APPENDIX D
FIRE DISTRICTS
SECTION D101
GENERAL
D101.1 Scope.
D101.2 Establishment of area.
D101.2.1 Adjoining blocks.
D101.2.2 Buffer zone.
D101.2.3 Developed blocks.
SECTION D102
BUILDING RESTRICTIONS
D102.2 Other specific requirements.
D102.2.2 Group H prohibited.
D102.2.5 Structural fire rating.
Walls, floors, roofs and their supporting structural members shall be not less than 1-hour fire-resistance-rated construction.
D102.2.6 Exterior walls.
Exterior load-bearing walls of Type II buildings shall have a fire-resistance rating of 2 hours or more where such walls are located within 30 feet (9144 mm) of a common property line or an assumed property line. Exterior nonload-bearing walls of Type II buildings located within 30 feet (9144 mm) of a common property line or an assumed property line shall have fire-resistance ratings as required by Table 601, but not less than 1 hour. Exterior walls located more than 30 feet (9144 mm) from a common property line or an assumed property line shall comply with Table 601.
D102.2.7 Architectural trim.
D102.2.8 Permanent canopies.
Permanent canopies are permitted to extend over adjacent open spaces provided that all of the following are met:
1.The canopy and its supports shall be of noncombustible material, fire-retardant-treated wood, Type IV construction or of 1-hour fire-resistance-rated construction.
2.Any canopy covering, other than textiles, shall have a flame spread index not greater than 25 when tested in accordance with ASTM E84 or UL 723 in the form intended for use.
3.The canopy shall have one long side open.
4.The maximum horizontal width of the canopy shall be not greater than 15 feet (4572 mm).
5.The fire resistance of exterior walls shall not be reduced.
D102.2.9 Roof structures.
D102.2.11 Plastic veneer.
SECTION D103
CHANGES TO BUILDINGS
D103.1 Existing buildings within the fire district.
D103.3 Moving buildings.
SECTION D104
BUILDINGS LOCATED PARTIALLY IN THE FIRE DISTRICT
D104.1 General.
SECTION D105
EXCEPTIONS TO RESTRICTIONS IN FIRE DISTRICT
D105.1 General.
The preceding provisions of this appendix shall not apply in the following instances:
1.Temporary buildings used in connection with duly authorized construction.
2.A private garage used exclusively as such, not more than one story in height, nor more than 650 square feet (60 m2) in area, located on the same lot with a dwelling.
3.Fences not over 8 feet (2438 mm) high.
4.Coal tipples, material bins and trestles of Type IV construction.
5.Water tanks and cooling towers conforming to Sections 1510.3 and 1510.4.
6.Greenhouses less than 15 feet (4572 mm) high.
7.Porches on dwellings not over one story in height, and not over 10 feet (3048 mm) wide from the face of the building, provided that such porch does not come within 5 feet (1524 mm) of any property line.
8.Sheds open on a long side not over 15 feet (4572 mm) high and 500 square feet (46 m2) in area.
9.One- and two-family dwellings where of a type of construction not permitted in the fire district can be extended 25 percent of the floor area existing at the time of inclusion in the fire district by any type of construction permitted by this code.
10.Wood decks less than 600 square feet (56 m2) where constructed of 2-inch (51 mm) nominal wood, pressure treated for exterior use.
11.Wood veneers on exterior walls conforming to Section 1404.5.
12.Exterior plastic veneer complying with Section 2605.2 where installed on exterior walls required to have a fire-resistance rating not less than 1 hour, provided that the exterior plastic veneer does not exhibit sustained flaming as defined in NFPA 268.
SECTION D106
REFERENCED STANDARDS
D106.1 General.
TABLE D106.1
REFERENCED STANDARDS