grounding conductors, grounding electrode conductors, and bonding jumpers shall be connected by one or more of the following means:

  1. 1.

    Listed pressure connectors.

  2. 2.

    Terminal bars.

  3. 3.

    Pressure connectors listed as grounding and bonding equipment.

  4. 4.

    Exothermic welding process.

  5. 5.

    Machine screw-type fasteners that engage not less than two threads or are secured with a nut.

  6. 6.

    Thread-forming machine screws that engage not less than two threads in the enclosure.

  7. 7.

    Connections that are part of a listed assembly.

  8. 8.

    Other listed means. [250.8 (A)]

E3406.14.2 Methods not permitted.

Connection devices or fittings that depend solely on solder shall not be used. [250.8 (B)]

Section E3407 Conductor and Terminal Identification

E3407.1 Grounded conductors.

Insulated grounded conductors of sizes 6 AWG or smaller shall be identified by a continuous white or gray outer finish or by three continuous white or gray stripes on other than green insulation along the entire length of the conductors. Conductors of sizes 4 AWG or larger shall be identified either by a continuous white or gray outer finish or by three continuous white or gray stripes on other than green insulation along its entire length, or, at the time of installation, be identified by a distinctive white or gray marking at its terminations. This marking shall encircle the conductor or insulation. [200.6(A) & (B)]

E3407.2 Wire-type equipment grounding conductors.

Wire-type equipment grounding conductors shall comply with Sections E3407.2.1 and E3407.2.2.

E3407.2.1 General.

Unless required elsewhere, equipment grounding conductors shall be permitted to be bare, covered or insulated. Individually covered or insulated equipment grounding conductors of the wire type shall have a continuous outer finish that is either green color or green color with one or more yellow stripes on the insulation or covering. Conductors with insulation or individual covering that is green, green with one or more yellow stripes, or otherwise identified as permitted by this section shall not be used for ungrounded or grounded circuit conductors. [250.119(A)]

E3407.2.2 Equipment grounding conductors 4 AWG and larger AWG.

Equipment grounding conductors 4 AWG and larger AWG that are not identified in accordance with Section E3407.2.1 shall, at the time of installation, be permanently identified as an equipment grounding conductor at each end and at every point where the conductor is accessible, except where such conductors are bare.

The required identification for conductors 4 AWG and larger shall encircle the conductor and shall be accomplished by one of the following:

  1. 1.

    Stripping the insulation or covering from the entire exposed length.

  2. 2.

    Coloring the exposed insulation or covering green at the termination.

  3. 3.

    Marking the exposed insulation or covering with green tape or green adhesive labels at the termination. [250.119( B )]

Exceptions:

  1. 1.

    Conductors 4 AWG and larger shall not be required to be identified in conduit bodies that do not contain splices or unused hubs. [250.119(B)(1) Exception]

  2. 2.

    Power-limited, Class 2 or Class 3 circuit cables containing only circuits operating at less than 50 volts shall be permitted to use a conductor with green insulation for other than equipment grounding purposes. [250.119(A) Exception No. 1]

E3407.3 Ungrounded conductors.

Insulation on the ungrounded conductors shall be a continuous color other than white, gray and green. [310.6(C)]

Exception: An insulated conductor that is part of a cable or flexible cord assembly and that has a white or gray finish or a finish marking with three continuous white or gray stripes shall be permitted to be used as an ungrounded conductor where it is permanently reidentified to indicate its use as an ungrounded conductor by marking tape, painting, or other effective means at all terminations and at each location where the conductor is visible and accessible. Identification shall encircle the insulation and shall be a color other than white, gray, and green. [200.7(C)(1), (2)]

Where used for single-pole, three-way or four-way switch loops, the reidentified conductor with white or gray insulation or three continuous white or gray stripes shall be used only for the supply to the switch, not as a return conductor from the switch to the outlet. [200.7(C)(1)]

E3407.4 Identification of terminals.

Terminals for attachment to conductors shall be identified in accordance with Sections E3407.4.1 and E3407.4.2.

E3407.4.1 Device terminals.

All devices excluding panelboards, provided with terminals for the attachment of conductors and intended for connection to more than one side of the circuit shall have terminals properly marked for identification, except where the terminal intended to be connected to the grounded conductor is clearly evident. [200.10(A)]

Exception: Terminal identification shall not be required for devices that have a normal current rating of over 30 amperes, other than polarized attachment caps and polarized receptacles for attachment caps as required in Section E3407.4.2. [200.10(A) Exception]

E3407.4.2 Receptacles, plugs and connectors.

Receptacles, polarized attachment plugs and cord connectors for plugs and polarized plugs shall have the terminal intended for connection to the grounded (white) conductor identified. Identification shall be by a metal or metal coating substantially white or silver in color or by the word “white” or the letter “W” located adjacent to the identified terminal. Where the terminal is not visible, the conductor entrance hole for the connection shall be colored white or marked with the word “white” or the letter “W.” [200.10(B)]