Friedman Edge Reading Room · 2024 GA IBC

Appendix L Earthquake Recording Instrumentation

State amendments integrated7 filed sections2024 editionEffective January 1, 2026
Browse this code

Appendix L Earthquake Recording Instrumentation

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.

Section L101 General

L101.1 General.

Every structure located where the 1-second spectral response acceleration, S1, determined in accordance with Chapter 11 of ASCE/SEI 7, is greater than 0.40 and either exceeds six stories in height with an aggregate floor area of 60,000 square feet (5574 m2) or more, or exceeds 10 stories in height regardless of floor area, shall be equipped with not fewer than three approved recording accelerographs. The accelerographs shall be interconnected for common start and common timing.

L101.2 Location.

As a minimum, instruments shall be located at the lowest level, mid-height, and near the top of the structure. Each instrument shall be located so that access is maintained at all times and is unobstructed by room contents. A sign stating “MAINTAIN CLEAR ACCESS TO THIS INSTRUMENT” in 1-inch (25 mm) block letters shall be posted in a conspicuous location.

L101.3 Maintenance.

Maintenance and service of the instrumentation shall be provided by the owner of the structure. Data produced by the instrument shall be made available to the building official on request.

Maintenance and service of the instruments shall be performed annually by an approved testing agency. The owner shall file with the building official a written report from an approved testing agency certifying that each instrument has been serviced and is in proper working condition. This report shall be submitted when the instruments are installed and annually thereafter. Each instrument shall have affixed to it an externally visible tag specifying the date of the last maintenance or service and the printed name and address of the testing agency.

Section L102 Referenced Standards

L102.1 General.

See Table L102.1 for standards that are referenced in various sections of this appendix. Standards are listed by the standard identification with the effective date, standard title, and the section or sections of this appendix that reference the standard.

TABLE L102.1 REFERENCED STANDARDS

STANDARD ACRONYM

STANDARD NAME

SECTIONS HEREIN REFERENCED

ASCE/SEI 7—22

Minimum Design Loads and Associated Criteria for Buildings and Other Structures with Supplement No. 1

L101.1

Source and transcript record

Record Georgia · 2024 IBC · Appendix L Earthquake Recording Instrumentation

Effective January 1, 2026 · source captured Aug 30, 2026

Transcript SHA-256 48ab4a2f9fd08e6c6b764a0eacfaa026fcb58f1e4c176c9349eee81a1f27d993 · text SHA-256 776e0c1d02a99a3955348ee0c98fb9dc7dcea46f6ce3dfb2fc1947427a4fe92d

Adoption authority · Official amendments · ICC chapter source