Chapter 4 Gas Piping Installations

State amendments integrated218 filed sections2024 editionEffective January 1, 2026
Browse this code

Chapter 4 Gas Piping Installations

Section 401 (IFGC) General

401.1 Scope.

This chapter shall govern the design, installation, modification and maintenance of piping systems. The applicability of this code to piping systems extends from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems.

401.1.1 Utility piping systems located within buildings.

Utility service piping located within buildings shall be installed in accordance with the structural safety and fire protection provisions of the International Building Code.

401.2 Liquefied petroleum gas storage.

The storage system for liquefied petroleum gas shall be designed and installed in accordance with the International Fire Code and NFPA 58.

401.3 Modifications to existing systems.

In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter.

401.4 Additional appliances.

Where an additional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be provided.

401.5 Identification.

For other than steel pipe and CSST, exposed piping shall be identified by a yellow label marked “Gas” in black letters. The marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on piping located in the same room as the appliance served. CSST shall be identified as required by ANSI LC 1/CSA 6.26.

401.6 Interconnections.

Where two or more meters are installed on the same premises but supply separate consumers, the piping systems shall not be interconnected on the outlet side of the meters.

401.7 Piping meter identification.

Piping from multiple meter installations shall be marked with an approved permanent identification by the installer so that the piping system supplied by each meter is readily identifiable.

401.8 Minimum sizes.

Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402.

401.9 Identification.

Each length of pipe and tubing and each pipe fitting, utilized in a fuel gas system, shall bear the identification of the manufacturer.

Exceptions:

  1. 1.

    Steel pipe sections that are 2 feet (610 mm) and less in length and are cut from longer sections of pipe.

  2. 2.

    Steel pipe fittings 2 inches and less in size.

  3. 3.

    Where identification is provided on the product packaging or crating.

  4. 4.

    Where other approved documentation is provided.

401.10 Piping materials standards.

Piping, tubing and fittings shall be manufactured to the applicable referenced standards, specifications and performance criteria listed in Section 403 and shall be identified in accordance with Section 401.9.

Section 402 (IFGS) Pipe Sizing

402.1 General considerations.

Piping systems shall be of such size and so installed as to provide a supply of gas sufficient to meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance.

402.2 Maximum gas demand.

The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the appliances served.

The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to be based on such loads.

The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation.

402.3 Sizing.

Gas piping shall be sized in accordance with one of the following:

  1. 1.

    Pipe sizing tables or sizing equations in accordance with Section 402.4 or 402.5 as applicable.

  2. 2.

    The sizing tables included in a listed piping system’s manufacturer’s installation instructions.

  3. 3.

    Engineering methods.

402.4 Sizing tables and equations.

This section applies to piping materials other than noncorrugated stainless steel tubing. Where Tables 402.4(1) through 402.4(37) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3.

Where Equations 4-1 and 4-2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3.

  1. 1.

    Low-pressure gas equation [Less than 1 1/2 pounds per square inch (psi) (10.3 kPa)]:

    Equation 4-1 D = Q 0 . 381 19 . 17 ( H C r × L ) 0 . 206
  2. 2.

    High-pressure gas equation [1 1/2 psi (10.3 kPa) and above]:

    Equation 4-2 D = Q 0 . 381 18 . 93 [ P 1 2 - P 2 2 × Y C r × L ] 0 . 206

    where:

    Cr =

    Value determined by Table 402.4.

    D =

    Inside diameter of pipe, inches (mm).

    Q =

    Input rate appliance(s), cubic feet per hour at 60°F (16°C) and 30-inch mercury column.

    P1 =

    Downstream pressure, psia (P1 + 14.7).

    P2 =

    Downstream pressure, psia (P2 + 14.7).

    L =

    Equivalent length of pipe, feet.

    Y =

    Value determined by Table 402.4.

    ΔH =

    Pressure drop, inch water column (27.7-inch water column = 1 psi).

TABLE 402.4 Cr AND Y VALUES FOR NATURAL GAS AND UNDILUTED PROPANE AT STANDARD CONDITIONS

GAS

EQUATION FACTORS

Cr

Y

Natural gas

0.6094

0.9992

Undiluted propane

1.2462

0.9910

For SI: 1 cubic foot = 0.028 m3, 1 foot = 305 mm, 1-inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W.

TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

0.3 in. w.c.

Specific Gravity

0.60

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

5

6

8

10

12

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

5.047

6.065

7.981

10.020

11.938

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

131

273

514

1,060

1,580

3,050

4,860

8,580

17,500

31,700

51,300

105,000

191,000

303,000

20

90

188

353

726

1,090

2,090

3,340

5,900

12,000

21,800

35,300

72,400

132,000

208,000

30

72

151

284

583

873

1,680

2,680

4,740

9,660

17,500

28,300

58,200

106,000

167,000

40

62

129

243

499

747

1,440

2,290

4,050

8,270

15,000

24,200

49,800

90,400

143,000

50

55

114

215

442

662

1,280

2,030

3,590

7,330

13,300

21,500

44,100

80,100

127,000

60

50

104

195

400

600

1,160

1,840

3,260

6,640

12,000

19,500

40,000

72,600

115,000

70

46

95

179

368

552

1,060

1,690

3,000

6,110

11,100

17,900

36,800

66,800

106,000

80

42

89

167

343

514

989

1,580

2,790

5,680

10,300

16,700

34,200

62,100

98,400

90

40

83

157

322

482

928

1,480

2,610

5,330

9,650

15,600

32,100

58,300

92,300

100

38

79

148

304

455

877

1,400

2,470

5,040

9,110

14,800

30,300

55,100

87,200

125

33

70

131

269

403

777

1,240

2,190

4,460

8,080

13,100

26,900

48,800

77,300

150

30

63

119

244

366

704

1,120

1,980

4,050

7,320

11,900

24,300

44,200

70,000

175

28

58

109

224

336

648

1,030

1,820

3,720

6,730

10,900

22,400

40,700

64,400

200

26

54

102

209

313

602

960

1,700

3,460

6,260

10,100

20,800

37,900

59,900

250

23

48

90

185

277

534

851

1,500

3,070

5,550

8,990

18,500

33,500

53,100

300

21

43

82

168

251

484

771

1,360

2,780

5,030

8,150

16,700

30,400

48,100

350

19

40

75

154

231

445

709

1,250

2,560

4,630

7,490

15,400

28,000

44,300

400

18

37

70

143

215

414

660

1,170

2,380

4,310

6,970

14,300

26,000

41,200

450

17

35

66

135

202

389

619

1,090

2,230

4,040

6,540

13,400

24,400

38,600

500

16

33

62

127

191

367

585

1,030

2,110

3,820

6,180

12,700

23,100

36,500

550

15

31

59

121

181

349

556

982

2,000

3,620

5,870

12,100

21,900

34,700

600

14

30

56

115

173

333

530

937

1,910

3,460

5,600

11,500

20,900

33,100

650

14

29

54

110

165

318

508

897

1,830

3,310

5,360

11,000

20,000

31,700

700

13

27

52

106

159

306

488

862

1,760

3,180

5,150

10,600

19,200

30,400

750

13

26

50

102

153

295

470

830

1,690

3,060

4,960

10,200

18,500

29,300

800

12

26

48

99

148

285

454

802

1,640

2,960

4,790

9,840

17,900

28,300

850

12

25

46

95

143

275

439

776

1,580

2,860

4,640

9,530

17,300

27,400

900

11

24

45

93

139

267

426

752

1,530

2,780

4,500

9,240

16,800

26,600

950

11

23

44

90

135

259

413

731

1,490

2,700

4,370

8,970

16,300

25,800

1,000

11

23

43

87

131

252

402

711

1,450

2,620

4,250

8,720

15,800

25,100

1,100

10

21

40

83

124

240

382

675

1,380

2,490

4,030

8,290

15,100

23,800

1,200

NA

20

39

79

119

229

364

644

1,310

2,380

3,850

7,910

14,400

22,700

1,300

NA

20

37

76

114

219

349

617

1,260

2,280

3,680

7,570

13,700

21,800

1,400

NA

19

35

73

109

210

335

592

1,210

2,190

3,540

7,270

13,200

20,900

1,500

NA

18

34

70

105

203

323

571

1,160

2,110

3,410

7,010

12,700

20,100

1,600

NA

18

33

68

102

196

312

551

1,120

2,030

3,290

6,770

12,300

19,500

1,700

NA

17

32

66

98

189

302

533

1,090

1,970

3,190

6,550

11,900

18,800

1,800

NA

16

31

64

95

184

293

517

1,050

1,910

3,090

6,350

11,500

18,300

1,900

NA

16

30

62

93

178

284

502

1,020

1,850

3,000

6,170

11,200

17,700

2,000

NA

16

29

60

90

173

276

488

1,000

1,800

2,920

6,000

10,900

17,200

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    NA means a flow of less than 10 cfh.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

0.5 in. w.c.

Specific Gravity

0.60

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

5

6

8

10

12

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

5.047

6.065

7.981

10.020

11.938

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

172

360

678

1,390

2,090

4,020

6,400

11,300

23,100

41,800

67,600

139,000

252,000

399,000

20

118

247

466

957

1,430

2,760

4,400

7,780

15,900

28,700

46,500

95,500

173,000

275,000

30

95

199

374

768

1,150

2,220

3,530

6,250

12,700

23,000

37,300

76,700

139,000

220,000

40

81

170

320

657

985

1,900

3,020

5,350

10,900

19,700

31,900

65,600

119,000

189,000

50

72

151

284

583

873

1,680

2,680

4,740

9,660

17,500

28,300

58,200

106,000

167,000

60

65

137

257

528

791

1,520

2,430

4,290

8,760

15,800

25,600

52,700

95,700

152,000

70

60

126

237

486

728

1,400

2,230

3,950

8,050

14,600

23,600

48,500

88,100

139,000

80

56

117

220

452

677

1,300

2,080

3,670

7,490

13,600

22,000

45,100

81,900

130,000

90

52

110

207

424

635

1,220

1,950

3,450

7,030

12,700

20,600

42,300

76,900

122,000

100

50

104

195

400

600

1,160

1,840

3,260

6,640

12,000

19,500

40,000

72,600

115,000

125

44

92

173

355

532

1,020

1,630

2,890

5,890

10,600

17,200

35,400

64,300

102,000

150

40

83

157

322

482

928

1,480

2,610

5,330

9,650

15,600

32,100

58,300

92,300

175

37

77

144

296

443

854

1,360

2,410

4,910

8,880

14,400

29,500

53,600

84,900

200

34

71

134

275

412

794

1,270

2,240

4,560

8,260

13,400

27,500

49,900

79,000

250

30

63

119

244

366

704

1,120

1,980

4,050

7,320

11,900

24,300

44,200

70,000

300

27

57

108

221

331

638

1,020

1,800

3,670

6,630

10,700

22,100

40,100

63,400

350

25

53

99

203

305

587

935

1,650

3,370

6,100

9,880

20,300

36,900

58,400

400

23

49

92

189

283

546

870

1,540

3,140

5,680

9,190

18,900

34,300

54,300

450

22

46

86

177

266

512

816

1,440

2,940

5,330

8,620

17,700

32,200

50,900

500

21

43

82

168

251

484

771

1,360

2,780

5,030

8,150

16,700

30,400

48,100

550

20

41

78

159

239

459

732

1,290

2,640

4,780

7,740

15,900

28,900

45,700

600

19

39

74

152

228

438

699

1,240

2,520

4,560

7,380

15,200

27,500

43,600

650

18

38

71

145

218

420

669

1,180

2,410

4,360

7,070

14,500

26,400

41,800

700

17

36

68

140

209

403

643

1,140

2,320

4,190

6,790

14,000

25,300

40,100

750

17

35

66

135

202

389

619

1,090

2,230

4,040

6,540

13,400

24,400

38,600

800

16

34

63

130

195

375

598

1,060

2,160

3,900

6,320

13,000

23,600

37,300

850

16

33

61

126

189

363

579

1,020

2,090

3,780

6,110

12,600

22,800

36,100

900

15

32

59

122

183

352

561

992

2,020

3,660

5,930

12,200

22,100

35,000

950

15

31

58

118

178

342

545

963

1,960

3,550

5,760

11,800

21,500

34,000

1,000

14

30

56

115

173

333

530

937

1,910

3,460

5,600

11,500

20,900

33,100

1,100

14

28

53

109

164

316

503

890

1,810

3,280

5,320

10,900

19,800

31,400

1,200

13

27

51

104

156

301

480

849

1,730

3,130

5,070

10,400

18,900

30,000

1,300

12

26

49

100

150

289

460

813

1,660

3,000

4,860

9,980

18,100

28,700

1,400

12

25

47

96

144

277

442

781

1,590

2,880

4,670

9,590

17,400

27,600

1,500

11

24

45

93

139

267

426

752

1,530

2,780

4,500

9,240

16,800

26,600

1,600

11

23

44

89

134

258

411

727

1,480

2,680

4,340

8,920

16,200

25,600

1,700

11

22

42

86

130

250

398

703

1,430

2,590

4,200

8,630

15,700

24,800

1,800

10

22

41

84

126

242

386

682

1,390

2,520

4,070

8,370

15,200

24,100

1,900

10

21

40

81

122

235

375

662

1,350

2,440

3,960

8,130

14,800

23,400

2,000

NA

20

39

79

119

229

364

644

1,310

2,380

3,850

7,910

14,400

22,700

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    NA means a flow of less than 10 cfh.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

3.0 in. w.c.

Specific Gravity

0.60

INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0-INCH W.C. OR GREATER

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

454

949

1,790

3,670

5,500

10,600

16,900

29,800

60,800

20

312

652

1,230

2,520

3,780

7,280

11,600

20,500

41,800

30

250

524

986

2,030

3,030

5,840

9,310

16,500

33,600

40

214

448

844

1,730

2,600

5,000

7,970

14,100

28,700

50

190

397

748

1,540

2,300

4,430

7,070

12,500

25,500

60

172

360

678

1,390

2,090

4,020

6,400

11,300

23,100

70

158

331

624

1,280

1,920

3,700

5,890

10,400

21,200

80

147

308

580

1,190

1,790

3,440

5,480

9,690

19,800

90

138

289

544

1,120

1,680

3,230

5,140

9,090

18,500

100

131

273

514

1,060

1,580

3,050

4,860

8,580

17,500

125

116

242

456

936

1,400

2,700

4,300

7,610

15,500

150

105

219

413

848

1,270

2,450

3,900

6,890

14,100

175

96

202

380

780

1,170

2,250

3,590

6,340

12,900

200

90

188

353

726

1,090

2,090

3,340

5,900

12,000

250

80

166

313

643

964

1,860

2,960

5,230

10,700

300

72

151

284

583

873

1,680

2,680

4,740

9,700

350

66

139

261

536

803

1,550

2,470

4,360

8,900

400

62

129

243

499

747

1,440

2,290

4,060

8,300

450

58

121

228

468

701

1,350

2,150

3,800

7,800

500

55

114

215

442

662

1,280

2,030

3,590

7,300

550

52

109

204

420

629

1,210

1,930

3,410

7,000

600

50

104

195

400

600

1,160

1,840

3,260

6,640

650

47

99

187

384

575

1,110

1,760

3,120

6,360

700

46

95

179

368

552

1,060

1,700

3,000

6,110

750

44

92

173

355

532

1,020

1,630

2,890

5,890

800

42

89

167

343

514

989

1,580

2,790

5,680

850

41

86

162

332

497

957

1,530

2,700

5,500

900

40

83

157

322

482

928

1,480

2,620

5,330

950

39

81

152

312

468

901

1,440

2,540

5,180

1,000

38

79

148

304

455

877

1,400

2,470

5,040

1,100

36

75

141

289

432

833

1,330

2,350

4,780

1,200

34

71

134

275

412

794

1,270

2,240

4,560

1,300

33

68

128

264

395

761

1,210

2,140

4,370

1,400

31

65

123

253

379

731

1,170

2,060

4,200

1,500

30

63

119

244

366

704

1,120

1,980

4,050

1,600

29

61

115

236

353

680

1,080

1,920

3,910

1,700

28

59

111

228

342

658

1,050

1,850

3,780

1,800

27

57

108

221

331

638

1,020

1,800

3,670

1,900

27

56

105

215

322

619

987

1,750

3,560

2,000

26

54

102

209

313

602

960

1,700

3,460

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

6.0 in. w.c.

Specific Gravity

0.60

INTENDED USE: INITIAL SUPPLY PRESSURE OF 11.0-INCH W.C. OR GREATER

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

660

1,380

2,600

5,340

8,000

15,400

24,600

43,400

88,500

20

454

949

1,790

3,670

5,500

10,600

16,900

29,900

60,800

30

364

762

1,440

2,950

4,420

8,500

13,600

24,000

48,900

40

312

652

1,230

2,520

3,780

7,280

11,600

20,500

41,800

50

276

578

1,090

2,240

3,350

6,450

10,300

18,200

37,100

60

250

524

986

2,030

3,030

5,840

9,310

16,500

33,600

70

230

482

907

1,860

2,790

5,380

8,570

15,100

30,900

80

214

448

844

1,730

2,600

5,000

7,970

14,100

28,700

90

201

420

792

1,630

2,440

4,690

7,480

13,200

27,000

100

190

397

748

1,540

2,300

4,430

7,070

12,500

25,500

125

168

352

663

1,360

2,040

3,930

6,260

11,100

22,600

150

153

319

601

1,230

1,850

3,560

5,670

10,000

20,500

175

140

293

553

1,140

1,700

3,280

5,220

9,230

18,800

200

131

273

514

1,060

1,580

3,050

4,860

8,580

17,500

250

116

242

456

936

1,400

2,700

4,300

7,610

15,500

300

105

219

413

848

1,270

2,450

3,900

6,890

14,100

350

96

202

380

780

1,170

2,250

3,590

6,340

12,900

400

90

188

353

726

1,090

2,090

3,340

5,900

12,000

450

84

176

332

681

1,020

1,970

3,130

5,540

11,300

500

80

166

313

643

964

1,860

2,960

5,230

10,700

550

76

158

297

611

915

1,760

2,810

4,970

10,100

600

72

151

284

583

873

1,680

2,680

4,740

9,660

650

69

144

272

558

836

1,610

2,570

4,540

9,250

700

66

139

261

536

803

1,550

2,470

4,360

8,890

750

64

134

252

516

774

1,490

2,380

4,200

8,560

800

62

129

243

499

747

1,440

2,290

4,060

8,270

850

60

125

235

483

723

1,390

2,220

3,920

8,000

900

58

121

228

468

701

1,350

2,150

3,800

7,760

950

56

118

221

454

681

1,310

2,090

3,700

7,540

1,000

55

114

215

442

662

1,280

2,030

3,590

7,330

1,100

52

109

204

420

629

1,210

1,930

3,410

6,960

1,200

50

104

195

400

600

1,160

1,840

3,260

6,640

1,300

47

99

187

384

575

1,100

1,760

3,120

6,360

1,400

46

95

179

368

552

1,060

1,700

3,000

6,110

1,500

44

92

173

355

532

1,020

1,630

2,890

5,890

1,600

42

89

167

343

514

989

1,580

2,790

5,680

1,700

41

86

162

332

497

957

1,530

2,700

5,500

1,800

40

83

157

322

482

928

1,480

2,620

5,330

1,900

39

81

152

312

468

901

1,440

2,540

5,180

2,000

38

79

148

304

455

877

1,400

2,470

5,040

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits

TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE

Gas

Natural

Inlet Pressure

2.0 psi

Pressure Drop

1.0 psi

Specific Gravity

0.60

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

1,510

3,040

5,560

11,400

17,100

32,900

52,500

92,800

189,000

20

1,070

2,150

3,930

8,070

12,100

23,300

37,100

65,600

134,000

30

869

1,760

3,210

6,590

9,880

19,000

30,300

53,600

109,000

40

753

1,520

2,780

5,710

8,550

16,500

26,300

46,400

94,700

50

673

1,360

2,490

5,110

7,650

14,700

23,500

41,500

84,700

60

615

1,240

2,270

4,660

6,980

13,500

21,400

37,900

77,300

70

569

1,150

2,100

4,320

6,470

12,500

19,900

35,100

71,600

80

532

1,080

1,970

4,040

6,050

11,700

18,600

32,800

67,000

90

502

1,010

1,850

3,810

5,700

11,000

17,500

30,900

63,100

100

462

934

1,710

3,510

5,260

10,100

16,100

28,500

58,200

125

414

836

1,530

3,140

4,700

9,060

14,400

25,500

52,100

150

372

751

1,370

2,820

4,220

8,130

13,000

22,900

46,700

175

344

695

1,270

2,601

3,910

7,530

12,000

21,200

43,300

200

318

642

1,170

2,410

3,610

6,960

11,100

19,600

40,000

250

279

583

1,040

2,140

3,210

6,180

9,850

17,400

35,500

300

253

528

945

1,940

2,910

5,600

8,920

15,800

32,200

350

232

486

869

1,790

2,670

5,150

8,210

14,500

29,600

400

216

452

809

1,660

2,490

4,790

7,640

13,500

27,500

450

203

424

759

1,560

2,330

4,500

7,170

12,700

25,800

500

192

401

717

1,470

2,210

4,250

6,770

12,000

24,400

550

182

381

681

1,400

2,090

4,030

6,430

11,400

23,200

600

174

363

650

1,330

2,000

3,850

6,130

10,800

22,100

650

166

348

622

1,280

1,910

3,680

5,870

10,400

21,200

700

160

334

598

1,230

1,840

3,540

5,640

9,970

20,300

750

154

322

576

1,180

1,770

3,410

5,440

9,610

19,600

800

149

311

556

1,140

1,710

3,290

5,250

9,280

18,900

850

144

301

538

1,100

1,650

3,190

5,080

8,980

18,300

900

139

292

522

1,070

1,600

3,090

4,930

8,710

17,800

950

135

283

507

1,040

1,560

3,000

4,780

8,460

17,200

1,000

132

275

493

1,010

1,520

2,920

4,650

8,220

16,800

1,100

125

262

468

960

1,440

2,770

4,420

7,810

15,900

1,200

119

250

446

917

1,370

2,640

4,220

7,450

15,200

1,300

114

239

427

878

1,320

2,530

4,040

7,140

14,600

1,400

110

230

411

843

1,260

2,430

3,880

6,860

14,000

1,500

106

221

396

812

1,220

2,340

3,740

6,600

13,500

1,600

102

214

382

784

1,180

2,260

3,610

6,380

13,000

1,700

99

207

370

759

1,140

2,190

3,490

6,170

12,600

1,800

96

200

358

736

1,100

2,120

3,390

5,980

12,200

1,900

93

195

348

715

1,070

2,060

3,290

5,810

11,900

2,000

91

189

339

695

1,040

2,010

3,200

5,650

11,500

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes: Table entries have been rounded to three significant digits.

TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE

Gas

Natural

Inlet Pressure

3.0 psi

Pressure Drop

2.0 psi

Specific Gravity

0.60

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

2,350

4,920

9,270

19,000

28,500

54,900

87,500

155,000

316,000

20

1,620

3,380

6,370

13,100

19,600

37,700

60,100

106,000

217,000

30

1,300

2,720

5,110

10,500

15,700

30,300

48,300

85,400

174,000

40

1,110

2,320

4,380

8,990

13,500

25,900

41,300

73,100

149,000

50

985

2,060

3,880

7,970

11,900

23,000

36,600

64,800

132,000

60

892

1,870

3,520

7,220

10,800

20,800

33,200

58,700

120,000

70

821

1,720

3,230

6,640

9,950

19,200

30,500

54,000

110,000

80

764

1,600

3,010

6,180

9,260

17,800

28,400

50,200

102,000

90

717

1,500

2,820

5,800

8,680

16,700

26,700

47,100

96,100

100

677

1,420

2,670

5,470

8,200

15,800

25,200

44,500

90,800

125

600

1,250

2,360

4,850

7,270

14,000

22,300

39,500

80,500

150

544

1,140

2,140

4,400

6,590

12,700

20,200

35,700

72,900

175

500

1,050

1,970

4,040

6,060

11,700

18,600

32,900

67,100

200

465

973

1,830

3,760

5,640

10,900

17,300

30,600

62,400

250

412

862

1,620

3,330

5,000

9,620

15,300

27,100

55,300

300

374

781

1,470

3,020

4,530

8,720

13,900

24,600

50,100

350

344

719

1,350

2,780

4,170

8,020

12,800

22,600

46,100

400

320

669

1,260

2,590

3,870

7,460

11,900

21,000

42,900

450

300

627

1,180

2,430

3,640

7,000

11,200

19,700

40,200

500

283

593

1,120

2,290

3,430

6,610

10,500

18,600

38,000

550

269

563

1,060

2,180

3,260

6,280

10,000

17,700

36,100

600

257

537

1,010

2,080

3,110

5,990

9,550

16,900

34,400

650

246

514

969

1,990

2,980

5,740

9,150

16,200

33,000

700

236

494

931

1,910

2,860

5,510

8,790

15,500

31,700

750

228

476

897

1,840

2,760

5,310

8,470

15,000

30,500

800

220

460

866

1,780

2,660

5,130

8,180

14,500

29,500

850

213

445

838

1,720

2,580

4,960

7,910

14,000

28,500

900

206

431

812

1,670

2,500

4,810

7,670

13,600

27,700

950

200

419

789

1,620

2,430

4,670

7,450

13,200

26,900

1,000

195

407

767

1,580

2,360

4,550

7,240

12,800

26,100

1,100

185

387

729

1,500

2,240

4,320

6,890

12,200

24,800

1,200

177

369

695

1,430

2,140

4,120

6,570

11,600

23,700

1,300

169

353

666

1,370

2,050

3,940

6,290

11,100

22,700

1,400

162

340

640

1,310

1,970

3,790

6,040

10,700

21,800

1,500

156

327

616

1,270

1,900

3,650

5,820

10,300

21,000

1,600

151

316

595

1,220

1,830

3,530

5,620

10,000

20,300

1,700

146

306

576

1,180

1,770

3,410

5,440

9,610

19,600

1,800

142

296

558

1,150

1,720

3,310

5,270

9,320

19,000

1,900

138

288

542

1,110

1,670

3,210

5,120

9,050

18,400

2,000

134

280

527

1,080

1,620

3,120

4,980

8,800

18,000

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE

Gas

Natural

Inlet Pressure

5.0 psi

Pressure Drop

3.5 psi

Specific Gravity

0.60

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

3,190

6,430

11,800

24,200

36,200

69,700

111,000

196,000

401,000

20

2,250

4,550

8,320

17,100

25,600

49,300

78,600

139,000

283,000

30

1,840

3,720

6,790

14,000

20,900

40,300

64,200

113,000

231,000

40

1,590

3,220

5,880

12,100

18,100

34,900

55,600

98,200

200,000

50

1,430

2,880

5,260

10,800

16,200

31,200

49,700

87,900

179,000

60

1,300

2,630

4,800

9,860

14,800

28,500

45,400

80,200

164,000

70

1,200

2,430

4,450

9,130

13,700

26,400

42,000

74,300

151,000

80

1,150

2,330

4,260

8,540

12,800

24,700

39,300

69,500

142,000

90

1,060

2,150

3,920

8,050

12,100

23,200

37,000

65,500

134,000

100

979

1,980

3,620

7,430

11,100

21,400

34,200

60,400

123,000

125

876

1,770

3,240

6,640

9,950

19,200

30,600

54,000

110,000

150

786

1,590

2,910

5,960

8,940

17,200

27,400

48,500

98,900

175

728

1,470

2,690

5,520

8,270

15,900

25,400

44,900

91,600

200

673

1,360

2,490

5,100

7,650

14,700

23,500

41,500

84,700

250

558

1,170

2,200

4,510

6,760

13,000

20,800

36,700

74,900

300

506

1,060

1,990

4,090

6,130

11,800

18,800

33,300

67,800

350

465

973

1,830

3,760

5,640

10,900

17,300

30,600

62,400

400

433

905

1,710

3,500

5,250

10,100

16,100

28,500

58,100

450

406

849

1,600

3,290

4,920

9,480

15,100

26,700

54,500

500

384

802

1,510

3,100

4,650

8,950

14,300

25,200

51,500

550

364

762

1,440

2,950

4,420

8,500

13,600

24,000

48,900

600

348

727

1,370

2,810

4,210

8,110

12,900

22,900

46,600

650

333

696

1,310

2,690

4,030

7,770

12,400

21,900

44,600

700

320

669

1,260

2,590

3,880

7,460

11,900

21,000

42,900

750

308

644

1,210

2,490

3,730

7,190

11,500

20,300

41,300

800

298

622

1,170

2,410

3,610

6,940

11,100

19,600

39,900

850

288

602

1,130

2,330

3,490

6,720

10,700

18,900

38,600

900

279

584

1,100

2,260

3,380

6,520

10,400

18,400

37,400

950

271

567

1,070

2,190

3,290

6,330

10,100

17,800

36,400

1,000

264

551

1,040

2,130

3,200

6,150

9,810

17,300

35,400

1,100

250

524

987

2,030

3,030

5,840

9,320

16,500

33,600

1,200

239

500

941

1,930

2,900

5,580

8,890

15,700

32,000

1,300

229

478

901

1,850

2,770

5,340

8,510

15,000

30,700

1,400

220

460

866

1,780

2,660

5,130

8,180

14,500

29,500

1,500

212

443

834

1,710

2,570

4,940

7,880

13,900

28,400

1,600

205

428

806

1,650

2,480

4,770

7,610

13,400

27,400

1,700

198

414

780

1,600

2,400

4,620

7,360

13,000

26,500

1,800

192

401

756

1,550

2,330

4,480

7,140

12,600

25,700

1,900

186

390

734

1,510

2,260

4,350

6,930

12,300

25,000

2,000

181

379

714

1,470

2,200

4,230

6,740

11,900

24,300

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(8) SEMIRIGID COPPER TUBING

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

0.3 in. w.c.

Specific Gravity

0.60

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

20

42

85

148

210

448

806

1,270

2,650

20

14

29

58

102

144

308

554

873

1,820

30

11

23

47

82

116

247

445

701

1,460

40

10

20

40

70

99

211

381

600

1,250

50

NA

17

35

62

88

187

337

532

1,110

60

NA

16

32

56

79

170

306

482

1,000

70

NA

14

29

52

73

156

281

443

924

80

NA

13

27

48

68

145

262

413

859

90

NA

13

26

45

64

136

245

387

806

100

NA

12

24

43

60

129

232

366

761

125

NA

11

22

38

53

114

206

324

675

150

NA

10

20

34

48

103

186

294

612

175

NA

NA

18

31

45

95

171

270

563

200

NA

NA

17

29

41

89

159

251

523

250

NA

NA

15

26

37

78

141

223

464

300

NA

NA

13

23

33

71

128

202

420

350

NA

NA

12

22

31

65

118

186

387

400

NA

NA

11

20

28

61

110

173

360

450

NA

NA

11

19

27

57

103

162

338

500

NA

NA

10

18

25

54

97

153

319

550

NA

NA

NA

17

24

51

92

145

303

600

NA

NA

NA

16

23

49

88

139

289

650

NA

NA

NA

15

22

47

84

133

277

700

NA

NA

NA

15

21

45

81

128

266

750

NA

NA

NA

14

20

43

78

123

256

800

NA

NA

NA

14

20

42

75

119

247

850

NA

NA

NA

13

19

40

73

115

239

900

NA

NA

NA

13

18

39

71

111

232

950

NA

NA

NA

13

18

38

69

108

225

1,000

NA

NA

NA

12

17

37

67

105

219

1,100

NA

NA

NA

12

16

35

63

100

208

1,200

NA

NA

NA

11

16

34

60

95

199

1,300

NA

NA

NA

11

15

32

58

91

190

1,400

NA

NA

NA

10

14

31

56

88

183

1,500

NA

NA

NA

NA

14

30

54

84

176

1,600

NA

NA

NA

NA

13

29

52

82

170

1,700

NA

NA

NA

NA

13

28

50

79

164

1,800

NA

NA

NA

NA

13

27

49

77

159

1,900

NA

NA

NA

NA

12

26

47

74

155

2,000

NA

NA

NA

NA

12

25

46

72

151

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    NA means a flow of less than 10 cfh.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(9) SEMIRIGID COPPER TUBING

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

0.5 in. w.c.

Specific Gravity

0.60

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

27

55

111

195

276

590

1,060

1,680

3,490

20

18

38

77

134

190

406

730

1,150

2,400

30

15

30

61

107

152

326

586

925

1,930

40

13

26

53

92

131

279

502

791

1,650

50

11

23

47

82

116

247

445

701

1,460

60

10

21

42

74

105

224

403

635

1,320

70

NA

19

39

68

96

206

371

585

1,220

80

NA

18

36

63

90

192

345

544

1,130

90

NA

17

34

59

84

180

324

510

1,060

100

NA

16

32

56

79

170

306

482

1,000

125

NA

14

28

50

70

151

271

427

890

150

NA

13

26

45

64

136

245

387

806

175

NA

12

24

41

59

125

226

356

742

200

NA

11

22

39

355

117

210

331

690

250

NA

NA

20

34

48

103

186

294

612

300

NA

NA

18

31

44

94

169

266

554

350

NA

NA

16

28

40

86

155

245

510

400

NA

NA

15

26

38

80

144

228

474

450

NA

NA

14

25

35

75

135

214

445

500

NA

NA

13

23

33

71

128

202

420

550

NA

NA

13

22

32

68

122

192

399

600

NA

NA

12

21

30

64

116

183

381

650

NA

NA

12

20

29

62

111

175

365

700

NA

NA

11

20

28

59

107

168

350

750

NA

NA

11

19

27

57

103

162

338

800

NA

NA

10

18

26

55

99

156

326

850

NA

NA

10

18

25

53

96

151

315

900

NA

NA

NA

17

24

52

93

147

306

950

NA

NA

NA

17

24

50

90

143

297

1,000

NA

NA

NA

16

23

49

88

139

289

1,100

NA

NA

NA

15

22

46

84

132

274

1,200

NA

NA

NA

15

21

44

80

126

262

1,300

NA

NA

NA

14

20

42

76

120

251

1,400

NA

NA

NA

13

19

41

73

116

241

1,500

NA

NA

NA

13

18

39

71

111

232

1,600

NA

NA

NA

13

18

38

68

108

224

1,700

NA

NA

NA

12

17

37

66

104

217

1,800

NA

NA

NA

12

17

36

64

101

210

1,900

NA

NA

NA

11

16

35

62

98

204

2,000

NA

NA

NA

11

16

34

60

95

199

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    NA means a flow of less than 10 cfh.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(10) SEMIRIGID COPPER TUBING

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

1.0 in. w.c.

Specific Gravity

0.60

INTENDED USE: SIZING BETWEEN HOUSE LINE REGULATOR AND THE APPLIANCE

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

39

80

162

283

402

859

1,550

2,440

5,080

20

27

55

111

195

276

590

1,060

1,680

3,490

30

21

44

89

156

222

474

853

1,350

2,800

40

18

38

77

134

190

406

730

1,150

2,400

50

16

33

68

119

168

359

647

1,020

2,130

60

15

30

61

107

152

326

586

925

1,930

70

13

28

57

99

140

300

539

851

1,770

80

13

26

53

92

131

279

502

791

1,650

90

12

24

49

86

122

262

471

742

1,550

100

11

23

47

82

116

247

445

701

1,460

125

NA

20

41

72

103

219

394

622

1,290

150

NA

18

37

65

93

198

357

563

1,170

175

NA

17

34

60

85

183

329

518

1,080

200

NA

16

32

56

79

170

306

482

1,000

250

NA

14

28

50

70

151

271

427

890

300

NA

13

26

45

64

136

245

387

806

350

NA

12

24

41

59

125

226

356

742

400

NA

11

22

39

55

117

210

331

690

450

NA

10

21

36

51

110

197

311

647

500

NA

NA

20

34

48

103

186

294

612

550

NA

NA

19

32

46

98

177

279

581

600

NA

NA

18

31

44

94

169

266

554

650

NA

NA

17

30

42

90

162

255

531

700

NA

NA

16

28

40

86

155

245

510

750

NA

NA

16

27

39

83

150

236

491

800

NA

NA

15

26

38

80

144

228

474

850

NA

NA

15

26

36

78

140

220

459

900

NA

NA

14

25

35

75

135

214

445

950

NA

NA

14

24

34

73

132

207

432

1,000

NA

NA

13

23

33

71

128

202

420

1,100

NA

NA

13

22

32

68

122

192

399

1,200

NA

NA

12

21

30

64

116

183

381

1,300

NA

NA

12

20

29

62

111

175

365

1,400

NA

NA

11

20

28

59

107

168

350

1,500

NA

NA

11

19

27

57

103

162

338

1,600

NA

NA

10

18

26

55

99

156

326

1,700

NA

NA

10

18

25

53

96

151

315

1,800

NA

NA

NA

17

24

52

93

147

306

1,900

NA

NA

NA

17

24

50

90

143

297

2,000

NA

NA

NA

16

23

49

88

139

289

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    NA means a flow of less than 10 cfh.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(11) SEMIRIGID COPPER TUBING

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

17.0 in. w.c.

Specific Gravity

0.60

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

190

391

796

1,390

1,970

4,220

7,590

12,000

24,900

20

130

269

547

956

1,360

2,900

5,220

8,230

17,100

30

105

216

439

768

1,090

2,330

4,190

6,610

13,800

40

90

185

376

657

932

1,990

3,590

5,650

11,800

50

79

164

333

582

826

1,770

3,180

5,010

10,400

60

72

148

302

528

749

1,600

2,880

4,540

9,460

70

66

137

278

486

689

1,470

2,650

4,180

8,700

80

62

127

258

452

641

1,370

2,460

3,890

8,090

90

58

119

243

424

601

1,280

2,310

3,650

7,590

100

55

113

229

400

568

1,210

2,180

3,440

7,170

125

48

100

203

355

503

1,080

1,940

3,050

6,360

150

44

90

184

321

456

974

1,750

2,770

5,760

175

40

83

169

296

420

896

1,610

2,540

5,300

200

38

77

157

275

390

834

1,500

2,370

4,930

250

33

69

140

244

346

739

1,330

2,100

4,370

300

30

62

126

221

313

670

1,210

1,900

3,960

350

28

57

116

203

288

616

1,110

1,750

3,640

400

26

53

108

189

268

573

1,030

1,630

3,390

450

24

50

102

177

252

538

968

1,530

3,180

500

23

47

96

168

238

508

914

1,440

3,000

550

22

45

91

159

226

482

868

1,370

2,850

600

21

43

87

152

215

460

829

1,310

2,720

650

20

41

83

145

206

441

793

1,250

2,610

700

19

39

80

140

198

423

762

1,200

2,500

750

18

38

77

135

191

408

734

1,160

2,410

800

18

37

74

130

184

394

709

1,120

2,330

850

17

35

72

126

178

381

686

1,080

2,250

900

17

34

70

122

173

370

665

1,050

2,180

950

16

33

68

118

168

359

646

1,020

2,120

1,000

16

32

66

115

163

349

628

991

2,060

1,100

15

31

63

109

155

332

597

941

1,960

1,200

14

29

60

104

148

316

569

898

1,870

1,300

14

28

57

100

142

303

545

860

1,790

1,400

13

27

55

96

136

291

524

826

1,720

1,500

13

26

53

93

131

280

505

796

1,660

1,600

12

25

51

89

127

271

487

768

1,600

1,700

12

24

49

86

123

262

472

744

1,550

1,800

11

24

48

84

119

254

457

721

1,500

1,900

11

23

47

81

115

247

444

700

1,460

2,000

11

22

45

79

112

240

432

681

1,420

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(12) SEMIRIGID COPPER TUBING

Gas

Natural

Inlet Pressure

2 psi

Pressure Drop

1.0 psi

Specific Gravity

0.60

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

245

506

1,030

1,800

2,550

5,450

9,820

15,500

32,200

20

169

348

708

1,240

1,760

3,750

6,750

10,600

22,200

30

135

279

568

993

1,410

3,010

5,420

8,550

17,800

40

116

239

486

850

1,210

2,580

4,640

7,310

15,200

50

103

212

431

754

1,070

2,280

4,110

6,480

13,500

60

93

192

391

683

969

2,070

3,730

5,870

12,200

70

86

177

359

628

891

1,900

3,430

5,400

11,300

80

80

164

334

584

829

1,770

3,190

5,030

10,500

90

75

154

314

548

778

1,660

2,990

4,720

9,820

100

71

146

296

518

735

1,570

2,830

4,450

9,280

125

63

129

263

459

651

1,390

2,500

3,950

8,220

150

57

117

238

416

590

1,260

2,270

3,580

7,450

175

52

108

219

383

543

1,160

2,090

3,290

6,850

200

49

100

204

356

505

1,080

1,940

3,060

6,380

250

43

89

181

315

448

956

1,720

2,710

5,650

300

39

80

164

286

406

866

1,560

2,460

5,120

350

36

74

150

263

373

797

1,430

2,260

4,710

400

33

69

140

245

347

741

1,330

2,100

4,380

450

31

65

131

230

326

696

1,250

1,970

4,110

500

30

61

124

217

308

657

1,180

1,870

3,880

550

28

58

118

206

292

624

1,120

1,770

3,690

600

27

55

112

196

279

595

1,070

1,690

3,520

650

26

53

108

188

267

570

1,030

1,620

3,370

700

25

51

103

181

256

548

986

1,550

3,240

750

24

49

100

174

247

528

950

1,500

3,120

800

23

47

96

168

239

510

917

1,450

3,010

850

22

46

93

163

231

493

888

1,400

2,920

900

22

44

90

158

224

478

861

1,360

2,830

950

21

43

88

153

217

464

836

1,320

2,740

1,000

20

42

85

149

211

452

813

1,280

2,670

1,100

19

40

81

142

201

429

772

1,220

2,540

1,200

18

38

77

135

192

409

737

1,160

2,420

1,300

18

36

74

129

183

392

705

1,110

2,320

1,400

17

35

71

124

176

376

678

1,070

2,230

1,500

16

34

68

120

170

363

653

1,030

2,140

1,600

16

33

66

116

164

350

630

994

2,070

1,700

15

31

64

112

159

339

610

962

2,000

1,800

15

30

62

108

154

329

592

933

1,940

1,900

14

30

60

105

149

319

575

906

1,890

2,000

14

29

59

102

145

310

559

881

1,830

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(13) SEMIRIGID COPPER TUBING

Gas

Natural

Inlet Pressure

2 psi

Pressure Drop

1.5 psi

Specific Gravity

0.60

INTENDED USE

Pipe sizing between point of delivery and the house line regulator. Total load supplied by a single house line regulator not exceeding 150 cubic feet per hour.

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

303

625

1,270

2,220

3,150

6,740

12,100

19,100

39,800

20

208

430

874

1,530

2,170

4,630

8,330

13,100

27,400

30

167

345

702

1,230

1,740

3,720

6,690

10,600

22,000

40

143

295

601

1,050

1,490

3,180

5,730

9,030

18,800

50

127

262

532

931

1,320

2,820

5,080

8,000

16,700

60

115

237

482

843

1,200

2,560

4,600

7,250

15,100

70

106

218

444

776

1,100

2,350

4,230

6,670

13,900

80

98

203

413

722

1,020

2,190

3,940

6,210

12,900

90

92

190

387

677

961

2,050

3,690

5,820

12,100

100

87

180

366

640

907

1,940

3,490

5,500

11,500

125

77

159

324

567

804

1,720

3,090

4,880

10,200

150

70

144

294

514

729

1,560

2,800

4,420

9,200

175

64

133

270

472

670

1,430

2,580

4,060

8,460

200

60

124

252

440

624

1,330

2,400

3,780

7,870

250

53

110

223

390

553

1,180

2,130

3,350

6,980

300

48

99

202

353

501

1,070

1,930

3,040

6,320

350

44

91

186

325

461

984

1,770

2,790

5,820

400

41

85

173

302

429

916

1,650

2,600

5,410

450

39

80

162

283

402

859

1,550

2,440

5,080

500

36

75

153

268

380

811

1,460

2,300

4,800

550

35

72

146

254

361

771

1,390

2,190

4,560

600

33

68

139

243

344

735

1,320

2,090

4,350

650

32

65

133

232

330

704

1,270

2,000

4,160

700

30

63

128

223

317

676

1,220

1,920

4,000

750

29

60

123

215

305

652

1,170

1,850

3,850

800

28

58

119

208

295

629

1,130

1,790

3,720

850

27

57

115

201

285

609

1,100

1,730

3,600

900

27

55

111

195

276

590

1,060

1,680

3,490

950

26

53

108

189

268

573

1,030

1,630

3,390

1,000

25

52

105

184

261

558

1,000

1,580

3,300

1,100

24

49

100

175

248

530

954

1,500

3,130

1,200

23

47

95

167

237

505

910

1,430

2,990

1,300

22

45

91

160

227

484

871

1,370

2,860

1,400

21

43

88

153

218

465

837

1,320

2,750

1,500

20

42

85

148

210

448

806

1,270

2,650

1,600

19

40

82

143

202

432

779

1,230

2,560

1,700

19

39

79

138

196

419

753

1,190

2,470

1,800

18

38

77

134

190

406

731

1,150

2,400

1,900

18

37

74

130

184

394

709

1,120

2,330

2,000

17

36

72

126

179

383

690

1,090

2,270

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    Where this table is used to size the tubing upstream of a line pressure regulator, the pipe or tubing downstream of the line pressure regulator shall be sized using a pressure drop not greater than 1 inch w.c.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(14) SEMIRIGID COPPER TUBING

Gas

Natural

Inlet Pressure

5.0 psi

Pressure Drop

3.5 psi

Specific Gravity

0.60

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

511

1,050

2,140

3,750

5,320

11,400

20,400

32,200

67,100

20

351

724

1,470

2,580

3,650

7,800

14,000

22,200

46,100

30

282

582

1,180

2,070

2,930

6,270

11,300

17,800

37,000

40

241

498

1,010

1,770

2,510

5,360

9,660

15,200

31,700

50

214

441

898

1,570

2,230

4,750

8,560

13,500

28,100

60

194

400

813

1,420

2,020

4,310

7,750

12,200

25,500

70

178

368

748

1,310

1,860

3,960

7,130

11,200

23,400

80

166

342

696

1,220

1,730

3,690

6,640

10,500

21,800

90

156

321

653

1,140

1,620

3,460

6,230

9,820

20,400

100

147

303

617

1,080

1,530

3,270

5,880

9,270

19,300

125

130

269

547

955

1,360

2,900

5,210

8,220

17,100

150

118

243

495

866

1,230

2,620

4,720

7,450

15,500

175

109

224

456

796

1,130

2,410

4,350

6,850

14,300

200

101

208

424

741

1,050

2,250

4,040

6,370

13,300

250

90

185

376

657

932

1,990

3,580

5,650

11,800

300

81

167

340

595

844

1,800

3,250

5,120

10,700

350

75

154

313

547

777

1,660

2,990

4,710

9,810

400

69

143

291

509

722

1,540

2,780

4,380

9,120

450

65

134

273

478

678

1,450

2,610

4,110

8,560

500

62

127

258

451

640

1,370

2,460

3,880

8,090

550

58

121

245

429

608

1,300

2,340

3,690

7,680

600

56

115

234

409

580

1,240

2,230

3,520

7,330

650

53

110

224

392

556

1,190

2,140

3,370

7,020

700

51

106

215

376

534

1,140

2,050

3,240

6,740

750

49

102

207

362

514

1,100

1,980

3,120

6,490

800

48

98

200

350

497

1,060

1,910

3,010

6,270

850

46

95

194

339

481

1,030

1,850

2,910

6,070

900

45

92

188

328

466

1,000

1,790

2,820

5,880

950

43

90

182

319

452

967

1,740

2,740

5,710

1,000

42

87

177

310

440

940

1,690

2,670

5,560

1,100

40

83

169

295

418

893

1,610

2,530

5,280

1,200

38

79

161

281

399

852

1,530

2,420

5,040

1,300

37

76

154

269

382

816

1,470

2,320

4,820

1,400

35

73

148

259

367

784

1,410

2,220

4,630

1,500

34

70

143

249

353

755

1,360

2,140

4,460

1,600

33

68

138

241

341

729

1,310

2,070

4,310

1,700

32

65

133

233

330

705

1,270

2,000

4,170

1,800

31

63

129

226

320

684

1,230

1,940

4,040

1,900

30

62

125

219

311

664

1,200

1,890

3,930

2,000

29

60

122

213

302

646

1,160

1,830

3,820

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(15) CORRUGATED STAINLESS STEEL TUBING (CSST)

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

0.5 in. w.c.

Specific Gravity

0.60

TUBE SIZE (EHD)

Flow Designation

13

15

18

19

23

25

30

31

37

39

46

48

60

62

Length (ft)

Capacity in Cubic Feet of Gas per Hour

5

46

63

115

134

225

270

471

546

895

1,037

1,790

2,070

3,660

4,140

10

32

44

82

95

161

192

330

383

639

746

1,260

1,470

2,600

2,930

15

25

35

66

77

132

157

267

310

524

615

1,030

1,200

2,140

2,400

20

22

31

58

67

116

137

231

269

456

536

888

1,050

1,850

2,080

25

19

27

52

60

104

122

206

240

409

482

793

936

1,660

1,860

30

18

25

47

55

96

112

188

218

374

442

723

856

1,520

1,700

40

15

21

41

47

83

97

162

188

325

386

625

742

1,320

1,470

50

13

19

37

42

75

87

144

168

292

347

559

665

1,180

1,320

60

12

17

34

38

68

80

131

153

267

318

509

608

1,080

1,200

70

11

16

31

36

63

74

121

141

248

295

471

563

1,000

1,110

80

10

15

29

33

60

69

113

132

232

277

440

527

940

1,040

90

10

14

28

32

57

65

107

125

219

262

415

498

887

983

100

9

13

26

30

54

62

101

118

208

249

393

472

843

933

150

7

10

20

23

42

48

78

91

171

205

320

387

691

762

200

6

9

18

21

38

44

71

82

148

179

277

336

600

661

250

5

8

16

19

34

39

63

74

133

161

247

301

538

591

300

5

7

15

17

32

36

57

67

95

148

226

275

492

540

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (feet) of tubing and n is the number of additional fittings or bends.

  2. 2.

    EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(16) CORRUGATED STAINLESS STEEL TUBING (CSST)

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

3.0 in. w.c.

Specific Gravity

0.60

INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0-INCH W.C. OR GREATER

TUBE SIZE (EHD)

Flow Designation

13

15

18

19

23

25

30

31

37

39

46

48

60

62

Length (ft)

Capacity in Cubic Feet of Gas per Hour

5

120

160

277

327

529

649

1,180

1,370

2,140

2,423

4,430

5,010

8,800

10,100

10

83

112

197

231

380

462

828

958

1,530

1,740

3,200

3,560

6,270

7,160

15

67

90

161

189

313

379

673

778

1,250

1,433

2,540

2,910

5,140

5,850

20

57

78

140

164

273

329

580

672

1,090

1,249

2,200

2,530

4,460

5,070

25

51

69

125

147

245

295

518

599

978

1,123

1,960

2,270

4,000

4,540

30

46

63

115

134

225

270

471

546

895

1,029

1,790

2,070

3,660

4,140

40

39

54

100

116

196

234

407

471

778

897

1,550

1,800

3,180

3,590

50

35

48

89

104

176

210

363

421

698

806

1,380

1,610

2,850

3,210

60

32

44

82

95

161

192

330

383

639

739

1,260

1,470

2,600

2,930

70

29

41

76

88

150

178

306

355

593

686

1,170

1,360

2,420

2,720

80

27

38

71

82

141

167

285

331

555

644

1,090

1,280

2,260

2,540

90

26

36

67

77

133

157

268

311

524

609

1,030

1,200

2,140

2,400

100

24

34

63

73

126

149

254

295

498

579

974

1,140

2,030

2,280

150

19

27

52

60

104

122

206

240

409

477

793

936

1,660

1,860

200

17

23

45

52

91

106

178

207

355

415

686

812

1,440

1,610

250

15

21

40

46

82

95

159

184

319

373

613

728

1,290

1,440

300

13

19

37

42

75

87

144

168

234

342

559

665

1,180

1,320

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.

  2. 2.

    EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(17) CORRUGATED STAINLESS STEEL TUBING (CSST)

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

6.0 in. w.c.

Specific Gravity

0.60

INTENDED USE: INITIAL SUPPLY PRESSURE OF 11.0-INCH W.C. OR GREATER

TUBE SIZE (EHD)

Flow Designation

13

15

18

19

23

25

30

31

37

39

46

48

60

62

Length (ft)

Capacity in Cubic Feet of Gas per Hour

5

173

229

389

461

737

911

1,690

1,950

3,000

3,375

6,280

7,050

12,400

14,260

10

120

160

277

327

529

649

1,180

1,370

2,140

2,423

4,430

5,010

8,800

10,100

15

96

130

227

267

436

532

960

1,110

1,760

1,996

3,610

4,100

7,210

8,260

20

83

112

197

231

380

462

828

958

1,530

1,740

3,120

3,560

6,270

7,160

25

74

99

176

207

342

414

739

855

1,370

1,564

2,790

3,190

5,620

6,400

30

67

90

161

189

313

379

673

778

1,250

1,433

2,540

2,910

5,140

5,850

40

57

78

140

164

273

329

580

672

1,090

1,249

2,200

2,530

4,460

5,070

50

51

69

125

147

245

295

518

599

978

1,123

1,960

2,270

4,000

4,540

60

46

63

115

134

225

270

471

546

895

1,029

1,790

2,070

3,660

4,140

70

42

58

106

124

209

250

435

505

830

956

1,660

1,920

3,390

3,840

80

39

54

100

116

196

234

407

471

778

897

1,550

1,800

3,180

3,590

90

37

51

94

109

185

221

383

444

735

848

1,460

1,700

3,000

3,390

100

35

48

89

104

176

210

363

421

698

806

1,380

1,610

2,850

3,210

150

28

39

73

85

145

172

294

342

573

664

1,130

1,320

2,340

2,630

200

24

34

63

73

126

149

254

295

498

579

974

1,140

2,030

2,280

250

21

30

57

66

114

134

226

263

447

520

870

1,020

1,820

2,040

300

19

27

52

60

104

122

206

240

409

477

793

936

1,660

1,860

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.

  2. 2.

    EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(18) CORRUGATED STAINLESS STEEL TUBING (CSST)

Gas

Natural

Inlet Pressure

2 psi

Pressure Drop

1.0 psi

Specific Gravity

0.60

TUBE SIZE (EHD)

Flow Designation

13

15

18

19

23

25

30

31

37

39

46

48

60

62

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

270

353

587

700

1,100

1,370

2,590

2,990

4,510

5,037

9,600

10,700

18,600

21,600

25

166

220

374

444

709

876

1,620

1,870

2,890

3,258

6,040

6,780

11,900

13,700

30

151

200

342

405

650

801

1,480

1,700

2,640

2,987

5,510

6,200

10,900

12,500

40

129

172

297

351

567

696

1,270

1,470

2,300

2,605

4,760

5,380

9,440

10,900

50

115

154

266

314

510

624

1,140

1,310

2,060

2,343

4,260

4,820

8,470

9,720

75

93

124

218

257

420

512

922

1,070

1,690

1,932

3,470

3,950

6,940

7,940

80

89

120

211

249

407

496

892

1,030

1,640

1,874

3,360

3,820

6,730

7,690

100

79

107

189

222

366

445

795

920

1,470

1,685

3,000

3,420

6,030

6,880

150

64

87

155

182

302

364

646

748

1,210

1,389

2,440

2,800

4,940

5,620

200

55

75

135

157

263

317

557

645

1,050

1,212

2,110

2,430

4,290

4,870

250

49

67

121

141

236

284

497

576

941

1,090

1,890

2,180

3,850

4,360

300

44

61

110

129

217

260

453

525

862

999

1,720

1,990

3,520

3,980

400

38

52

96

111

189

225

390

453

749

871

1,490

1,730

3,060

3,450

500

34

46

86

100

170

202

348

404

552

783

1,330

1,550

2,740

3,090

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 3/4 psi, DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate.

  2. 2.

    CAUTION: Capacities shown in the table might exceed maximum capacity for a selected regulator. Consult with the regulator or tubing manufacturer for guidance.

  3. 3.

    Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.

  4. 4.

    EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.

  5. 5.

    Table entries have been rounded to three significant digits.

TABLE 402.4(19) CORRUGATED STAINLESS STEEL TUBING (CSST)

Gas

Natural

Inlet Pressure

5.0 psi

Pressure Drop

3.5 psi

Specific Gravity

0.60

TUBE SIZE (EHD)

Flow Designation

13

15

18

19

23

25

30

31

37

39

46

48

60

62

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

523

674

1,080

1,300

2,000

2,530

4,920

5,660

8,300

9,140

18,100

19,800

34,400

40,400

25

322

420

691

827

1,290

1,620

3,080

3,540

5,310

5,911

11,400

12,600

22,000

25,600

30

292

382

632

755

1,180

1,480

2,800

3,230

4,860

5,420

10,400

11,500

20,100

23,400

40

251

329

549

654

1,030

1,280

2,420

2,790

4,230

4,727

8,970

10,000

17,400

20,200

50

223

293

492

586

926

1,150

2,160

2,490

3,790

4,251

8,020

8,930

15,600

18,100

75

180

238

403

479

763

944

1,750

2,020

3,110

3,506

6,530

7,320

12,800

14,800

80

174

230

391

463

740

915

1,690

1,960

3,020

3,400

6,320

7,090

12,400

14,300

100

154

205

350

415

665

820

1,510

1,740

2,710

3,057

5,650

6,350

11,100

12,800

150

124

166

287

339

548

672

1,230

1,420

2,220

2,521

4,600

5,200

9,130

10,500

200

107

143

249

294

478

584

1,060

1,220

1,930

2,199

3,980

4,510

7,930

9,090

250

95

128

223

263

430

524

945

1,090

1,730

1,977

3,550

4,040

7,110

8,140

300

86

116

204

240

394

479

860

995

1,590

1,813

3,240

3,690

6,500

7,430

400

74

100

177

208

343

416

742

858

1,380

1,581

2,800

3,210

5,650

6,440

500

66

89

159

186

309

373

662

766

1,040

1,422

2,500

2,870

5,060

5,760

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 3/4 psi, DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate.

  2. 2.

    CAUTION: Capacities shown in the table might exceed maximum capacity for a selected regulator. Consult with the regulator or tubing manufacturer for guidance.

  3. 3.

    Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.

  4. 4.

    EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.

  5. 5.

    Table entries have been rounded to three significant digits.

TABLE 402.4(20) POLYETHYLENE PLASTIC PIPE

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

0.3 in. w.c.

Specific Gravity

0.60

PIPE SIZE (inch)

Nominal OD

1/2

3/4

1

1 1/4

1 1/2

2

3

4

Designation

SDR 9

SDR 11

SDR 11

SDR 10

SDR 11

SDR 11

SDR 11

SDR 11

Actual ID

0.660

0.860

1.077

1.328

1.554

1.943

2.864

3.682

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

153

305

551

955

1,440

2,590

7,170

13,900

20

105

210

379

656

991

1,780

4,920

9,520

30

84

169

304

527

796

1,430

3,950

7,640

40

72

144

260

451

681

1,220

3,380

6,540

50

64

128

231

400

604

1,080

3,000

5,800

60

58

116

209

362

547

983

2,720

5,250

70

53

107

192

333

503

904

2,500

4,830

80

50

99

179

310

468

841

2,330

4,500

90

46

93

168

291

439

789

2,180

4,220

100

44

88

159

275

415

745

2,060

3,990

125

39

78

141

243

368

661

1,830

3,530

150

35

71

127

221

333

598

1,660

3,200

175

32

65

117

203

306

551

1,520

2,940

200

30

60

109

189

285

512

1,420

2,740

250

27

54

97

167

253

454

1,260

2,430

300

24

48

88

152

229

411

1,140

2,200

350

22

45

81

139

211

378

1,050

2,020

400

21

42

75

130

196

352

974

1,880

450

19

39

70

122

184

330

914

1,770

500

18

37

66

115

174

312

863

1,670

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(21) POLYETHYLENE PLASTIC PIPE

Gas

Natural

Inlet Pressure

Less than 2 psi

Pressure Drop

0.5 in. w.c.

Specific Gravity

0.60

PIPE SIZE (inch)

Nominal OD

1/2

3/4

1

1 1/4

1 1/2

2

3

4

Designation

SDR 9

SDR 11

SDR 11

SDR 10

SDR 11

SDR 11

SDR 11

SDR 11

Actual ID

0.660

0.860

1.077

1.328

1.554

1.943

2.864

3.682

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

201

403

726

1,260

1,900

3,410

9,450

18,260

20

138

277

499

865

1,310

2,350

6,490

12,550

30

111

222

401

695

1,050

1,880

5,210

10,080

40

95

190

343

594

898

1,610

4,460

8,630

50

84

169

304

527

796

1,430

3,950

7,640

60

76

153

276

477

721

1,300

3,580

6,930

70

70

140

254

439

663

1,190

3,300

6,370

80

65

131

236

409

617

1,110

3,070

5,930

90

61

123

221

383

579

1,040

2,880

5,560

100

58

116

209

362

547

983

2,720

5,250

125

51

103

185

321

485

871

2,410

4,660

150

46

93

168

291

439

789

2,180

4,220

175

43

86

154

268

404

726

2,010

3,880

200

40

80

144

249

376

675

1,870

3,610

250

35

71

127

221

333

598

1,660

3,200

300

32

64

115

200

302

542

1,500

2,900

350

29

59

106

184

278

499

1,380

2,670

400

27

55

99

171

258

464

1,280

2,480

450

26

51

93

160

242

435

1,200

2,330

500

24

48

88

152

229

411

1,140

2,200

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(22) POLYETHYLENE PLASTIC PIPE

Gas

Natural

Inlet Pressure

2.0 psi

Pressure Drop

1.0 psi

Specific Gravity

0.60

PIPE SIZE (inch)

Nominal OD

1/2

3/4

1

1 1/4

1 1/2

2

3

4

Designation

SDR 9

SDR 11

SDR 11

SDR 10

SDR 11

SDR 11

SDR 11

SDR 11

Actual ID

0.660

0.860

1.077

1.328

1.554

1.943

2.864

3.682

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

1,860

3,720

6,710

11,600

17,600

31,600

87,300

169,000

20

1,280

2,560

4,610

7,990

12,100

21,700

60,000

116,000

30

1,030

2,050

3,710

6,420

9,690

17,400

48,200

93,200

40

878

1,760

3,170

5,490

8,300

14,900

41,200

79,700

50

778

1,560

2,810

4,870

7,350

13,200

36,600

70,700

60

705

1,410

2,550

4,410

6,660

12,000

33,100

64,000

70

649

1,300

2,340

4,060

6,130

11,000

30,500

58,900

80

603

1,210

2,180

3,780

5,700

10,200

28,300

54,800

90

566

1,130

2,050

3,540

5,350

9,610

26,600

51,400

100

535

1,070

1,930

3,350

5,050

9,080

25,100

48,600

125

474

949

1,710

2,970

4,480

8,050

22,300

43,000

150

429

860

1,550

2,690

4,060

7,290

20,200

39,000

175

395

791

1,430

2,470

3,730

6,710

18,600

35,900

200

368

736

1,330

2,300

3,470

6,240

17,300

33,400

250

326

652

1,180

2,040

3,080

5,530

15,300

29,600

300

295

591

1,070

1,850

2,790

5,010

13,900

26,800

350

272

544

981

1,700

2,570

4,610

12,800

24,700

400

253

506

913

1,580

2,390

4,290

11,900

22,900

450

237

475

856

1,480

2,240

4,020

11,100

21,500

500

224

448

809

1,400

2,120

3,800

10,500

20,300

550

213

426

768

1,330

2,010

3,610

9,990

19,300

600

203

406

733

1,270

1,920

3,440

9,530

18,400

650

194

389

702

1,220

1,840

3,300

9,130

17,600

700

187

374

674

1,170

1,760

3,170

8,770

16,900

750

180

360

649

1,130

1,700

3,050

8,450

16,300

800

174

348

627

1,090

1,640

2,950

8,160

15,800

850

168

336

607

1,050

1,590

2,850

7,890

15,300

900

163

326

588

1,020

1,540

2,770

7,650

14,800

950

158

317

572

990

1,500

2,690

7,430

14,400

1,000

154

308

556

963

1,450

2,610

7,230

14,000

1,100

146

293

528

915

1,380

2,480

6,870

13,300

1,200

139

279

504

873

1,320

2,370

6,550

12,700

1,300

134

267

482

836

1,260

2,270

6,270

12,100

1,400

128

257

463

803

1,210

2,180

6,030

11,600

1,500

124

247

446

773

1,170

2,100

5,810

11,200

1,600

119

239

431

747

1,130

2,030

5,610

10,800

1,700

115

231

417

723

1,090

1,960

5,430

10,500

1,800

112

224

404

701

1,060

1,900

5,260

10,200

1,900

109

218

393

680

1,030

1,850

5,110

9,900

2,000

106

212

382

662

1,000

1,800

4,970

9,600

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(23) POLYETHYLENE PLASTIC PIPE

Gas

Natural

Inlet Pressure

Less than 2.0 psi

Pressure Drop

0.3 in. w.c.

Specific Gravity

0.60

PLASTIC TUBING SIZE (CTS) (inch)

Nominal OD

1/2

3/4

Designation

SDR 7

SDR 11

Actual ID

0.445

0.927

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

54

372

20

37

256

30

30

205

40

26

176

50

23

156

60

21

141

70

19

130

80

18

121

90

17

113

100

16

107

125

14

95

150

13

86

175

12

79

200

11

74

225

10

69

250

NA

65

275

NA

62

300

NA

59

350

NA

54

400

NA

51

450

NA

47

500

NA

45

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    NA means a flow of less than 10 cfh.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(24) POLYETHYLENE PLASTIC PIPE

Gas

Natural

Inlet Pressure

Less than 2.0 psi

Pressure Drop

0.5 in. w.c.

Specific Gravity

0.60

PLASTIC TUBING SIZE (CTS) (inch)

Nominal OD

1/2

3/4

Designation

SDR 7

SDR 11

Actual ID

0.445

0.927

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

72

490

20

49

337

30

39

271

40

34

232

50

30

205

60

27

186

70

25

171

80

23

159

90

22

149

100

21

141

125

18

125

150

17

113

175

15

104

200

14

97

225

13

91

250

12

86

275

11

82

300

11

78

350

10

72

400

NA

67

450

NA

63

500

NA

59

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    NA means a flow of less than 10 cfh.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(25) SCHEDULE 40 METALLIC PIPE

Gas

Undiluted Propane

Inlet Pressure

10.0 psi

Pressure Drop

1.0 psi

Specific Gravity

1.50

INTENDED USE

Pipe sizing between first stage (high-pressure regulator) and second stage (low-pressure regulator).

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Thousands of Btu per Hour

10

3,320

6,950

13,100

26,900

40,300

77,600

124,000

219,000

446,000

20

2,280

4,780

9,000

18,500

27,700

53,300

85,000

150,000

306,000

30

1,830

3,840

7,220

14,800

22,200

42,800

68,200

121,000

246,000

40

1,570

3,280

6,180

12,700

19,000

36,600

58,400

103,000

211,000

50

1,390

2,910

5,480

11,300

16,900

32,500

51,700

91,500

187,000

60

1,260

2,640

4,970

10,200

15,300

29,400

46,900

82,900

169,000

70

1,160

2,430

4,570

9,380

14,100

27,100

43,100

76,300

156,000

80

1,080

2,260

4,250

8,730

13,100

25,200

40,100

70,900

145,000

90

1,010

2,120

3,990

8,190

12,300

23,600

37,700

66,600

136,000

100

956

2,000

3,770

7,730

11,600

22,300

35,600

62,900

128,000

125

848

1,770

3,340

6,850

10,300

19,800

31,500

55,700

114,000

150

768

1,610

3,020

6,210

9,300

17,900

28,600

50,500

103,000

175

706

1,480

2,780

5,710

8,560

16,500

26,300

46,500

94,700

200

657

1,370

2,590

5,320

7,960

15,300

24,400

43,200

88,100

250

582

1,220

2,290

4,710

7,060

13,600

21,700

38,300

78,100

300

528

1,100

2,080

4,270

6,400

12,300

19,600

34,700

70,800

350

486

1,020

1,910

3,930

5,880

11,300

18,100

31,900

65,100

400

452

945

1,780

3,650

5,470

10,500

16,800

29,700

60,600

450

424

886

1,670

3,430

5,140

9,890

15,800

27,900

56,800

500

400

837

1,580

3,240

4,850

9,340

14,900

26,300

53,700

550

380

795

1,500

3,070

4,610

8,870

14,100

25,000

51,000

600

363

759

1,430

2,930

4,400

8,460

13,500

23,900

48,600

650

347

726

1,370

2,810

4,210

8,110

12,900

22,800

46,600

700

334

698

1,310

2,700

4,040

7,790

12,400

21,900

44,800

750

321

672

1,270

2,600

3,900

7,500

12,000

21,100

43,100

800

310

649

1,220

2,510

3,760

7,240

11,500

20,400

41,600

850

300

628

1,180

2,430

3,640

7,010

11,200

19,800

40,300

900

291

609

1,150

2,360

3,530

6,800

10,800

19,200

39,100

950

283

592

1,110

2,290

3,430

6,600

10,500

18,600

37,900

1,000

275

575

1,080

2,230

3,330

6,420

10,200

18,100

36,900

1,100

261

546

1,030

2,110

3,170

6,100

9,720

17,200

35,000

1,200

249

521

982

2,020

3,020

5,820

9,270

16,400

33,400

1,300

239

499

940

1,930

2,890

5,570

8,880

15,700

32,000

1,400

229

480

903

1,850

2,780

5,350

8,530

15,100

30,800

1,500

221

462

870

1,790

2,680

5,160

8,220

14,500

29,600

1,600

213

446

840

1,730

2,590

4,980

7,940

14,000

28,600

1,700

206

432

813

1,670

2,500

4,820

7,680

13,600

27,700

1,800

200

419

789

1,620

2,430

4,670

7,450

13,200

26,900

1,900

194

407

766

1,570

2,360

4,540

7,230

12,800

26,100

2,000

189

395

745

1,530

2,290

4,410

7,030

12,400

25,400

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

Table entries have been rounded to three significant digits.

TABLE 402.4(26) SCHEDULE 40 METALLIC PIPE

Gas

Undiluted Propane

Inlet Pressure

10.0 psi

Pressure Drop

3.0 psi

Specific Gravity

1.50

INTENDED USE

Pipe sizing between first stage (high-pressure regulator) and second stage (low-pressure regulator).

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Thousands of Btu per Hour

10

5,890

12,300

23,200

47,600

71,300

137,000

219,000

387,000

789,000

20

4,050

8,460

15,900

32,700

49,000

94,400

150,000

266,000

543,000

30

3,250

6,790

12,800

26,300

39,400

75,800

121,000

214,000

436,000

40

2,780

5,810

11,000

22,500

33,700

64,900

103,000

183,000

373,000

50

2,460

5,150

9,710

19,900

29,900

57,500

91,600

162,000

330,000

60

2,230

4,670

8,790

18,100

27,100

52,100

83,000

147,000

299,000

70

2,050

4,300

8,090

16,600

24,900

47,900

76,400

135,000

275,000

80

1,910

4,000

7,530

15,500

23,200

44,600

71,100

126,000

256,000

90

1,790

3,750

7,060

14,500

21,700

41,800

66,700

118,000

240,000

100

1,690

3,540

6,670

13,700

20,500

39,500

63,000

111,000

227,000

125

1,500

3,140

5,910

12,100

18,200

35,000

55,800

98,700

201,000

150

1,360

2,840

5,360

11,000

16,500

31,700

50,600

89,400

182,000

175

1,250

2,620

4,930

10,100

15,200

29,200

46,500

82,300

167,800

200

1,160

2,430

4,580

9,410

14,100

27,200

43,300

76,500

156,100

250

1,030

2,160

4,060

8,340

12,500

24,100

38,400

67,800

138,400

300

935

1,950

3,680

7,560

11,300

21,800

34,800

61,500

125,400

350

860

1,800

3,390

6,950

10,400

20,100

32,000

56,500

115,300

400

800

1,670

3,150

6,470

9,690

18,700

29,800

52,600

107,300

450

751

1,570

2,960

6,070

9,090

17,500

27,900

49,400

100,700

500

709

1,480

2,790

5,730

8,590

16,500

26,400

46,600

95,100

550

673

1,410

2,650

5,450

8,160

15,700

25,000

44,300

90,300

600

642

1,340

2,530

5,200

7,780

15,000

23,900

42,200

86,200

650

615

1,290

2,420

4,980

7,450

14,400

22,900

40,500

82,500

700

591

1,240

2,330

4,780

7,160

13,800

22,000

38,900

79,300

750

569

1,190

2,240

4,600

6,900

13,300

21,200

37,400

76,400

800

550

1,150

2,170

4,450

6,660

12,800

20,500

36,200

73,700

850

532

1,110

2,100

4,300

6,450

12,400

19,800

35,000

71,400

900

516

1,080

2,030

4,170

6,250

12,000

19,200

33,900

69,200

950

501

1,050

1,970

4,050

6,070

11,700

18,600

32,900

67,200

1,000

487

1,020

1,920

3,940

5,900

11,400

18,100

32,000

65,400

1,100

463

968

1,820

3,740

5,610

10,800

17,200

30,400

62,100

1,200

442

923

1,740

3,570

5,350

10,300

16,400

29,000

59,200

1,300

423

884

1,670

3,420

5,120

9,870

15,700

27,800

56,700

1,400

406

849

1,600

3,280

4,920

9,480

15,100

26,700

54,500

1,500

391

818

1,540

3,160

4,740

9,130

14,600

25,700

52,500

1,600

378

790

1,490

3,060

4,580

8,820

14,100

24,800

50,700

1,700

366

765

1,440

2,960

4,430

8,530

13,600

24,000

49,000

1,800

355

741

1,400

2,870

4,300

8,270

13,200

23,300

47,600

1,900

344

720

1,360

2,780

4,170

8,040

12,800

22,600

46,200

2,000

335

700

1,320

2,710

4,060

7,820

12,500

22,000

44,900

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(27) SCHEDULE 40 METALLIC PIPE

Gas

Undiluted Propane

Inlet Pressure

2.0 psi

Pressure Drop

1.0 psi

Specific Gravity

1.50

INTENDED USE

Pipe sizing between 2 psig service and line pressure regulator.

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Thousands of Btu per Hour

10

2,680

5,590

10,500

21,600

32,400

62,400

99,500

176,000

359,000

20

1,840

3,850

7,240

14,900

22,300

42,900

68,400

121,000

247,000

30

1,480

3,090

5,820

11,900

17,900

34,500

54,900

97,100

198,000

40

1,260

2,640

4,980

10,200

15,300

29,500

47,000

83,100

170,000

50

1,120

2,340

4,410

9,060

13,600

26,100

41,700

73,700

150,000

60

1,010

2,120

4,000

8,210

12,300

23,700

37,700

66,700

136,000

70

934

1,950

3,680

7,550

11,300

21,800

34,700

61,400

125,000

80

869

1,820

3,420

7,020

10,500

20,300

32,300

57,100

116,000

90

815

1,700

3,210

6,590

9,880

19,000

30,300

53,600

109,000

100

770

1,610

3,030

6,230

9,330

18,000

28,600

50,600

103,000

125

682

1,430

2,690

5,520

8,270

15,900

25,400

44,900

91,500

150

618

1,290

2,440

5,000

7,490

14,400

23,000

40,700

82,900

175

569

1,190

2,240

4,600

6,890

13,300

21,200

37,400

76,300

200

529

1,110

2,080

4,280

6,410

12,300

19,700

34,800

71,000

250

469

981

1,850

3,790

5,680

10,900

17,400

30,800

62,900

300

425

889

1,670

3,440

5,150

9,920

15,800

27,900

57,000

350

391

817

1,540

3,160

4,740

9,120

14,500

25,700

52,400

400

364

760

1,430

2,940

4,410

8,490

13,500

23,900

48,800

450

341

714

1,340

2,760

4,130

7,960

12,700

22,400

45,800

500

322

674

1,270

2,610

3,910

7,520

12,000

21,200

43,200

550

306

640

1,210

2,480

3,710

7,140

11,400

20,100

41,100

600

292

611

1,150

2,360

3,540

6,820

10,900

19,200

39,200

650

280

585

1,100

2,260

3,390

6,530

10,400

18,400

37,500

700

269

562

1,060

2,170

3,260

6,270

9,990

17,700

36,000

750

259

541

1,020

2,090

3,140

6,040

9,630

17,000

34,700

800

250

523

985

2,020

3,030

5,830

9,300

16,400

33,500

850

242

506

953

1,960

2,930

5,640

9,000

15,900

32,400

900

235

490

924

1,900

2,840

5,470

8,720

15,400

31,500

950

228

476

897

1,840

2,760

5,310

8,470

15,000

30,500

1,000

222

463

873

1,790

2,680

5,170

8,240

14,600

29,700

1,100

210

440

829

1,700

2,550

4,910

7,830

13,800

28,200

1,200

201

420

791

1,620

2,430

4,680

7,470

13,200

26,900

1,300

192

402

757

1,550

2,330

4,490

7,150

12,600

25,800

1,400

185

386

727

1,490

2,240

4,310

6,870

12,100

24,800

1,500

178

372

701

1,440

2,160

4,150

6,620

11,700

23,900

1,600

172

359

677

1,390

2,080

4,010

6,390

11,300

23,000

1,700

166

348

655

1,340

2,010

3,880

6,180

10,900

22,300

1,800

161

337

635

1,300

1,950

3,760

6,000

10,600

21,600

1,900

157

327

617

1,270

1,900

3,650

5,820

10,300

21,000

2,000

152

318

600

1,230

1,840

3,550

5,660

10,000

20,400

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(28) SCHEDULE 40 METALLIC PIPE

Gas

Undiluted Propane

Inlet Pressure

11.0 in. w.c.

Pressure Drop

0.5 in. w.c.

Specific Gravity

1.50

INTENDED USE

Pipe sizing between single- or second-stage (low pressure) regulator and appliance.

PIPE SIZE (inch)

Nominal

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

Actual ID

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

Length (ft)

Capacity in Thousands of Btu per Hour

10

291

608

1,150

2,350

3,520

6,790

10,800

19,100

39,000

20

200

418

787

1,620

2,420

4,660

7,430

13,100

26,800

30

160

336

632

1,300

1,940

3,750

5,970

10,600

21,500

40

137

287

541

1,110

1,660

3,210

5,110

9,030

18,400

50

122

255

480

985

1,480

2,840

4,530

8,000

16,300

60

110

231

434

892

1,340

2,570

4,100

7,250

14,800

70

101

212

400

821

1,230

2,370

3,770

6,670

13,600

80

94

197

372

763

1,140

2,200

3,510

6,210

12,700

90

89

185

349

716

1,070

2,070

3,290

5,820

11,900

100

84

175

330

677

1,010

1,950

3,110

5,500

11,200

125

74

155

292

600

899

1,730

2,760

4,880

9,950

150

67

140

265

543

814

1,570

2,500

4,420

9,010

175

62

129

243

500

749

1,440

2,300

4,060

8,290

200

58

120

227

465

697

1,340

2,140

3,780

7,710

250

51

107

201

412

618

1,190

1,900

3,350

6,840

300

46

97

182

373

560

1,080

1,720

3,040

6,190

350

42

89

167

344

515

991

1,580

2,790

5,700

400

40

83

156

320

479

922

1,470

2,600

5,300

450

37

78

146

300

449

865

1,380

2,440

4,970

500

35

73

138

283

424

817

1,300

2,300

4,700

550

33

70

131

269

403

776

1,240

2,190

4,460

600

32

66

125

257

385

741

1,180

2,090

4,260

650

30

64

120

246

368

709

1,130

2,000

4,080

700

29

61

115

236

354

681

1,090

1,920

3,920

750

28

59

111

227

341

656

1,050

1,850

3,770

800

27

57

107

220

329

634

1,010

1,790

3,640

850

26

55

104

213

319

613

978

1,730

3,530

900

25

53

100

206

309

595

948

1,680

3,420

950

25

52

97

200

300

578

921

1,630

3,320

1,000

24

50

95

195

292

562

895

1,580

3,230

1,100

23

48

90

185

277

534

850

1,500

3,070

1,200

22

46

86

176

264

509

811

1,430

2,930

1,300

21

44

82

169

253

487

777

1,370

2,800

1,400

20

42

79

162

243

468

746

1,320

2,690

1,500

19

40

76

156

234

451

719

1,270

2,590

1,600

19

39

74

151

226

436

694

1,230

2,500

1,700

18

38

71

146

219

422

672

1,190

2,420

1,800

18

37

69

142

212

409

652

1,150

2,350

1,900

17

36

67

138

206

397

633

1,120

2,280

2,000

17

35

65

134

200

386

615

1,090

2,220

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(29) SEMIRIGID COPPER TUBING

Gas

Undiluted Propane

Inlet Pressure

10.0 psi

Pressure Drop

1.0 psi

Specific Gravity

1.50

INTENDED USE

Sizing between first stage (high-pressure regulator) and second stage (low-pressure regulator).

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Thousands of Btu per Hour

10

513

1,060

2,150

3,760

5,330

11,400

20,500

32,300

67,400

20

352

727

1,480

2,580

3,670

7,830

14,100

22,200

46,300

30

283

584

1,190

2,080

2,940

6,290

11,300

17,900

37,200

40

242

500

1,020

1,780

2,520

5,380

9,690

15,300

31,800

50

215

443

901

1,570

2,230

4,770

8,590

13,500

28,200

60

194

401

816

1,430

2,020

4,320

7,780

12,300

25,600

70

179

369

751

1,310

1,860

3,980

7,160

11,300

23,500

80

166

343

699

1,220

1,730

3,700

6,660

10,500

21,900

90

156

322

655

1,150

1,630

3,470

6,250

9,850

20,500

100

147

304

619

1,080

1,540

3,280

5,900

9,310

19,400

125

131

270

549

959

1,360

2,910

5,230

8,250

17,200

150

118

244

497

869

1,230

2,630

4,740

7,470

15,600

175

109

225

457

799

1,130

2,420

4,360

6,880

14,300

200

101

209

426

744

1,060

2,250

4,060

6,400

13,300

250

90

185

377

659

935

2,000

3,600

5,670

11,800

300

81

168

342

597

847

1,810

3,260

5,140

10,700

350

75

155

314

549

779

1,660

3,000

4,730

9,840

400

70

144

292

511

725

1,550

2,790

4,400

9,160

450

65

135

274

480

680

1,450

2,620

4,130

8,590

500

62

127

259

453

643

1,370

2,470

3,900

8,120

550

59

121

246

430

610

1,300

2,350

3,700

7,710

600

56

115

235

410

582

1,240

2,240

3,530

7,350

650

54

111

225

393

558

1,190

2,140

3,380

7,040

700

51

106

216

378

536

1,140

2,060

3,250

6,770

750

50

102

208

364

516

1,100

1,980

3,130

6,520

800

48

99

201

351

498

1,060

1,920

3,020

6,290

850

46

96

195

340

482

1,030

1,850

2,920

6,090

900

45

93

189

330

468

1,000

1,800

2,840

5,910

950

44

90

183

320

454

970

1,750

2,750

5,730

1,000

42

88

178

311

442

944

1,700

2,680

5,580

1,100

40

83

169

296

420

896

1,610

2,540

5,300

1,200

38

79

161

282

400

855

1,540

2,430

5,050

1,300

37

76

155

270

383

819

1,470

2,320

4,840

1,400

35

73

148

260

368

787

1,420

2,230

4,650

1,500

34

70

143

250

355

758

1,360

2,150

4,480

1,600

33

68

138

241

343

732

1,320

2,080

4,330

1,700

32

66

134

234

331

708

1,270

2,010

4,190

1,800

31

64

130

227

321

687

1,240

1,950

4,060

1,900

30

62

126

220

312

667

1,200

1,890

3,940

2,000

29

60

122

214

304

648

1,170

1,840

3,830

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(30) SEMIRIGID COPPER TUBING

Gas

Undiluted Propane

Inlet Pressure

11.0 in. w.c.

Pressure Drop

0.5 in. w.c.

Specific Gravity

1.50

INTENDED USE

Sizing between single or second stage (low-pressure regulator) and appliance.

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Thousands of Btu per Hour

10

45

93

188

329

467

997

1,800

2,830

5,890

20

31

64

129

226

321

685

1,230

1,950

4,050

30

25

51

104

182

258

550

991

1,560

3,250

40

21

44

89

155

220

471

848

1,340

2,780

50

19

39

79

138

195

417

752

1,180

2,470

60

17

35

71

125

177

378

681

1,070

2,240

70

16

32

66

115

163

348

626

988

2,060

80

15

30

61

107

152

324

583

919

1,910

90

14

28

57

100

142

304

547

862

1,800

100

13

27

54

95

134

287

517

814

1,700

125

11

24

48

84

119

254

458

722

1,500

150

10

21

44

76

108

230

415

654

1,360

175

NA

20

40

70

99

212

382

602

1,250

200

NA

18

37

65

92

197

355

560

1,170

250

NA

16

33

58

82

175

315

496

1,030

300

NA

15

30

52

74

158

285

449

936

350

NA

14

28

48

68

146

262

414

861

400

NA

13

26

45

63

136

244

385

801

450

NA

12

24

42

60

127

229

361

752

500

NA

11

23

40

56

120

216

341

710

550

NA

11

22

38

53

114

205

324

674

600

NA

10

21

36

51

109

196

309

643

650

NA

NA

20

34

49

104

188

296

616

700

NA

NA

19

33

47

100

180

284

592

750

NA

NA

18

32

45

96

174

274

570

800

NA

NA

18

31

44

93

168

264

551

850

NA

NA

17

30

42

90

162

256

533

900

NA

NA

17

29

41

87

157

248

517

950

NA

NA

16

28

40

85

153

241

502

1,000

NA

NA

16

27

39

83

149

234

488

1,100

NA

NA

15

26

37

78

141

223

464

1,200

NA

NA

14

25

35

75

135

212

442

1,300

NA

NA

14

24

34

72

129

203

423

1,400

NA

NA

13

23

32

69

124

195

407

1,500

NA

NA

13

22

31

66

119

188

392

1,600

NA

NA

12

21

30

64

115

182

378

1,700

NA

NA

12

20

29

62

112

176

366

1,800

NA

NA

11

20

28

60

108

170

355

1,900

NA

NA

11

19

27

58

105

166

345

2,000

NA

NA

11

19

27

57

102

161

335

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    NA means a flow of less than 10,000 Btu/h.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(31) SEMIRIGID COPPER TUBING

Gas

Undiluted Propane

Inlet Pressure

2.0 psi

Pressure Drop

1.0 psi

Specific Gravity

1.50

INTENDED USE

Tube sizing between 2 psig service and line pressure regulator.

TUBE SIZE (inch)

Nominal

K & L

1/4

3/8

1/2

5/8

3/4

1

1 1/4

1 1/2

2

ACR

3/8

1/2

5/8

3/4

7/8

1 1/8

1 3/8

Outside

0.375

0.500

0.625

0.750

0.875

1.125

1.375

1.625

2.125

Inside

0.305

0.402

0.527

0.652

0.745

0.995

1.245

1.481

1.959

Length (ft)

Capacity in Thousands of Btu per Hour

10

413

852

1,730

3,030

4,300

9,170

16,500

26,000

54,200

20

284

585

1,190

2,080

2,950

6,310

11,400

17,900

37,300

30

228

470

956

1,670

2,370

5,060

9,120

14,400

29,900

40

195

402

818

1,430

2,030

4,330

7,800

12,300

25,600

50

173

356

725

1,270

1,800

3,840

6,920

10,900

22,700

60

157

323

657

1,150

1,630

3,480

6,270

9,880

20,600

70

144

297

605

1,060

1,500

3,200

5,760

9,090

18,900

80

134

276

562

983

1,390

2,980

5,360

8,450

17,600

90

126

259

528

922

1,310

2,790

5,030

7,930

16,500

100

119

245

498

871

1,240

2,640

4,750

7,490

15,600

125

105

217

442

772

1,100

2,340

4,210

6,640

13,800

150

95

197

400

700

992

2,120

3,820

6,020

12,500

175

88

181

368

644

913

1,950

3,510

5,540

11,500

200

82

168

343

599

849

1,810

3,270

5,150

10,700

250

72

149

304

531

753

1,610

2,900

4,560

9,510

300

66

135

275

481

682

1,460

2,620

4,140

8,610

350

60

124

253

442

628

1,340

2,410

3,800

7,920

400

56

116

235

411

584

1,250

2,250

3,540

7,370

450

53

109

221

386

548

1,170

2,110

3,320

6,920

500

50

103

209

365

517

1,110

1,990

3,140

6,530

550

47

97

198

346

491

1,050

1,890

2,980

6,210

600

45

93

189

330

469

1,000

1,800

2,840

5,920

650

43

89

181

316

449

959

1,730

2,720

5,670

700

41

86

174

304

431

921

1,660

2,620

5,450

750

40

82

168

293

415

888

1,600

2,520

5,250

800

39

80

162

283

401

857

1,540

2,430

5,070

850

37

77

157

274

388

829

1,490

2,350

4,900

900

36

75

152

265

376

804

1,450

2,280

4,750

950

35

72

147

258

366

781

1,410

2,220

4,620

1,000

34

71

143

251

356

760

1,370

2,160

4,490

1,100

32

67

136

238

338

721

1,300

2,050

4,270

1,200

31

64

130

227

322

688

1,240

1,950

4,070

1,300

30

61

124

217

309

659

1,190

1,870

3,900

1,400

28

59

120

209

296

633

1,140

1,800

3,740

1,500

27

57

115

201

286

610

1,100

1,730

3,610

1,600

26

55

111

194

276

589

1,060

1,670

3,480

1,700

26

53

108

188

267

570

1,030

1,620

3,370

1,800

25

51

104

182

259

553

1,000

1,570

3,270

1,900

24

50

101

177

251

537

966

1,520

3,170

2,000

23

48

99

172

244

522

940

1,480

3,090

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.

  2. 2.

    Table entries have been rounded to three significant digits.

TABLE 402.4(32) CORRUGATED STAINLESS STEEL TUBING (CSST)

Gas

Undiluted Propane

Inlet Pressure

11.0 in. w.c.

Pressure Drop

0.5 in. w.c.

Specific Gravity

1.50

INTENDED USE: SIZING BETWEEN SINGLE- OR SECOND-STAGE (Low-Pressure) REGULATOR AND THE APPLIANCE SHUTOFF VALVE

TUBE SIZE (EHD)

Flow Designation

13

15

18

19

23

25

30

31

37

39

46

48

60

62

Length (ft)

Capacity in Thousands of Btu per Hour

5

72

99

181

211

355

426

744

863

1,420

1,638

2,830

3,270

5,780

6,550

10

50

69

129

150

254

303

521

605

971

1,179

1,990

2,320

4,110

4,640

15

39

55

104

121

208

248

422

490

775

972

1,620

1,900

3,370

3,790

20

34

49

91

106

183

216

365

425

661

847

1,400

1,650

2,930

3,290

25

30

42

82

94

164

192

325

379

583

762

1,250

1,480

2,630

2,940

30

28

39

74

87

151

177

297

344

528

698

1,140

1,350

2,400

2,680

40

23

33

64

74

131

153

256

297

449

610

988

1,170

2,090

2,330

50

20

30

58

66

118

137

227

265

397

548

884

1,050

1,870

2,080

60

19

26

53

60

107

126

207

241

359

502

805

961

1,710

1,900

70

17

25

49

57

99

117

191

222

330

466

745

890

1,590

1,760

80

15

23

45

52

94

109

178

208

307

438

696

833

1,490

1,650

90

15

22

44

50

90

102

169

197

286

414

656

787

1,400

1,550

100

14

20

41

47

85

98

159

186

270

393

621

746

1,330

1,480

150

11

15

31

36

66

75

123

143

217

324

506

611

1,090

1,210

200

9

14

28

33

60

69

112

129

183

283

438

531

948

1,050

250

8

12

25

30

53

61

99

117

163

254

390

476

850

934

300

8

11

23

26

50

57

90

107

147

234

357

434

777

854

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.

  2. 2.

    EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.

  3. 3.

    Table entries have been rounded to three significant digits.

TABLE 402.4(33) CORRUGATED STAINLESS STEEL TUBING (CSST)

Gas

Undiluted Propane

Inlet Pressure

2.0 psi

Pressure Drop

1.0 psi

Specific Gravity

1.50

INTENDED USE: SIZING BETWEEN 2 PSI SERVICE AND THE LINE PRESSURE REGULATOR

TUBE SIZE (EHD)

Flow Designation

13

15

18

19

23

25

30

31

37

39

46

48

60

62

Length (ft)

Capacity in Thousands of Btu per Hour

10

426

558

927

1,110

1,740

2,170

4,100

4,720

7,130

7,958

15,200

16,800

29,400

34,200

25

262

347

591

701

1,120

1,380

2,560

2,950

4,560

5,147

9,550

10,700

18,800

21,700

30

238

316

540

640

1,030

1,270

2,330

2,690

4,180

4,719

8,710

9,790

17,200

19,800

40

203

271

469

554

896

1,100

2,010

2,320

3,630

4,116

7,530

8,500

14,900

17,200

50

181

243

420

496

806

986

1,790

2,070

3,260

3,702

6,730

7,610

13,400

15,400

75

147

196

344

406

663

809

1,460

1,690

2,680

3,053

5,480

6,230

11,000

12,600

80

140

189

333

393

643

768

1,410

1,630

2,590

2,961

5,300

6,040

10,600

12,200

100

124

169

298

350

578

703

1,260

1,450

2,330

2,662

4,740

5,410

9,530

10,900

150

101

137

245

287

477

575

1,020

1,180

1,910

2,195

3,860

4,430

7,810

8,890

200

86

118

213

248

415

501

880

1,020

1,660

1,915

3,340

3,840

6,780

7,710

250

77

105

191

222

373

448

785

910

1,490

1,722

2,980

3,440

6,080

6,900

300

69

96

173

203

343

411

716

829

1,360

1,578

2,720

3,150

5,560

6,300

400

60

82

151

175

298

355

616

716

1,160

1,376

2,350

2,730

4,830

5,460

500

53

72

135

158

268

319

550

638

1,030

1,237

2,100

2,450

4,330

4,880

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1/2 psi (based on 13 in. w.c. outlet pressure), DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate.

  2. 2.

    CAUTION: Capacities shown in the table might exceed maximum capacity for a selected regulator. Consult with the regulator or tubing manufacturer for guidance.

  3. 3.

    Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.

  4. 4.

    EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.

  5. 5.

    Table entries have been rounded to three significant digits.

TABLE 402.4(34) CORRUGATED STAINLESS STEEL TUBING (CSST)

Gas

Undiluted Propane

Inlet Pressure

5.0 psi

Pressure Drop

3.5 psi

Specific Gravity

1.50

TUBE SIZE (EHD)

Flow Designation

13

15

18

19

23

25

30

31

37

39

46

48

60

62

Length (ft)

Capacity in Thousands of Btu per Hour

10

826

1,070

1,710

2,060

3,150

4,000

7,830

8,950

13,100

14,441

28,600

31,200

54,400

63,800

25

509

664

1,090

1,310

2,040

2,550

4,860

5,600

8,400

9,339

18,000

19,900

34,700

40,400

30

461

603

999

1,190

1,870

2,340

4,430

5,100

7,680

8,564

16,400

18,200

31,700

36,900

40

396

520

867

1,030

1,630

2,030

3,820

4,400

6,680

7,469

14,200

15,800

27,600

32,000

50

352

463

777

926

1,460

1,820

3,410

3,930

5,990

6,717

12,700

14,100

24,700

28,600

75

284

376

637

757

1,210

1,490

2,770

3,190

4,920

5,539

10,300

11,600

20,300

23,400

80

275

363

618

731

1,170

1,450

2,680

3,090

4,770

5,372

9,990

11,200

19,600

22,700

100

243

324

553

656

1,050

1,300

2,390

2,760

4,280

4,830

8,930

10,000

17,600

20,300

150

196

262

453

535

866

1,060

1,940

2,240

3,510

3,983

7,270

8,210

14,400

16,600

200

169

226

393

464

755

923

1,680

1,930

3,050

3,474

6,290

7,130

12,500

14,400

250

150

202

352

415

679

828

1,490

1,730

2,740

3,124

5,620

6,390

11,200

12,900

300

136

183

322

379

622

757

1,360

1,570

2,510

2,865

5,120

5,840

10,300

11,700

400

117

158

279

328

542

657

1,170

1,360

2,180

2,498

4,430

5,070

8,920

10,200

500

104

140

251

294

488

589

1,050

1,210

1,950

2,247

3,960

4,540

8,000

9,110

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. 1.

    Table does not include effect of pressure drop across line regulator. Where regulator loss exceeds 1 psi, DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drop across regulator may vary with the flow rate.

  2. 2.

    CAUTION: Capacities shown in the table might exceed maximum capacity of selected regulator. Consult with the tubing manufacturer for guidance.

  3. 3.

    Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.

  4. 4.

    EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.

  5. 5.

    Table entries have been rounded to three significant digits.

TABLE 402.4(35) POLYETHYLENE PLASTIC PIPE

Gas

Undiluted Propane

Inlet Pressure

11.0 in. w.c.

Pressure Drop

0.5 in. w.c.

Specific Gravity

1.50

INTENDED USE

PE pipe sizing between integral two-stage regulator at tank or second stage (low-pressure regulator) and building.

PIPE SIZE (inch)

Nominal OD

1/2

3/4

1

1 1/4

1 1/2

2

3

4

Designation

SDR 9

SDR 11

SDR 11

SDR 10

SDR 11

SDR 11

SDR 11

SDR 11

Actual ID

0.660

0.860

1.077

1.328

1.554

1.943

2.864

3.682

Length (ft)

Capacity in Thousands of Btu per Hour

10

340

680

1,230

2,130

3,210

5,770

16,000

30,900

20

233

468

844

1,460

2,210

3,970

11,000

21,200

30

187

375

677

1,170

1,770

3,180

8,810

17,000

40

160

321

580

1,000

1,520

2,730

7,540

14,600

50

142

285

514

890

1,340

2,420

6,680

12,900

60

129

258

466

807

1,220

2,190

6,050

11,700

70

119

237

428

742

1,120

2,010

5,570

10,800

80

110

221

398

690

1,040

1,870

5,180

10,000

90

103

207

374

648

978

1,760

4,860

9,400

100

98

196

353

612

924

1,660

4,590

8,900

125

87

173

313

542

819

1,470

4,070

7,900

150

78

157

284

491

742

1,330

3,690

7,130

175

72

145

261

452

683

1,230

3,390

6,560

200

67

135

243

420

635

1,140

3,160

6,100

250

60

119

215

373

563

1,010

2,800

5,410

300

54

108

195

338

510

916

2,530

4,900

350

50

99

179

311

469

843

2,330

4,510

400

46

92

167

289

436

784

2,170

4,190

450

43

87

157

271

409

736

2,040

3,930

500

41

82

148

256

387

695

1,920

3,720

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(36) POLYETHYLENE PLASTIC PIPE

Gas

Undiluted Propane

Inlet Pressure

2.0 psi

Pressure Drop

1.0 psi

Specific Gravity

1.50

INTENDED USE

PE pipe sizing between 2 psig service regulator and line pressure regulator.

PIPE SIZE (inch)

Nominal OD

1/2

3/4

1

1 1/4

1 1/2

2

3

4

Designation

SDR 9

SDR 11

SDR 11

SDR 10

SDR 11

SDR 11

SDR 11

SDR 11

Actual ID

0.660

0.860

1.077

1.328

1.554

1.943

2.864

3.682

Length (ft)

Capacity in Thousands of Btu per Hour

10

3,130

6,260

11,300

19,600

29,500

53,100

147,000

284,000

20

2,150

4,300

7,760

13,400

20,300

36,500

101,000

195,000

30

1,730

3,450

6,230

10,800

16,300

29,300

81,100

157,000

40

1,480

2,960

5,330

9,240

14,000

25,100

69,400

134,100

50

1,310

2,620

4,730

8,190

12,400

22,200

61,500

119,000

60

1,190

2,370

4,280

7,420

11,200

20,100

55,700

108,000

70

1,090

2,180

3,940

6,830

10,300

18,500

51,300

99,100

80

1,010

2,030

3,670

6,350

9,590

17,200

47,700

92,200

90

952

1,910

3,440

5,960

9,000

16,200

44,700

86,500

100

899

1,800

3,250

5,630

8,500

15,300

42,300

81,700

125

797

1,600

2,880

4,990

7,530

13,500

37,500

72,400

150

722

1,450

2,610

4,520

6,830

12,300

33,900

65,600

175

664

1,330

2,400

4,160

6,280

11,300

31,200

60,300

200

618

1,240

2,230

3,870

5,840

10,500

29,000

56,100

250

548

1,100

1,980

3,430

5,180

9,300

25,700

49,800

300

496

994

1,790

3,110

4,690

8,430

23,300

45,100

350

457

914

1,650

2,860

4,320

7,760

21,500

41,500

400

425

851

1,530

2,660

4,020

7,220

12,000

38,600

450

399

798

1,440

2,500

3,770

6,770

18,700

36,200

500

377

754

1,360

2,360

3,560

6,390

17,700

34,200

550

358

716

1,290

2,240

3,380

6,070

16,800

32,500

600

341

683

1,230

2,140

3,220

5,790

16,000

31,000

650

327

654

1,180

2,040

3,090

5,550

15,400

29,700

700

314

628

1,130

1,960

2,970

5,330

14,700

28,500

750

302

605

1,090

1,890

2,860

5,140

14,200

27,500

800

292

585

1,050

1,830

2,760

4,960

13,700

26,500

850

283

566

1,020

1,770

2,670

4,800

13,300

25,700

900

274

549

990

1,710

2,590

4,650

12,900

24,900

950

266

533

961

1,670

2,520

4,520

12,500

24,200

1,000

259

518

935

1,620

2,450

4,400

12,200

23,500

1,100

246

492

888

1,540

2,320

4,170

11,500

22,300

1,200

234

470

847

1,470

2,220

3,980

11,000

21,300

1,300

225

450

811

1,410

2,120

3,810

10,600

20,400

1,400

216

432

779

1,350

2,040

3,660

10,100

19,600

1,500

208

416

751

1,300

1,960

3,530

9,760

18,900

1,600

201

402

725

1,260

1,900

3,410

9,430

18,200

1,700

194

389

702

1,220

1,840

3,300

9,130

17,600

1,800

188

377

680

1,180

1,780

3,200

8,850

17,100

1,900

183

366

661

1,140

1,730

3,110

8,590

16,600

2,000

178

356

643

1,110

1,680

3,020

8,360

16,200

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(37) POLYETHYLENE PLASTIC PIPE

Gas

Undiluted Propane

Inlet Pressure

11.0 in. w.c.

Pressure Drop

0.5 in. w.c.

Specific Gravity

1.50

INTENDED USE

PE pipe sizing between integral two-stage regulator at tank or second stage (low-pressure regulator) and building.

Plastic Tubing Size (CTS) (inch)

Nominal OD

1/2

1

Designation

SDR 7

SDR 11

Actual ID

0.445

0.927

Length (ft)

Capacity in Cubic Feet of Gas per Hour

10

121

828

20

83

569

30

67

457

40

57

391

50

51

347

60

46

314

70

42

289

80

39

269

90

37

252

100

35

238

125

31

211

150

28

191

175

26

176

200

24

164

225

22

154

250

21

145

275

20

138

300

19

132

350

18

121

400

16

113

450

15

106

500

15

100

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.0 1745 rad.

Note: Table entries have been rounded to three significant digits.

402.4.1 Longest length method.

The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section.

402.4.2 Branch length method.

Pipe shall be sized as follows:

  1. 1.

    Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section.

  2. 2.

    The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section.

402.4.3 Hybrid pressure.

The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator.

402.5 Noncorrugated stainless steel tubing.

Noncorrugated stainless steel tubing shall be sized in accordance with Equations 4-1 and 4-2 of Section 402.4 in conjunction with Section 402.4.1, 402.4.2 or 402.4.3.

402.6 Allowable pressure drop.

The design pressure loss in a piping system, from the point of delivery to the inlet connection of all appliances served, shall be such that the supply pressure at each appliance inlet is greater than or equal to the minimum pressure required by the appliance.

402.7 Maximum operating pressure.

The maximum operating pressure for piping systems located inside buildings shall not exceed 5 pounds per square inch gauge (psig) (34 kPa gauge) except where one or more of the following conditions are met:

  1. 1.

    The piping joints are welded or brazed.

  2. 2.

    The piping is joined by fittings listed to ANSI LC-4/CSA6.32 and installed in accordance with the manufacturer’s instructions.

  3. 3.

    The piping joints are flanged and pipe-to-flange connections are made by welding or brazing.

  4. 4.

    The piping is located in a ventilated chase or otherwise enclosed for protection against accidental gas accumulation.

  5. 5.

    The piping is located inside buildings or separate areas of buildings used exclusively for any of the following:

    1. 5.1.

      Industrial processing or heating.

    2. 5.2.

      Research.

    3. 5.3.

      Warehousing.

    4. 5.4.

      Boiler or mechanical rooms.

  6. 6.

    The piping is a temporary installation for buildings under construction.

  7. 7.

    The piping serves appliances or equipment used for agricultural purposes.

  8. 8.

    The piping system is an LP-gas piping system with an operating pressure greater than 20 psi (137.9 kPa) and complies with NFPA 58.

402.7.1 Operation below -5°F (-21°C).

LP-gas systems designed to operate below -5°F (-21°C) or with butane or a propane-butane mix shall be designed to either accommodate liquid LP-gas or prevent LP-gas vapor from condensing into a liquid.

Section 403 (IFGS) Piping Materials

403.1 General.

Materials used for piping systems shall comply with the requirements of this chapter or shall be approved.

403.2 Used materials.

Pipe, fittings, valves and other materials shall not be used again except where they are free of foreign materials and have been ascertained to be adequate for the service intended.

403.3 Metallic pipe.

Metallic pipe shall comply with Sections 403.3.1 through 403.3.4.

403.3.1 Cast iron.

Cast-iron pipe shall not be used.

403.3.2 Steel.

Steel, stainless steel and wrought-iron pipe shall be not lighter than Schedule 10 and shall comply with the dimensional standards of ASME B36.10M and one of the following standards:

  1. 1.

    ASTM A53/A53M.

  2. 2.

    ASTM A106.

  3. 3.

    ASTM A312.

403.3.3 Copper and copper alloy.

Copper and copper alloy pipe shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet of gas (0.7 milligrams per 100 liters). Threaded copper, copper alloy and aluminum-alloy pipe shall not be used with gases corrosive to such materials.

403.3.4 Aluminum.

Aluminum-alloy pipe shall comply with ASTM B241 except that the use of alloy 5456 is prohibited. Aluminum-alloy pipe shall be marked at each end of each length indicating compliance. Aluminum-alloy pipe shall be coated to protect against external corrosion where it is in contact with masonry, plaster or insulation, or is subject to repeated wettings by such liquids as water, detergents or sewage. Aluminum-alloy pipe shall not be used in exterior locations or underground.

403.4 Metallic tubing.

Tubing shall not be used with gases corrosive to the tubing material.

403.4.1 Steel tubing.

Steel tubing shall comply with ASTM A254.

403.4.2 Stainless steel.

Stainless steel tubing shall comply with ASTM A268 or ASTM A269.

403.4.3 Copper and copper alloy tubing.

Copper tubing shall comply with Standard Type K or L of ASTM B88 or ASTM B280.

Copper and copper alloy tubing shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet of gas (0.7 milligrams per 100 liters).

403.4.4 Aluminum tubing.

Aluminum-alloy tubing shall comply with ASTM B210 or ASTM B241. Aluminum-alloy tubing shall be coated to protect against external corrosion where it is in contact with masonry, plaster or insulation, or is subject to repeated wettings by such liquids as water, detergent or sewage.

Aluminum-alloy tubing shall not be used in exterior locations or underground.

403.4.5 Corrugated stainless steel tubing.

Corrugated stainless steel tubing shall be listed in accordance with ANSI LC 1/CSA 6.26.

403.5 Plastic pipe, tubing and fittings.

Polyethylene plastic pipe, tubing and fittings used to supply fuel gas shall conform to ASTM D2513. Such pipe shall be marked “Gas” and “ASTM D2513.”

Polyamide pipe, tubing and fittings shall be identified and conform to ASTM F2945. Such pipe shall be marked “Gas” and “ASTM F2945.”

Polyvinyl chloride (PVC) and chlorinated polyvinyl chloride (CPVC) plastic pipe, tubing and fittings shall not be used to supply fuel gas.

403.5.1 Anodeless risers.

Plastic pipe, tubing and anodeless risers shall comply with the following:

  1. 1.

    Factory-assembled anodeless risers shall be recommended by the manufacturer for the gas used and shall be leak tested by the manufacturer in accordance with written procedures.

  2. 2.

    Service head adapters and field-assembled anodeless risers incorporating service head adapters shall be recommended by the manufacturer for the gas used, and shall be designed and certified to meet the requirements of Category I of ASTM D2513, and US Department of Transportation, Code of Federal Regulations, Title 49, Part 192.281(e). The manufacturer shall provide the user with qualified installation instructions as prescribed by the US Department of Transportation, Code of Federal Regulations, Title 49, Part 192.283(b).

403.5.2 LP-gas systems.

The use of plastic pipe, tubing and fittings in undiluted liquefied petroleum gas piping systems shall be in accordance with NFPA 58.

403.5.3 Regulator vent piping.

Plastic pipe and fittings used to connect regulator vents to remote vent terminations shall be PVC conforming to UL 651. PVC vent piping shall not be installed indoors.

403.6 Workmanship and defects.

Gas pipe, tubing and fittings at the time of installation shall meet the following requirements:

  1. 1.

    Gas pipe, tubing and fittings shall be clear and free from cutting burrs and visible defects in structure or threading.

  2. 2.

    Gas pipe, tubing and fittings shall be thoroughly cleaned to remove chip, scale and debris.

  3. 3.

    Visible defects in pipe, tubing and fittings shall not be repaired.

  4. 4.

    Pipe, tubing and fittings with visible defects shall be replaced.

403.7 Protective coating.

Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion-resistant material shall be used. External or internal coatings or linings used on piping or components shall not be considered as adding strength.

403.8 Metallic pipe threads.

Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1.20.1.

403.8.1 Damaged threads.

Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used.

403.8.2 Number of threads.

Field threading of metallic pipe shall be in accordance with Table 403.8.2.

TABLE 403.8.2 SPECIFICATIONS FOR THREADING METALLIC PIPE

IRON PIPE SIZE
(inches)

APPROXIMATE LENGTH OF THREADED PORTION
(inches)

APPROXIMATE NUMBER OF THREADS TO BE CUT

1/2

3/4

10

3/4

3/4

10

1

7/8

10

1 1/4

1

11

1 1/2

1

11

2

1

11

2 1/2

1 1/2

12

3

1 1/2

12

4

1 5/8

13

For SI: 1 inch = 25.4 mm.

403.8.3 Threaded joint sealing.

Threaded joints shall be made using a thread joint sealing material. Thread joint sealing materials shall be nonhardening and shall be resistant to the chemical constituents of the gases to be conducted through the piping. Thread joint sealing materials shall be compatible with the pipe and fitting materials on which the sealing materials are used.

403.9 Metallic piping joints and fittings.

The type of piping joint used shall conform to the following:

  1. 1.

    It shall be suitable for the pressure-temperature conditions.

  2. 2.

    It shall be selected giving consideration to joint tightness and mechanical strength under the service conditions.

  3. 3.

    It shall be able to sustain the maximum forces inclusive of temperature expansion or contraction, vibration, fatigue, internal pressure or the weight of the pipe and its contents.

403.9.1 Pipe joints.

Schedule 40 and heavier pipe joints shall be threaded, flanged, brazed, welded or assembled with press-connect fittings listed in accordance with ANSI LC-4/CSA 6.32. Pipe lighter than Schedule 40 shall be connected using press-connect fittings, flanges, brazing or welding. Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1,000°F (538°C). Brazing alloys shall not contain more than 0.05 percent phosphorus.

403.9.2 Copper tubing joints.

Copper tubing joints shall be assembled with approved gas tubing fittings, shall be brazed with a material having a melting point in excess of 1,000°F (538°C) or assembled with press-connect fittings listed in accordance with ANSI LC-4/CSA 6.32. Brazing alloys shall not contain more than 0.05 percent phosphorus.

403.9.3 Stainless steel tubing joints.

Stainless steel tubing joints shall be welded, assembled with approved tubing fittings, brazed with a material having a melting point in excess of 1,000°F (578°C), or assembled with press-connect fittings listed in accordance with ANSI LC-4/CSA 6.32.

403.9.4 Flared joints.

Flared joints shall be used only in systems constructed from nonferrous pipe and tubing where experience or tests have demonstrated that the joint is suitable for the conditions and where provisions are made in the design to prevent separation of the joints.

403.9.5 Metallic fittings.

Metallic fittings shall comply with the following:

  1. 1.

    Threaded fittings in sizes larger than 4 inches (102 mm) shall not be used.

  2. 2.

    Fittings used with steel, stainless steel or wrought-iron pipe shall be steel, stainless steel, copper alloy, malleable iron or cast iron.

  3. 3.

    Fittings used with copper or copper alloy pipe shall be copper or copper alloy.

  4. 4.

    Fittings used with aluminum-alloy pipe shall be of aluminum alloy.

  5. 5.

    Cast-iron fittings:

    1. 5.1.

      Flanges shall be permitted.

    2. 5.2.

      Bushings shall not be used.

    3. 5.3.

      Fittings shall not be used in systems containing flammable gas-air mixtures.

    4. 5.4.

      Fittings in sizes 4 inches (102 mm) and larger shall not be used indoors except where approved.

    5. 5.5.

      Fittings in sizes 6 inches (152 mm) and larger shall not be used except where approved.

  6. 6.

    Aluminum-alloy fittings. Threads shall not form the joint seal.

  7. 7.

    Zinc aluminum-alloy fittings. Fittings shall not be used in systems containing flammable gas-air mixtures.

  8. 8.

    Special fittings. Fittings such as couplings, proprietary-type joints, saddle tees, gland-type compression fittings and flared, flareless and compression-type tubing fittings shall be: used within the fitting manufacturer’s pressure-temperature recommendations; used within the service conditions anticipated with respect to vibration, fatigue, thermal expansion and contraction; and shall be approved.

  9. 9.

    Where pipe fittings are drilled and tapped in the field, the operation shall be in accordance with all of the following:

    1. 9.1.

      The operation shall be performed on systems having operating pressures of 5 psi (34.5 kPa) or less.

    2. 9.2.

      The operation shall be performed by the gas supplier or the gas supplier’s designated representative.

    3. 9.3.

      The drilling and tapping operation shall be performed in accordance with written procedures prepared by the gas supplier.

    4. 9.4.

      The fittings shall be located outdoors.

    5. 9.5.

      The tapped fitting assembly shall be inspected and proven to be free of leakage.

403.10 Plastic pipe, joints and fittings.

Plastic pipe, tubing and fittings shall be joined in accordance with the manufacturer’s instructions. Such joint shall comply with the following:

  1. 1.

    The joint shall be designed and installed so that the longitudinal pull-out resistance of the joint will be greater than or equal to the tensile strength of the plastic piping material.

  2. 2.

    Heat-fusion joints shall be made in accordance with qualified procedures that have been established and proven by test to produce gas-tight joints as strong as or stronger than the pipe or tubing being joined. Joints shall be made with the joining method recommended by the pipe manufacturer. Polyethylene heat fusion fittings shall be marked “ASTM D2513.” Polyamide heat fusion fittings shall be marked “ASTM F2945.”

  3. 3.

    Where compression-type mechanical joints are used, the gasket material in the fitting shall be compatible with the plastic piping and with the gas distributed by the system. An internal tubular rigid stiffener shall be used in conjunction with the fitting. The stiffener shall be flush with the end of the pipe or tubing and shall extend to or beyond the outside end of the compression fitting when installed. The stiffener shall be free of rough or sharp edges and shall not be a force-fit in the plastic. Split tubular stiffeners shall not be used.

  4. 4.

    Plastic piping joints and fittings for use in liquefied petroleum gas piping systems shall be in accordance with NFPA 58.

403.11 Flanges.

Flanges and flange gaskets shall comply with Sections 403.11.1 through 403.11.7.

403.11.1 Cast iron.

Cast-iron flanges shall be in accordance with ASME B16.1.

403.11.2 Steel.

Steel flanges shall be in accordance with ASME B16.5 or ASME B16.47.

403.11.3 Nonferrous.

Nonferrous flanges shall be in accordance with ASME B16.24 except listed components using aluminum flange connections constructed in accordance with the dimensional specifications of ANSI/ASME B16.5.

403.11.4 Ductile iron.

Ductile-iron flanges shall be in accordance with ASME B16.42.

403.11.5 Raised face.

Raised face flanges shall not be joined to flat faced cast-iron, ductile-iron or nonferrous material flanges.

403.11.6 Flange facings.

Standard facings shall be permitted for use under this code. Where 150-pound (1034 kPa) pressure-rated steel flanges are bolted to Class 125 cast-iron flanges, the raised face on the steel flange shall be removed.

403.11.7 Lapped flanges.

Lapped flanges shall be used only above ground or in exposed locations accessible for inspection.

403.12 Flange gaskets.

Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), composition, aluminum “O” rings, spiral wound metal gaskets, rubber-faced phenolic and elastomeric. Where a flanged joint is opened, the gasket shall be replaced. Full-face flange gaskets shall be used with all nonsteel flanges.

403.12.1 Flanges.

When flanges are separated and before gaskets are replaced, the following shall be met:

  1. 1.

    Flange faces shall be cleaned.

  2. 2.

    Flange surfaces shall be inspected for pitting, corrosion and other surface defects.

  3. 3.

    Flanges that contain pitting, corrosion and other surface defects on faces shall be repaired or replaced.

403.12.2 Metallic gaskets.

Metallic flange gaskets shall be in accordance with ASME B16.20.

403.12.3 Nonmetallic gaskets.

Nonmetallic flange gaskets shall be in accordance with ASME B16.21.

Section 404 (IFGC) Piping System Installation

404.1 Installation of materials.

Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manufacturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply.

404.2 CSST.

CSST piping systems shall be installed in accordance with the terms of their approval, the conditions of listing, the manufacturer’s instructions and this code.

404.3 Prohibited locations.

Piping shall not be installed in or through a ducted supply, return or exhaust, or a clothes chute, chimney or gas vent, dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not extend through any townhouse unit other than the unit served by such piping.

404.4 Piping in solid partitions and walls.

Concealed piping shall not be located in solid partitions and solid walls, unless installed in a chase or casing.

404.5 Fittings in concealed locations.

Fittings installed in concealed locations shall be limited to the following types:

  1. 1.

    Threaded elbows, tees, couplings, plugs and caps.

  2. 2.

    Brazed fittings.

  3. 3.

    Welded fittings.

  4. 4.

    Fittings listed to ANSI LC-1/CSA 6.26 or ANSI LC-4/CSA 6.32.

404.6 Piping through foundation wall.

Underground piping where installed below grade through the foundation or basement wall of a building, shall be encased in a protective pipe sleeve. The annular space between the gas piping and the sleeve shall be sealed.

404.7 Protection against physical damage.

Where piping will be concealed within light-frame construction assemblies, the piping shall be protected against penetration by fasteners in accordance with Sections 404.7.1 through 404.7.3.

Exception: Black steel piping and galvanized steel piping shall not be required to be protected.

404.7.1 Piping through holes or notches.

Where piping is installed through holes or notches in framing members and the piping is located less than 1 1/2 inches (38 mm) from the framing member face to which wall, ceiling or floor membranes will be attached, the pipe shall be protected by shield plates that cover the width of the pipe and the framing member. Where the framing member that the piping passes through is a bottom plate, bottom track, top plate or top track, the shield plates shall cover the framing member and extend not less than 4 inches (102 mm) above the bottom framing member and not less than 4 inches (102 mm) below the top framing member.

404.7.2 Piping installed in other locations.

This section has been deleted.

404.7.3 Shield plates.

Shield plates shall be of steel material having a thickness of not less than 0.0575 inch (1.463 mm) (No. 16 gage).

404.8 Piping in solid floors.

Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels, the piping shall be installed in a conduit of Schedule 40 steel, wrought iron, PVC or ABS pipe in accordance with Section 404.8.1 or 404.8.2.

404.8.1 Conduit with one end terminating outdoors.

The conduit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches (51 mm) beyond the point where the pipe emerges from the floor. If the end sealing is capable of withstanding the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such conduit shall extend not less than 4 inches (102 mm) outside the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects.

404.8.2 Conduit with both ends terminating indoors.

Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in a portion of the building with access and shall not be sealed. The conduit shall extend not less than 2 inches (51 mm) beyond the point where the pipe emerges from the floor.

404.9 Above-ground outdoor piping.

Piping installed outdoors shall be elevated not less than 3 1/2 inches (89 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1/2 inches (89 mm) above the roof surface. Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion by coating or wrapping with an inert material. Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed.

404.10 Isolation.

Metallic piping and metallic tubing that conveys fuel gas from an LP-gas storage container shall be provided with an approved dielectric fitting to electrically isolate the underground portion of the pipe or tube from the above-ground portion that enters a building. Such dielectric fitting shall be installed above ground, outdoors.

404.11 Protection against corrosion.

Steel pipe or tubing exposed to corrosive action, such as soil conditions or moisture, shall be protected in accordance Sections 404.11.1 through 404.11.4.

404.11.1 Galvanizing.

This section has been deleted.

404.11.2 Protection methods.

Underground piping shall comply with one or more of the following:

  1. 1.

    The piping shall be made of corrosion-resistant material that is suitable for the environment in which it will be installed.

  2. 2.

    Pipe shall have a factory-applied, electrically-insulating coating. Fittings and joints between sections of coated pipe shall be coated in accordance with the coating manufacturer’s instructions.

  3. 3.

    The piping shall have a cathodic protection system installed and the system shall be monitored and maintained in accordance with an approved program.

404.11.3 Dissimilar metals.

Where dissimilar metals are joined underground, an insulating coupling or fitting shall be used.

404.11.4 Protection of risers.

Steel risers connected to plastic piping shall be cathodically protected by means of a welded anode, except where such risers are anodeless risers.

404.12 Minimum burial depth.

Underground piping systems shall be installed a minimum depth of 12 inches (305 mm) below grade, except as provided for in Section 404.12.1.

404.12.1 Individual outdoor appliances.

Individual lines to outdoor lights, grills and other appliances shall be installed not less than 8 inches (203 mm) below finished grade, provided that such installation is approved and is installed in locations not susceptible to physical damage.

404.13 Trenches.

The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench.

404.14 Piping underground beneath buildings.

Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron, plastic pipe, steel pipe, a piping or encasement system listed for installation beneath buildings, or other approved conduit material designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 or 404.14.2.

404.14.1 Conduit with one end terminating outdoors.

The conduit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches (51 mm) beyond the point where the pipe emerges from the floor. Where the end sealing is capable of withstanding the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such conduit shall extend not less than 4 inches (102 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects.

404.14.2 Conduit with both ends terminating indoors.

Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in a portion of the building with access and shall not be sealed. The conduit shall extend not less than 2 inches (51 mm) beyond the point where the pipe emerges from the floor.

404.15 Outlet closures.

Gas outlets that do not connect to appliances shall be capped gastight.

Exception: Listed and labeled flush-mounted-type quick-disconnect devices and listed and labeled gas convenience outlets shall be installed in accordance with the manufacturer’s instructions.

404.16 Location of outlets.

The unthreaded portion of piping outlets shall extend not less than 1 inch (25 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches (51 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed.

Exception: Listed and labeled flush-mounted-type quick-disconnect devices and listed and labeled gas convenience outlets shall be installed in accordance with the manufacturer’s instructions.

404.17 Plastic pipe.

The installation of plastic pipe shall comply with Sections 404.17.1 through 404.17.3.

404.17.1 Limitations.

Plastic pipe shall be installed outdoors underground only. Plastic pipe shall not be used within or under any building or slab or be operated at pressures greater than 100 psig (689 kPa) for natural gas or 30 psig (207 kPa) for LP-gas.

Exceptions:

  1. 1.

    Plastic pipe shall be permitted to terminate above ground outside of buildings where installed in premanufactured anodeless risers or service head adapter risers that are installed in accordance with the manufacturer’s instructions.

  2. 2.

    Plastic pipe shall be permitted to terminate with a wall head adapter within buildings where the plastic pipe is inserted in a piping material for fuel gas use in buildings.

  3. 3.

    Plastic pipe shall be permitted under outdoor patio, walkway and driveway slabs provided that the burial depth complies with Section 404.12.

404.17.2 Connections.

Connections made outdoors and underground between metallic and plastic piping shall be made only with transition fittings conforming to ASTM D2513 Category I or ASTM F1973.

404.17.3 Tracer.

A yellow insulated copper tracer wire or other approved conductor, or a product specifically designed for that purpose, shall be installed adjacent to underground nonmetallic piping. Access shall be provided to the tracer wire or the tracer wire shall terminate above ground at each end of the nonmetallic piping. The tracer wire size shall be not less than 18 AWG and the insulation type shall be suitable for direct burial.

404.18 Pipe debris removal.

The interior of piping shall be clear of debris. The use of a flammable or combustible gas to clean or remove debris from a piping system shall be prohibited.

404.19 Prohibited devices.

A device shall not be placed inside the piping or fittings that will reduce the cross-sectional area or otherwise obstruct the free flow of gas.

Exceptions:

  1. 1.

    Approved gas filters.

  2. 2.

    An approved fitting or device where the gas piping system has been sized to accommodate the pressure drop of the fitting or device.

404.20 Testing of piping.

Before any system of piping is put in service or concealed, it shall be tested to ensure that it is gastight. Testing, inspection and purging of piping systems shall comply with Section 406.

Section 405 (IFGS) Piping Bends and Changes in Direction

405.1 General.

Changes in direction of pipe shall be permitted to be made by the use of fittings, factory bends or field bends.

405.2 Metallic pipe.

Metallic pipe bends shall comply with the following:

  1. 1.

    Bends shall be made only with bending tools and procedures intended for that purpose.

  2. 2.

    Bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage.

  3. 3.

    The longitudinal weld of the pipe shall be near the neutral axis of the bend.

  4. 4.

    Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad).

  5. 5.

    The inside radius of a bend shall be not less than six times the outside diameter of the pipe.

405.3 Plastic pipe.

Plastic pipe bends shall comply with the following:

  1. 1.

    The pipe shall not be damaged and the internal diameter of the pipe shall not be effectively reduced.

  2. 2.

    Joints shall not be located in pipe bends.

  3. 3.

    The radius of the inner curve of such bends shall be not less than 25 times the inside diameter of the pipe.

  4. 4.

    Where the piping manufacturer specifies the use of special bending tools or procedures, such tools or procedures shall be used.

405.4 Elbows.

Factory-made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch (25 mm) in pipe sizes 2 inches (51 mm) and larger.

Section 406 (IFGS) Inspection, Testing and Purging

406.1 General.

Prior to acceptance and initial operation, all piping installations shall be visually inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code.

406.1.1 Inspections.

Inspection shall consist of visual examination during or after manufacture, fabrication, assembly or pressure tests.

406.1.2 Repairs and additions.

In the event repairs or additions are made after the pressure test, the affected piping shall be tested.

Minor repairs and additions shall not be required to be pressure tested provided that the work is inspected and connections are tested with a noncorrosive leak-detecting fluid or other approved leak-detecting methods.

406.1.3 New branches.

Where new branches are installed to new appliances, only the newly installed branches shall be required to be pressure tested. Connections between the new piping and the existing piping shall be tested with a noncorrosive leak-detecting fluid or other approved leak-detecting methods.

406.1.4 Section testing.

A piping system shall be permitted to be tested as a complete unit or in sections. A valve in a line shall not be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed valve system is installed. A valve shall not be subjected to the test pressure unless it can be determined that the valve, including the valve-closing mechanism, is designed to safely withstand the test pressure.

406.1.5 Regulators and valve assemblies.

Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication.

406.1.6 Pipe clearing.

Prior to testing, the interior of the pipe shall be cleared of all foreign material.

406.2 Test medium.

The test medium shall be air, nitrogen, carbon dioxide or an inert gas. Oxygen shall not be used as a test medium.

406.3 Test preparation.

Pipe joints, including welds, shall be left exposed for examination during the test.

Exception: Covered or concealed pipe end joints that have been previously tested in accordance with this code.

406.3.1 Expansion joints.

Expansion joints shall be provided with temporary restraints, if required, for the additional thrust load under test.

406.3.2 Appliance and equipment isolation.

Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested.

406.3.3 Appliance and equipment disconnection.

Where the piping system is connected to appliances or equipment designed for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s).

406.3.4 Valve isolation.

Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliances or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s).

406.3.5 Testing precautions.

Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test.

406.4 Test pressure measurement.

Test pressure shall be measured with a manometer or with a pressure-measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure.

406.4.1 Test pressure.

The test pressure to be used shall be not less than 1 1/2 times the proposed maximum working pressure, but not less than 3 psig (20 kPa gauge). Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.

406.4.2 Test duration.

Test duration shall be not less than 1/2 hour for each 500 cubic feet (14 m3) of pipe volume or fraction thereof. When testing a system having a volume less than 10 cubic feet (0.28 m3) or a system in a single-family dwelling, the test duration shall be not less than 10 minutes. The duration of the test shall not be required to exceed 24 hours.

406.5 Detection of leaks and defects.

The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects.

Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reduction can be readily attributed to some other cause.

406.5.1 Detection methods.

The leakage shall be located by means of a listed combustible gas detector, a noncorrosive leak detection fluid or other approved leak detection methods.

406.5.2 Corrections.

Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested.

406.6 Piping system and equipment leakage check.

Leakage checking of systems and equipment shall be in accordance with Sections 406.6.1 through 406.6.4.

406.6.1 Test gases.

Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406.

406.6.2 Before turning gas on.

During the process of turning gas on into a system of new gas piping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped.

406.6.3 Leak check.

Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for leakage. Where leakage is indicated, the gas supply shall be shut off until the necessary repairs have been made.

406.6.4 Placing appliances and equipment in operation.

Appliances and equipment shall not be placed in operation until after the piping system has been checked for leakage in accordance with Section 406.6.3, the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage.

406.7 Purging.

The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3.

406.7.1 Piping systems required to be purged outdoors.

The purging of piping systems shall be in accordance with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following:

  1. 1.

    The design operating gas pressure is greater than 2 psig (13.79 kPa).

  2. 2.

    The piping being purged contains one or more sections of pipe or tubing meeting the size and length criteria of Table 406.7.1.1.

406.7.1.1 Removal from service.

Where existing gas piping is opened, the section that is opened shall be isolated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas.

TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING

NOMINAL PIPE SIZE (inches)a

LENGTH OF PIPING (feet)

≥ 2 1/2 < 3

> 50

≥ 3 < 4

> 30

≥ 4 < 6

> 15

≥ 6 < 8

> 10

≥ 8

Any length

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

a. CSST EHD size of 62 is equivalent to nominal 2-inch pipe or tubing size.

406.7.1.2 Placing in operation.

Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3.

406.7.1.3 Outdoor discharge of purged gases.

The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements:

  1. 1.

    The point of discharge shall be controlled with a shutoff valve.

  2. 2.

    The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings, and not less than 25 feet (7620 mm) from mechanical air intake openings.

  3. 3.

    During discharge, the open point of discharge shall be continuously attended and monitored with a combustible gas indicator that complies with Section 406.7.1.4.

  4. 4.

    Purging operations introducing fuel gas shall be stopped when 90 percent fuel gas by volume is detected within the pipe.

  5. 5.

    Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of discharge.

406.7.1.4 Combustible gas indicator.

Combustible gas indicators shall be listed and shall be calibrated in accordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 100 percent in 1 percent or smaller increments.

406.7.2 Piping systems allowed to be purged indoors or outdoors.

The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the following:

  1. 1.

    The design operating gas pressure is 2 psig (13.79 kPa) or less.

  2. 2.

    The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1.

406.7.2.1 Purging procedure.

The piping system shall be purged in accordance with one or more of the following:

  1. 1.

    The piping shall be purged with fuel gas and shall discharge to the outdoors.

  2. 2.

    The piping shall be purged with fuel gas and shall discharge to the indoors or outdoors through an appliance burner not located in a combustion chamber. Such burner shall be provided with a continuous source of ignition.

  3. 3.

    The piping shall be purged with fuel gas and shall discharge to the indoors or outdoors through a burner that has a continuous source of ignition and that is designed for such purpose.

  4. 4.

    The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Section 406.7.2.2. Purging shall be stopped when fuel gas is detected.

  5. 5.

    The piping shall be purged by the gas supplier in accordance with written procedures.

406.7.2.2 Combustible gas detector.

Combustible gas detectors shall be listed and shall be calibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas.

406.7.3 Purging appliances and equipment.

After the piping system has been placed in operation, appliances and equipment shall be purged before being placed into operation.

406.7.3.1 Abandoned fuel gas piping.

Where fuel gas piping is removed from service for an indefinite time period, it shall be purged.

Section 407 (IFGC) Piping Support

407.1 General.

Piping shall be provided with support in accordance with Section 407.2.

407.2 Design and installation.

Piping shall be supported with pipe hooks, pipe straps, bands, brackets, hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue strains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP-58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. The components of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping.

Section 408 (IFGC) Drips and Sloped Piping

408.1 Slopes.

Piping for other than dry gas conditions shall be sloped not less than 1/4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps.

408.2 Drips.

Where wet gas exists, a drip shall be provided at any point in the line of pipe where condensate could collect. A drip shall be provided at the outlet of the meter and shall be installed so as to constitute a trap wherein an accumulation of condensate will shut off the flow of gas before the condensate will run back into the meter.

408.3 Location of drips.

Drips shall be provided with ready access to permit cleaning or emptying. A drip shall not be located where the condensate is subject to freezing.

408.4 Sediment trap.

Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitting having a capped nipple of any length installed vertically in the bottommost opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appliances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped.

FIGURE 408.4 METHOD OF INSTALLING A TEE FITTING SEDIMENT TRAP
GAFGC2024V1.0_Pt03_Ch04_Sec408.4_FigR4084.svg

Section 409 (IFGC) Shutoff Valves

409.1 General.

Piping systems shall be provided with shutoff valves in accordance with this section.

409.1.1 Valve approval.

Shutoff valves shall be of an approved type; shall be constructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table 409.1.1.

TABLE 409.1.1 MANUAL GAS VALVE STANDARDS

VALVE STANDARDS

APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1/2 psig PRESSURE

OTHER VALVE APPLICATIONS

UP TO 1/2 psig PRESSURE

UP TO 2 psig PRESSURE

UP TO 5 psig PRESSURE

UP TO 125 psig PRESSURE

ANSI Z21.15/CSA 9.1

X

ASME B16.44

X

X

Xa

Xb

ASME B16.33

X

X

X

X

X

For SI: 1 pound per square inch gauge = 6.895 kPa.

  1. a.

    If labeled 2G.

  2. b.

    If labeled 5G.

409.1.2 Prohibited locations.

Shutoff valves shall be prohibited in concealed locations and furnace plenums.

409.1.3 Access to shutoff valves.

Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage.

409.2 Meter valve.

Every meter shall be equipped with a shutoff valve located on the supply side of the meter.

409.2.1 System shutoff valve.

Where the point of delivery is the outlet of the service meter assembly, or the outlet of the service regulator, a system shutoff valve shall be installed in accordance with the following:

  1. 1.

    The system shutoff valve shall be installed downstream in the piping as close as practical to the point of delivery.

  2. 2.

    The system shutoff valve shall not be located indoors.

  3. 3.

    The system shutoff valve shall be installed in a location with ready access.

  4. 4.

    Where a system shutoff valve is provided after the outlet of the service meter assembly, such valve shall be considered to be downstream of the point of delivery.

Such valve is considered to be part of the customer piping system.

409.3 Shutoff valves for multiple-house line systems.

Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall be provided for each building or tenant.

409.3.1 Multiple-tenant buildings.

In multiple-tenant buildings, where a common piping system is installed to supply other than one- and two-family dwellings, shutoff valves shall be provided for each tenant. Each tenant shall have access to the shutoff valve serving that tenant’s space.

409.3.2 Individual buildings.

In a common system serving more than one building, shutoff valves shall be installed outdoors at each building.

409.3.3 Identification of shutoff valves.

Each house line shutoff valve shall be plainly marked with an identification tag attached by the installer so that the piping systems supplied by such valves are readily identified.

409.4 MP regulator valves.

A listed shutoff valve shall be installed immediately ahead of each MP regulator.

409.5 Appliance shutoff valve.

Each appliance shall be provided with a shutoff valve in accordance with Section 409.5.1, 409.5.2 or 409.5.3.

409.5.1 Located within same room.

The shutoff valve shall be located in the same room as the appliance. The shutoff valve shall be within 6 feet (1829 mm) of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access. Shutoff valves serving movable appliances, such as cooking appliances and clothes dryers, shall be considered to be provided with access where installed behind such appliances. Appliance shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions.

409.5.2 Vented decorative appliances and room heaters.

Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall not serve another appliance. The piping from the shutoff valve to within 6 feet (1829 mm) of the appliance shall be designed, sized and installed in accordance with Sections 401 through 408.

409.5.3 Located at manifold.

Where the appliance shutoff valve is installed at a manifold, such shutoff valve shall be located within 50 feet (15 240 mm) of the appliance served and shall have ready access and be permanently identified. The piping from the manifold to within 6 feet (1829 mm) of the appliance shall be designed, sized and installed in accordance with Sections 401 through 408.

409.6 Shutoff valve for laboratories.

Where provided with two or more fuel gas outlets, including table-, bench- and hoodmounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through which all such gas outlets shall be supplied. The dedicated shutoff valve shall have ready access, be located within the laboratory space served, be located adjacent to the egress door from the space and shall be identified by approved signage stating “Gas Shutoff.”

409.7 Shutoff valves in tubing systems.

Shutoff valves installed in tubing systems shall be rigidly and securely supported independently of the tubing.

Section 410 (IFGC) Flow Controls

410.1 Pressure regulators.

A line pressure regulator shall be installed where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80/CSA 6.22. Access shall be provided to pressure regulators. Pressure regulators shall be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation.

410.2 MP regulators.

MP pressure regulators shall comply with the following:

  1. 1.

    The MP regulator shall be approved and shall be suitable for the inlet and outlet gas pressures for the application.

  2. 2.

    The MP regulator shall maintain a reduced outlet pressure under lock-up (no-flow) conditions.

  3. 3.

    The capacity of the MP regulator, determined by published ratings of its manufacturer, shall be adequate to supply the appliances served.

  4. 4.

    The MP pressure regulator shall be provided with access. Where located indoors, the regulator shall be vented to the outdoors or shall be equipped with a leak-limiting device, in either case complying with Section 410.3.

  5. 5.

    A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure-measuring instrument and to serve as a sediment trap.

  6. 6.

    A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure-measuring instrument. The tee fitting is not required where the MP regulator serves an appliance that has a pressure test port on the gas control inlet side and the appliance is located in the same room as the MP regulator.

  7. 7.

    Where connected to rigid piping, a union shall be installed within 1 foot (304 mm) of either side of the MP regulator.

410.3 Venting of regulators.

Pressure regulators that require a vent shall be vented directly to the outdoors. The vent shall be designed to prevent the entry of insects, water and foreign objects.

Exception: A vent to the outdoors is not required for regulators equipped with and labeled for utilization with an approved vent-limiting device installed in accordance with the manufacturer’s instructions.

410.3.1 Vent piping.

Vent piping for relief vents and breather vents shall be constructed of materials allowed for gas piping in accordance with Section 403. Vent piping shall be not smaller than the vent connection on the pressure-regulating device. Vent piping serving relief vents and combination relief and breather vents shall be run independently to the outdoors and shall serve only a single device vent. Vent piping serving only breather vents is permitted to be connected in a manifold arrangement where sized in accordance with an approved design that minimizes backpressure in the event of diaphragm rupture. Regulator vent piping shall not exceed the length specified in the regulator manufacturer’s instructions.

410.4 Excess flow valves.

Where automatic excess flow valves are installed, they shall be listed in accordance with ANSI Z21.93/CSA 6.30 and shall be sized and installed in accordance with the manufacturer’s instructions.

410.5 Flashback arrestor check valve.

Where fuel gas is used with oxygen in any hot work operation, a listed protective device that serves as a combination flashback arrestor and backflow check valve shall be installed at an approved location on both the fuel gas and oxygen supply lines. Where the pressure of the piped fuel gas supply is insufficient to ensure such safe operation, approved equipment shall be installed between the gas meter and the appliance that increases pressure to the level required for such safe operation.

Section 411 (IFGC) Appliance and Manufactured Home Connections

411.1 Connecting appliances.

Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following:

  1. 1.

    Rigid metallic pipe and fittings.

  2. 2.

    Corrugated stainless steel tubing (CSST) where installed in accordance with the manufacturer’s instructions.

  3. 3.

    Semirigid metallic tubing and metallic fittings. Lengths shall not exceed 6 feet (1829 mm) and shall be located entirely in the same room as the appliance. Semirigid metallic tubing shall not enter a motor-operated appliance through an unprotected knockout opening.

  4. 4.

    Listed and labeled appliance connectors in compliance with ANSI Z21.24/CSA 6.10 and installed in accordance with the manufacturer’s instructions and located entirely in the same room as the appliance.

  5. 5.

    Listed and labeled quick-disconnect devices in compliance with ANSI Z21.41/CSA 6.9 used in conjunction with listed and labeled appliance connectors.

  6. 6.

    Listed and labeled convenience outlets in compliance with ANSI Z21.90/CSA 6.24 used in conjunction with listed and labeled appliance connectors.

  7. 7.

    Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions.

  8. 8.

    Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect portable outdoor appliances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick-disconnect device or listed gas convenience outlet.

  9. 9.

    Gas hose connectors for use in laboratories and educational facilities in accordance with Section 411.4.

411.1.1 Commercial cooking appliances.

Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.69/CSA 6.16. The commercial cooking appliance connector installation shall be configured in accordance with the manufacturer’s instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s instructions.

411.1.2 Protection against damage.

Connectors and tubing shall be installed so as to be protected against physical damage.

411.1.3 Connector installation.

Appliance fuel connectors shall be installed in accordance with the manufacturer’s instructions and Sections 411.1.3.1 through 411.1.3.4.

411.1.3.1 Maximum length.

Connectors shall have an overall length not to exceed 6 feet (1829 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance.

Exception: Rigid metallic piping used to connect an appliance to the piping system shall be permitted to have a total length greater than 6 feet (1829 mm), provided that the connecting pipe is sized as part of the piping system in accordance with Section 402 and the location of the appliance shutoff valve complies with Section 409.5.

411.1.3.2 Minimum size.

Connectors shall have the capacity for the total demand of the connected appliance.

411.1.3.3 Prohibited locations and penetrations.

Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings.

Exceptions:

  1. 1.

    Connectors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2 or 409.5.3.

  2. 2.

    Rigid steel pipe connectors shall be permitted to extend through openings in appliance housings.

  3. 3.

    Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in accordance with the listing of the appliance.

  4. 4.

    Semirigid tubing and listed connectors shall be permitted to extend through an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage.

411.1.3.4 Shutoff valve.

A shutoff valve not less than the nominal size of the connector shall be installed ahead of the connector in accordance with Section 409.5.

411.1.4 Movable appliances.

Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69/CSA 6.16 or by means of Item 1 of Section 411.1. Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer’s instructions.

411.1.5 (IFGS) Connection of gas engine-powered air conditioners.

Internal combustion engines shall not be rigidly connected to the gas supply piping.

411.1.6 Unions.

A union fitting shall be provided for appliances connected by rigid metallic pipe. Such unions shall have access and be located within 6 feet (1829 mm) of the appliance.

411.2 Manufactured home connections.

Manufactured homes shall be connected to the distribution piping system by one of the following materials:

  1. 1.

    Metallic pipe in accordance with Section 403.3.

  2. 2.

    Metallic tubing in accordance with Section 403.4.

  3. 3.

    Listed and labeled connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions.

411.3 Suspended low-intensity infrared tube heaters.

Suspended low-intensity infrared tube heaters shall be connected to the building piping system with a connector listed for the application complying with ANSI Z21.24/CSA 6.10. The connector shall be installed as specified by the tube heater manufacturer’s instructions.

411.4 Injection Bunsen-type burners.

Injection Bunsen-type burners used in laboratories and educational facilities shall be connected to the gas supply system by either a listed or unlisted hose.

Section 412 (IFGC) Liquefied Petroleum Gas Motor Vehicle Fuel-Dispensing Facilities

[F] 412.1 General.

Under Georgia law, the Rules and Regulations of the Georgia Safety Fire Commissioner’s Office govern the storage, delivery and dispensing of Liquefied Petroleum Gas. Refer to the Rules and Regulations of the Georgia Safety Fire Commissioner’s Office and NFPA 58 as adopted and amended for all requirements concerning liquefied petroleum gas motor vehicle fuel-dispensing facilities.

Section 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities

[F] 413.1 General.

Under Georgia law, the Rules and Regulations of the Georgia Safety Fire Commissioner govern the storage, delivery and dispensing of compressed natural gas. Refer to the Rules and Regulations of the Georgia Safety Fire Commissioner and NFPA 52 as adopted and amended for all requirements concerning compressed natural gas motor vehicle fuel-dispensing stations.

Section 414 (IFGC) Supplemental and Standby Gas Supply

414.1 Use of air or oxygen under pressure.

Where air or oxygen under pressure is used in connection with the gas supply, effective means such as a backpressure regulator and relief valve shall be provided to prevent air or oxygen from passing back into the gas piping. Where oxygen is used, installation shall be in accordance with NFPA 51.

414.2 Interconnections for standby fuels.

Where supplementary gas for standby use is connected downstream from a meter or a service regulator where a meter is not provided, a device to prevent backflow shall be installed. A three-way valve installed to admit the standby supply and at the same time shut off the regular supply shall be permitted to be used for this purpose.

Section 415 (IFGS) Piping Support Intervals

415.1 Interval of support.

Piping shall be supported at intervals not exceeding the spacing specified in Table 415.1. Spacing of supports for CSST shall be in accordance with the CSST manufacturer’s instructions.

TABLE 415.1 SUPPORT OF PIPING

STEEL PIPE, NOMINAL SIZE OF PIPE (inches)

SPACING OF SUPPORTS (feet)

NOMINAL SIZE OF TUBING (SMOOTH-WALL) (inch O.D.)

SPACING OF SUPPORTS (feet)

1/2

6

1/2

4

3/4 or 1

8

5/8 or 3/4

6

1 1/4 or larger (horizontal)

10

7/8 or 1 (horizontal)

8

1 1/4 or larger (vertical)

Every floor level

1 or larger (vertical)

Every floor level

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

Section 416 (IFGS) Overpressure Protection Devices

416.1 Where required.

Where the serving gas supplier delivers gas at a pressure greater than 2 psi for piping systems serving appliances designed to operate at a gas pressure of 14 inches w.c. or less, overpressure protection devices shall be installed. Piping systems serving equipment designed to operate at inlet pressures greater than 14 inches w.c. shall be equipped with overpressure protection devices as required by the appliance manufacturer’s installation instructions.

416.2 Pressure limitation requirements.

The requirements for pressure limitation shall be in accordance with Sections 416.2.1 through 416.2.5.

416.2.1 Pressure under 14 inches w.c.

Where piping systems serving appliances designed to operate with a gas supply pressure of 14 inches w.c. or less are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance to 2 psi or less upon a failure of the line pressure regulator.

416.2.2 Pressure over 14 inches w.c.

Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches w.c. are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s installation instructions.

416.2.3 Device capability.

Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by this Section 416.2.1, independently of any other pressure control equipment in the piping system.

416.2.4 Failure detection.

Each gas piping system for which an overpressure protection device is required by Section 416 shall be designed and installed so that a failure of the primary pressure control device(s) is detectable.

416.2.5 Relief valve.

Where a pressure relief valve is used to meet the requirements of Section 416, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 416.2.1 under all of the following conditions:

  1. 1.

    The line pressure regulator for which the relief valve is providing overpressure protection has failed wide open.

  2. 2.

    The gas pressure at the inlet of the line pressure regulator for which the relief valve is providing over-pressure protection is not less than the regulator’s normal operating inlet pressure.

416.3 Overpressure protection devices.

Overpressure protection devices shall be one of the following:

  1. 1.

    Pressure relief valve.

  2. 2.

    Monitoring regulator.

  3. 3.

    Series regulator installed upstream from the line regulator and set to continuously limit the pressure on the inlet of the line regulator.

  4. 4.

    Automatic shutoff device installed in series with the line pressure regulator and designed so that it will remain closed until manually reset.

The devices specified in this section shall be installed either as an integral part of the service or line pressure regulator or as separate units. Where separate overpressure protection devices are installed, they shall comply with Sections 416.3.1 through 416.3.6.

416.3.1 Construction and installation.

Overpressure protection devices shall be constructed of materials so that the operation of the devices will not be impaired by corrosion of external parts by the atmosphere or of internal parts by the gas. Overpressure protection devices shall be designed and installed so that they can be operated to determine whether the valve is free. The devices shall be designed and installed so that they can be tested to determine the pressure at which they will operate and examined for leakage when in the closed position.

416.3.2 External control piping.

External control piping shall be designed and installed so that damage to the control piping of one device will not render both the regulator and the overpressure protection device inoperative.

416.3.3 Setting.

Each overpressure protection device shall be set so that the gas pressure supplied to the connected appliances does not exceed the limits specified in Sections 416.2.1 and 416.2.2.

416.3.4 Unauthorized operation.

Where unauthorized operation of any shutoff valve could render an overpressure protection device inoperative, one of the following shall be accomplished:

  1. 1.

    The valve shall be locked in the open position. Authorized personnel shall be instructed in the importance of leaving the shutoff valve open and of being present while the shutoff valve is closed so that it can be locked in the open position before leaving the premises.

  2. 2.

    Duplicate relief valves shall be installed, each having adequate capacity to protect the system, and the isolating valves and three-way valves shall be arranged so that only one relief valve can be rendered inoperative at a time.

416.3.5 Vents.

The discharge stacks, vents and outlet parts of all overpressure protection devices shall be located so that gas is safely discharged to the outdoors. Discharge stacks and vents shall be designed to prevent the entry of water, insects and other foreign material that could cause blockage. The discharge stack or vent line shall be not less than the same size as the outlet of the pressure-relieving device.

416.3.6 Size of fittings, pipe and openings.

The fittings, pipe and openings located between the system to be protected and the pressure-relieving device shall be sized to prevent hammering of the valve and to prevent reduction of relief capacity.